Inspections for the day of: Friday, September 2, 2005.
Number of inspections: 29
Percentage of inspections complete: 97 %
Percentage of inspections not complete: 3 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00209 INSP-Final Inspection8/30/20058/31/2005 A 
Scheduled by a contractor via Hello! on 8/30/2005 at 4:20:18 PM. Contact: ###-####.
MIS05-00125 FIR-Final9/1/20059/2/20059/6/2005 1:41:21 PMACANC
No time for this inspection, to be scheduled for 9/7/05 per agreement with Jason at ###-####.
FIR05-00338 INSP-Supply line flush9/1/20059/2/20059/2/2005 4:25:13 PMAPART
UG fire line flush is satisfactory. Advised contractor that the depth of bury still appears too shallow, however, site work is not complete. Will verify before final approval that the depth of cover is sufficient.
FIR05-00338 INSP-Sprinkler Rough-in/Hydro9/1/20059/2/20059/2/2005 4:19:53 PMAPART
Hydrostatic test of the underground fire supply line passed. Although the site work is not completed, depth of bury still appears too shallow as evidenced by my mark on an adjacent concrete vault.
BLD05-02034 FIRE-Final Inspection9/1/20059/2/20059/2/2005 3:17:27 PMPFAIL
Numerous code deficiencies include door hardware, fire sprinkler system, hydrant flow, sprinkler flow, fire lane marking, non functional exit signs and emergency lights, and fire alarm permit final, need to be addressed prior to approval. A correction notice with a non-comprehensive list was left at the site with Nate Hosac.
BLD05-02035 FIRE-Final Inspection9/1/20059/2/20059/2/2005 3:11:44 PMPFAIL
Provide approved door hardware at restrooms, exit sign at west door is not installed, provide one 2A10 BC fire ext.
BLD05-02037 FIRE-Final Inspection9/1/20059/2/20059/2/2005 3:09:44 PMPFAIL
Manual thumbturns are not allowed on the main entry /exit doors, provide a fire ext., repair emergency light.
BLD05-01529 FIRE-Final Inspection9/1/20059/2/20059/2/2005 2:00:51 PMAPASS
Fire life safety passed inspection, permit finaled.
BLD05-01345 FIRE-Final Inspection9/1/20059/2/20059/2/2005 1:23:31 PMAPART
Fire alarm permit must be finaled prior to BLD fire/life safety final. All other life safety issues have been inspected and are satisfactory.
BLD04-03002 FIRE-Final Inspection9/1/20059/2/20059/2/2005 1:19:14 PMAFAIL
Door closures have not been installed, relocated smoke detectors are acceptable.
FIR05-00493 INSP-Sprinkler Rough-in9/2/20059/2/20059/2/2005 12:37:45 PMPCANC
No time for this inspection today, spoke with Jonathan to schedule for next week per our conversation.
BLD05-01283 FIRE-Final Inspection9/2/20059/2/20059/2/2005 12:34:26 PMPPASS
Fire life safety finaled.
BLD05-01687 FIRE-Final Inspection9/2/20059/2/20059/2/2005 12:29:57 PMPPASS
Fire life safety finaled.
BLD04-01909 FIRE-Final Inspection9/1/20059/2/20059/2/2005 11:47:25 AMAPART
Temporary occupancy approved with Sam Rogers permission pending completion of permanent dual phone lines for final of fire alarm permit. Life safety approved when fire alarm, door hardware, emergency light, and one exit sign are repaired as discussed.
BLD05-01857 FIRE-Final Inspection9/1/20059/2/20059/2/2005 11:39:11 AMAPASS
Life safety passed inspection.
FIR05-00186 INSP-Final Inspection8/31/20059/2/20059/2/2005 10:24:26 AMACANC
No time today for this re-inspection, spoke with Ray to schedule for next week.
FIR05-00511 INSP-Final Inspection9/1/20059/2/20059/2/2005 10:21:59 AMACANC
larren or ###-####; Phone #: ###-#### No time for this inspection today, spoke with Larren to re-schedule for next week per our agreement.
BLD04-01823 FIRE-Final Inspection9/1/20059/2/20059/2/2005 10:10:11 AMACANC
Duplicate inspection, shell fire safety is satisfactory.
BLD05-01269 FIRE-Final Inspection9/1/20059/2/20059/2/2005 9:53:47 AMAFAIL
A stop work order was issued due to a fire alarm modification made without a permit. See fire code review comments note #1 and #5.
FIR05-00390 INSP-Final Inspection8/30/20059/2/20059/2/2005 12:00:00 AMADONE
Scheduled by a contractor via Hello! on 8/30/2005 at 5:08:48 PM. Contact: ###-####.
MIS05-00123 BLD-Final9/2/20059/2/20059/2/2005 12:00:00 AMAPASS
Locking hardware at door to the shared restroom access has been removed, permit finaled.
FIR05-00369 INSP-Alarm Testing9/1/20059/2/20059/2/2005 12:00:00 AMPFAIL
This inspection to be completed by Mary Froemke.

