ELE05-03226
| Final | 9/2/2005 | 9/2/2005 | 9/2/2005 4:16:35 PM | P | NH |
|
|
carrie ###-#### notice posted
|
ELE05-03226
| Permanent Service | 9/2/2005 | 9/2/2005 | 9/2/2005 4:16:05 PM | P | NH |
|
|
carrie ###-#### notice posted
|
ELE05-02878
| Electrical Rough-In | 9/1/2005 | 9/2/2005 | 9/2/2005 3:56:03 PM | P | PASS |
|
|
underground//jeff blake; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa ok
|
ELE05-01437
| Electrical Rough-In | 9/2/2005 | 9/2/2005 | 9/2/2005 3:55:41 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 9/2/2005 at 8:07:36 AM. Contact: ###-####. rest rm ceilings ok
|
ELE05-03215
| Electrical Rough-In | 9/2/2005 | 9/2/2005 | 9/2/2005 3:10:26 PM | P | PART |
|
|
Partial Underground Inspection ; Phone #: ###-#### Internet Inspection Request from: Cathy Felin ok
|
ELE05-03204
| Rough-In Permanent Service | 9/2/2005 | 9/2/2005 | 9/2/2005 2:33:44 PM | P | FAIL |
|
|
jaime or ###-####; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa conference box fill 300.4 410.8 210.52(A) needs plans at job site u/g needs to 18"
|
ELE05-02363
| Final | 9/1/2005 | 9/2/2005 | 9/2/2005 1:51:36 PM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 9/1/2005 at 4:22:57 PM. Contact: ###-####. cor. posted called680.23(F) no UF cable allowed,680.26 complete all bonding,362.22 3/4" ent too much wire fill, 110.26(F)(2) clearence foe panel by pool equip, or make jbox out of it, 250.148 grd jbox, uncover all wiring covered before inspection, this is the 2nd time posting this violation
|
ELE05-03213
| Electrical Rough-In | 9/1/2005 | 9/2/2005 | 9/2/2005 10:42:38 AM | A | FAIL |
|
|
ROUGH-IN FOR BATHROOM REMODEL. THANKS; Phone #: ###-#### Internet Inspection Request from: Barry Kendall cor. posted called box fill and nail plates and 11/4"
|
ELE04-02928
| Final | 9/1/2005 | 9/2/2005 | 9/2/2005 10:13:25 AM | A | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: Dana Moyer alloway ok correction posted to home owners of sub division for doing electrical work no permit, covered before inspection, and requires electrical contractor to do work and secure permit double permit fee due called alloway he said he will contact home owners
|
ELE04-03054
| Electrical Rough-In | 9/1/2005 | 9/2/2005 | 9/2/2005 9:37:53 AM | A | PART |
|
|
ROUGH-IN FOR LOBBY & BASEMENT CEILINGS. THANKS; Phone #: ###-#### Internet Inspection Request from: Barry Kendall r/i ok anop
|
ELE05-03136
| Rough-In Permanent Service | 9/1/2005 | 9/2/2005 | 9/2/2005 8:51:25 AM | A | FAIL |
|
|
Internet Inspection Request from: Cevyn Recla cor. posted called 110.26(F) remove phone cable in dedicated space for p/s, 314.17 replace outside recept boxes with broken clamps,210.52(A&B) remove liv rm from kit circuit, and provide required spacing in din rm, 300.4 (A)(1)&(D)
|