BLD04-03002
| BLD-Final | 9/1/2005 | 9/2/2005 | 9/2/2005 4:06:29 PM | P | CANC |
|
|
Scheduled by a contractor via Hello! on 9/1/2005 at 10:12:35 AM. Contact: ###-####.
|
MIS05-00081
| BLD-Final | 9/2/2005 | 9/2/2005 | 9/2/2005 4:05:25 PM | P | FAIL |
|
|
randy; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa C/N Install hold downs non complying stairs/handrails
|
BLD05-02035
| BLD-Final | 9/2/2005 | 9/2/2005 | 9/2/2005 4:02:16 PM | P | NR |
|
|
nate; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
|
BLD05-02034
| BLD-Final | 9/2/2005 | 9/2/2005 | 9/2/2005 4:01:56 PM | P | NR |
|
|
nate; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
|
BLD05-02037
| BLD-Final | 9/2/2005 | 9/2/2005 | 9/2/2005 4:00:18 PM | P | NR |
|
|
nate; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
|
BLD05-01529
| BLD-Final | 9/1/2005 | 9/2/2005 | 9/2/2005 3:03:26 PM | P | PART |
|
|
darren; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa OK for Temp. OK for Perm Occ. (Structural) when Electr Perm Occ. OK'd
|
BLD05-00810
| BLD-Final | 9/1/2005 | 9/2/2005 | 9/2/2005 1:53:24 PM | P | PASS |
|
|
as late a spossible please///kerry; Phone #: ###-#### Internet Inspection Request from: Barbara Moore C/C issued
|
BLD05-00823
| BLD-Final | 9/1/2005 | 9/2/2005 | 9/2/2005 1:52:39 PM | P | PASS |
|
|
as late a spossible please///kerry; Phone #: ###-#### Internet Inspection Request from: Barbara Moore C/C issued
|
BLD04-02934
| BLD-Foundation | 9/1/2005 | 9/2/2005 | 9/2/2005 1:43:18 PM | A | FAIL |
|
|
foundation wall insp///don; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa Footing poured W/O special insp 3000psi C/N Need (stamped) letter from Eng of record reducing design strength of conc to 2500psi or less, or special insp required. Not accepting (unstamped) letter from Architect waiving special insp because project was simple and as no significance. Verts (#4) lapped less than 40 dia. (approx 12" or less).
|
BLD05-01231
| BLD-Final | 8/31/2005 | 9/2/2005 | 9/2/2005 10:03:14 AM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 8/31/2005 at 3:33:18 PM. Contact: ###-####. Need underfloor insul......Left note.
|
BLD05-02106
| BLD-Conference | 9/1/2005 | 9/2/2005 | 9/2/2005 9:22:49 AM | A | PART |
|
|
david-- call 1st before insp ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie Footing, found and framing OK.......Talked to owners about the need of Electrical permit and inspection before cover. We will check for Electr permit at final.
|
BLD05-00823
| DOC - Permit Finaled | 9/2/2005 | 9/2/2005 | 9/2/2005 12:00:00 AM | P | PASS |
|
|
|
BLD05-00810
| DOC - Permit Finaled | 9/2/2005 | 9/2/2005 | 9/2/2005 12:00:00 AM | P | PASS |
|
|
|