Inspections for the day of: Tuesday, September 2, 2008.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00597 INSP-Sprinkler Rough-in8/29/20089/2/20089/2/2008 4:52:43 PMPPART
Fire sprinkler work above hard lid ceilings is approved for cover, atrium and grid ceiling sprinkler work is not yet complete.
FIR07-00928 INSP-Sprinkler Rough-in/Hydro9/2/20089/2/20089/2/2008 4:25:20 PMPPART
Reviewed noted correction items from the previous inspection for deficiencies at the 3rd, 4th, 5th and 6th floor overhead rough-in for the dwelling units only. Corridor, elevator lobby, stairway landings, common areas are not complete at this time. Corrections per annotations on plans are finished with the exception of two missed locations-5th floor head spacing at the NW end unit, 4th floor sprinkler spacing at the NW end unit bedroom.
FIR08-00018 INSP-Sprinkler Rough-in/Hydro9/2/20089/2/20089/2/2008 4:19:11 PMPPART
7th floor rough-in is consistent with the provided as-built plans, final approval pending matched stamped resubmittals.
BLD08-01053 FIRE-Final Inspection9/2/20089/2/20089/2/2008 4:15:14 PMPFAIL
Need to provide approved hardware at three locations below marked exits or remove signage as discussed, install correct directional arrows at the hall exit sign, hardware at the pocket doors must be compliant.
FIR07-00879 INSP-Final Inspection9/2/20089/2/20089/2/2008 1:13:32 PMAPASS
UG fire supply line permit finaled.
FIR08-00597 INSP-Sprinkler Rough-in8/29/20089/2/20089/2/2008 11:14:13 AMAPART
OH fire sprinkler system modifications are okay for cover at the womens and mens locker room sheetrock ceiling areas-circled and initialed on stamped plans with today's date, also verified coverage outside remodel area due to new wall construction is compliant.
FIR07-00827 INSP-Sprinkler Rough-in9/2/20089/2/20089/2/2008 11:10:53 AMAPART
Refer to approved plan set for annotations regarding rough-in locations good for cover.
BLD07-00170 FIRE-Conference9/2/20089/2/20089/2/2008 11:09:35 AMADONE
Regarding life safety and project related fire sprinkler permit final needed.