FIR05-00209
| INSP-Final Inspection | 8/30/2005 | 8/31/2005 | | A | |
|
|
Scheduled by a contractor via Hello! on 8/30/2005 at 4:20:18 PM. Contact: ###-####.
|
MIS05-00125
| FIR-Final | 9/1/2005 | 9/2/2005 | 9/6/2005 1:41:21 PM | A | CANC |
|
|
No time for this inspection, to be scheduled for 9/7/05 per agreement with Jason at ###-####.
|
FIR05-00338
| INSP-Supply line flush | 9/1/2005 | 9/2/2005 | 9/2/2005 4:25:13 PM | A | PART |
|
|
UG fire line flush is satisfactory. Advised contractor that the depth of bury still appears too shallow, however, site work is not complete. Will verify before final approval that the depth of cover is sufficient.
|
FIR05-00338
| INSP-Sprinkler Rough-in/Hydro | 9/1/2005 | 9/2/2005 | 9/2/2005 4:19:53 PM | A | PART |
|
|
Hydrostatic test of the underground fire supply line passed. Although the site work is not completed, depth of bury still appears too shallow as evidenced by my mark on an adjacent concrete vault.
|
BLD05-02034
| FIRE-Final Inspection | 9/1/2005 | 9/2/2005 | 9/2/2005 3:17:27 PM | P | FAIL |
|
|
Numerous code deficiencies include door hardware, fire sprinkler system, hydrant flow, sprinkler flow, fire lane marking, non functional exit signs and emergency lights, and fire alarm permit final, need to be addressed prior to approval. A correction notice with a non-comprehensive list was left at the site with Nate Hosac.
|
BLD05-02035
| FIRE-Final Inspection | 9/1/2005 | 9/2/2005 | 9/2/2005 3:11:44 PM | P | FAIL |
|
|
Provide approved door hardware at restrooms, exit sign at west door is not installed, provide one 2A10 BC fire ext.
|
BLD05-02037
| FIRE-Final Inspection | 9/1/2005 | 9/2/2005 | 9/2/2005 3:09:44 PM | P | FAIL |
|
|
Manual thumbturns are not allowed on the main entry /exit doors, provide a fire ext., repair emergency light.
|
BLD05-01529
| FIRE-Final Inspection | 9/1/2005 | 9/2/2005 | 9/2/2005 2:00:51 PM | A | PASS |
|
|
Fire life safety passed inspection, permit finaled.
|
BLD05-01345
| FIRE-Final Inspection | 9/1/2005 | 9/2/2005 | 9/2/2005 1:23:31 PM | A | PART |
|
|
Fire alarm permit must be finaled prior to BLD fire/life safety final. All other life safety issues have been inspected and are satisfactory.
|
BLD04-03002
| FIRE-Final Inspection | 9/1/2005 | 9/2/2005 | 9/2/2005 1:19:14 PM | A | FAIL |
|
|
Door closures have not been installed, relocated smoke detectors are acceptable.
|
FIR05-00493
| INSP-Sprinkler Rough-in | 9/2/2005 | 9/2/2005 | 9/2/2005 12:37:45 PM | P | CANC |
|
|
No time for this inspection today, spoke with Jonathan to schedule for next week per our conversation.
|
BLD05-01283
| FIRE-Final Inspection | 9/2/2005 | 9/2/2005 | 9/2/2005 12:34:26 PM | P | PASS |
|
|
Fire life safety finaled.
|
BLD05-01687
| FIRE-Final Inspection | 9/2/2005 | 9/2/2005 | 9/2/2005 12:29:57 PM | P | PASS |
|
|
Fire life safety finaled.
|
BLD04-01909
| FIRE-Final Inspection | 9/1/2005 | 9/2/2005 | 9/2/2005 11:47:25 AM | A | PART |
|
|
Temporary occupancy approved with Sam Rogers permission pending completion of permanent dual phone lines for final of fire alarm permit. Life safety approved when fire alarm, door hardware, emergency light, and one exit sign are repaired as discussed.
|
BLD05-01857
| FIRE-Final Inspection | 9/1/2005 | 9/2/2005 | 9/2/2005 11:39:11 AM | A | PASS |
|
|
Life safety passed inspection.
|
FIR05-00186
| INSP-Final Inspection | 8/31/2005 | 9/2/2005 | 9/2/2005 10:24:26 AM | A | CANC |
|
|
No time today for this re-inspection, spoke with Ray to schedule for next week.
|
FIR05-00511
| INSP-Final Inspection | 9/1/2005 | 9/2/2005 | 9/2/2005 10:21:59 AM | A | CANC |
|
|
larren or ###-####; Phone #: ###-#### No time for this inspection today, spoke with Larren to re-schedule for next week per our agreement.
