Inspections for the day of: Friday, September 2, 2005.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-03226 Final9/2/20059/2/20059/2/2005 4:16:35 PMPNH
carrie ###-#### notice posted
ELE05-03226 Permanent Service9/2/20059/2/20059/2/2005 4:16:05 PMPNH
carrie ###-#### notice posted
ELE05-02878 Electrical Rough-In9/1/20059/2/20059/2/2005 3:56:03 PMPPASS
underground//jeff blake; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa ok
ELE05-01437 Electrical Rough-In9/2/20059/2/20059/2/2005 3:55:41 PMPPASS
Scheduled by a contractor via Hello! on 9/2/2005 at 8:07:36 AM. Contact: ###-####. rest rm ceilings ok
ELE05-03215 Electrical Rough-In9/2/20059/2/20059/2/2005 3:10:26 PMPPART
Partial Underground Inspection ; Phone #: ###-#### Internet Inspection Request from: Cathy Felin ok
ELE05-03204 Rough-In Permanent Service9/2/20059/2/20059/2/2005 2:33:44 PMPFAIL
jaime or ###-####; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa conference box fill 300.4 410.8 210.52(A) needs plans at job site u/g needs to 18"
ELE05-02363 Final9/1/20059/2/20059/2/2005 1:51:36 PMPFAIL
Scheduled by a contractor via Hello! on 9/1/2005 at 4:22:57 PM. Contact: ###-####. cor. posted called680.23(F) no UF cable allowed,680.26 complete all bonding,362.22 3/4" ent too much wire fill, 110.26(F)(2) clearence foe panel by pool equip, or make jbox out of it, 250.148 grd jbox, uncover all wiring covered before inspection, this is the 2nd time posting this violation
ELE05-03213 Electrical Rough-In9/1/20059/2/20059/2/2005 10:42:38 AMAFAIL
ROUGH-IN FOR BATHROOM REMODEL. THANKS; Phone #: ###-#### Internet Inspection Request from: Barry Kendall cor. posted called box fill and nail plates and 11/4"
ELE04-02928 Final9/1/20059/2/20059/2/2005 10:13:25 AMACANC
Phone #: ###-#### Internet Inspection Request from: Dana Moyer alloway ok correction posted to home owners of sub division for doing electrical work no permit, covered before inspection, and requires electrical contractor to do work and secure permit double permit fee due called alloway he said he will contact home owners
ELE04-03054 Electrical Rough-In9/1/20059/2/20059/2/2005 9:37:53 AMAPART
ROUGH-IN FOR LOBBY & BASEMENT CEILINGS. THANKS; Phone #: ###-#### Internet Inspection Request from: Barry Kendall r/i ok anop
ELE05-03136 Rough-In Permanent Service9/1/20059/2/20059/2/2005 8:51:25 AMAFAIL
Internet Inspection Request from: Cevyn Recla cor. posted called 110.26(F) remove phone cable in dedicated space for p/s, 314.17 replace outside recept boxes with broken clamps,210.52(A&B) remove liv rm from kit circuit, and provide required spacing in din rm, 300.4 (A)(1)&(D)