FAS does not match approved plans, incorrect candela ratings throughout the building and NAC panel does not match plans. Comments and cut sheets not on site for referral. Batteries are "swapped" from what the plans indicate.
FIR05-00393 INSP-Final Inspection9/2/20059/2/20059/2/2005 12:00:00 AMPPASS
Fire sprinkler permit finaled.
FIR05-00394 INSP-Final Inspection9/2/20059/2/20059/2/2005 12:00:00 AMPPASS
Fire alarm finaled.
FIR04-00737 INSP-Final Inspection9/2/20059/2/20059/2/2005 12:00:00 AMPPASS
Defficient items have been corrected and inspected, permit finaled.
FIR04-00627 INSP-Final Inspection9/2/20059/2/20059/2/2005 12:00:00 AMPPASS
Underground fire supply line permit finaled.
FIR05-00494 INSP-Final Inspection8/31/20059/2/20059/2/2005 12:00:00 AMPFAIL
Troy, We would like to schedule these (3) Buildings for inspection at the same time, since they are on the same Fire Alarm Panel, and in the same location. If you have any questions, or problems, please call me at the office, or on my cell at ###-####. Thanks, Jason; Phone #: ###-#### Internet Inspection Request from: Jason Minnick

Fire Sprinklers not activated. Could not verify flow or tampers. A PIV has been added, not included on the plans, nor was it connected to the FAS. 8 classrooms had insufficient visual coverage based on location in the room. (marked on plans). Resubmittal will be required prior to finaling the permit.

Tested all pull stations and smoke, remainder of notification is acceptable.
FIR05-00495 INSP-Final Inspection8/31/20059/2/20059/2/2005 12:00:00 AMPFAIL
Troy, We would like to schedule these (3) Buildings for inspection at the same time, since they are on the same Fire Alarm Panel, and in the same location. If you have any questions, or problems, please call me at the office, or on my cell at ###-####. Thanks, Jason; Phone #: ###-#### Internet Inspection Request from: Jason Minnick
Fire Sprinklers not activated. Could not verify flow or tampers. A PIV has been added, not included on the plans, nor was it connected to the FAS. 8 classrooms had insufficient visual coverage based on location in the room. (marked on plans). Resubmittal will be required prior to finaling the permit.

Tested all pull stations and smoke, remainder of notification is acceptable.
FIR05-00496 INSP-Final Inspection8/31/20059/2/20059/2/2005 12:00:00 AMPFAIL
Troy, We would like to schedule these (3) Buildings for inspection at the same time, since they are on the same Fire Alarm Panel, and in the same location. If you have any questions, or problems, please call me at the office, or on my cell at ###-####. Thanks, Jason; Phone #: ###-#### Internet Inspection Request from: Jason Minnick

Fire Sprinklers not activated. Could not verify flow or tampers. A PIV has been added, not included on the plans, nor was it connected to the FAS. 8 classrooms had insufficient visual coverage based on location in the room. (marked on plans). Resubmittal will be required prior to finaling the permit.

Tested all pull stations and smoke, remainder of notification is acceptable.