|
BLD04-01823
| FIRE-Final Inspection | 9/1/2005 | 9/2/2005 | 9/2/2005 10:10:11 AM | A | CANC |
|
|
Duplicate inspection, shell fire safety is satisfactory.
|
BLD05-01269
| FIRE-Final Inspection | 9/1/2005 | 9/2/2005 | 9/2/2005 9:53:47 AM | A | FAIL |
|
|
A stop work order was issued due to a fire alarm modification made without a permit. See fire code review comments note #1 and #5.
|
FIR05-00390
| INSP-Final Inspection | 8/30/2005 | 9/2/2005 | 9/2/2005 12:00:00 AM | A | DONE |
|
|
Scheduled by a contractor via Hello! on 8/30/2005 at 5:08:48 PM. Contact: ###-####.
|
MIS05-00123
| BLD-Final | 9/2/2005 | 9/2/2005 | 9/2/2005 12:00:00 AM | A | PASS |
|
|
Locking hardware at door to the shared restroom access has been removed, permit finaled.
|
FIR05-00369
| INSP-Alarm Testing | 9/1/2005 | 9/2/2005 | 9/2/2005 12:00:00 AM | P | FAIL |
|
|
This inspection to be completed by Mary Froemke.
FAS does not match approved plans, incorrect candela ratings throughout the building and NAC panel does not match plans. Comments and cut sheets not on site for referral. Batteries are "swapped" from what the plans indicate.
|
FIR05-00393
| INSP-Final Inspection | 9/2/2005 | 9/2/2005 | 9/2/2005 12:00:00 AM | P | PASS |
|
|
Fire sprinkler permit finaled.
|
FIR05-00394
| INSP-Final Inspection | 9/2/2005 | 9/2/2005 | 9/2/2005 12:00:00 AM | P | PASS |
|
|
Fire alarm finaled.
|
FIR04-00737
| INSP-Final Inspection | 9/2/2005 | 9/2/2005 | 9/2/2005 12:00:00 AM | P | PASS |
|
|
Defficient items have been corrected and inspected, permit finaled.
|
FIR04-00627
| INSP-Final Inspection | 9/2/2005 | 9/2/2005 | 9/2/2005 12:00:00 AM | P | PASS |
|
|
Underground fire supply line permit finaled.
|
FIR05-00494
| INSP-Final Inspection | 8/31/2005 | 9/2/2005 | 9/2/2005 12:00:00 AM | P | FAIL |
|
|
Troy, We would like to schedule these (3) Buildings for inspection at the same time, since they are on the same Fire Alarm Panel, and in the same location. If you have any questions, or problems, please call me at the office, or on my cell at ###-####. Thanks, Jason; Phone #: ###-#### Internet Inspection Request from: Jason Minnick
Fire Sprinklers not activated. Could not verify flow or tampers. A PIV has been added, not included on the plans, nor was it connected to the FAS. 8 classrooms had insufficient visual coverage based on location in the room. (marked on plans). Resubmittal will be required prior to finaling the permit.
Tested all pull stations and smoke, remainder of notification is acceptable.
|
FIR05-00495
| INSP-Final Inspection | 8/31/2005 | 9/2/2005 | 9/2/2005 12:00:00 AM | P | FAIL |
|
|
Troy, We would like to schedule these (3) Buildings for inspection at the same time, since they are on the same Fire Alarm Panel, and in the same location. If you have any questions, or problems, please call me at the office, or on my cell at ###-####. Thanks, Jason; Phone #: ###-#### Internet Inspection Request from: Jason Minnick
Fire Sprinklers not activated. Could not verify flow or tampers. A PIV has been added, not included on the plans, nor was it connected to the FAS. 8 classrooms had insufficient visual coverage based on location in the room. (marked on plans). Resubmittal will be required prior to finaling the permit.
Tested all pull stations and smoke, remainder of notification is acceptable.
|
FIR05-00496
| INSP-Final Inspection | 8/31/2005 | 9/2/2005 | 9/2/2005 12:00:00 AM | P | FAIL |
|
|
Troy, We would like to schedule these (3) Buildings for inspection at the same time, since they are on the same Fire Alarm Panel, and in the same location. If you have any questions, or problems, please call me at the office, or on my cell at ###-####. Thanks, Jason; Phone #: ###-#### Internet Inspection Request from: Jason Minnick
Fire Sprinklers not activated. Could not verify flow or tampers. A PIV has been added, not included on the plans, nor was it connected to the FAS. 8 classrooms had insufficient visual coverage based on location in the room. (marked on plans). Resubmittal will be required prior to finaling the permit.
Tested all pull stations and smoke, remainder of notification is acceptable.
|