Inspections for the day of: Wednesday, September 2, 2015.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRex Boyles
TitleELE-INSPECTOR
Phone #685-9023
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE15-01348 Conference9/2/20159/2/20159/2/2015 2:48:04 PMPDONE
Article 376 Wireways - Fill and Derating Conductors Phone #: ###-#### Inspection requested via web by Tom Betty discuss with Tom 2-custom pull boxes with 2 covers being made for electrical room. After reviewing drawings and NEC requirements, we agreed on this application that will satisfy NEC 376.22(A)&(B), will also satisfy 310.10 (H), will also satisfy 314.28(A)(2), will also satisfy 314.40(C)and(D), will also satisfy 314.71(A) and (B). Cables will be supported so as to not lay on cover.
GCE14-00207 GCE-Rough-In9/2/20159/2/20159/2/2015 1:15:32 PMPPASS
Kevin ###-#### - 2nd & 3rd floor and rooftop r/i ok 2nd and 3rd floor corridors east wing. Final ok rooftop mechanical electrical ok 500 mcm cu ok to 1600amp meter section
GCE15-00138 GCE-Final9/1/20159/2/20159/2/2015 10:22:25 AMACANC
David ###-#### not needed or ready for final
ELE15-02730 Electrical Rough-In9/1/20159/2/20159/2/2015 10:21:43 AMAPASS
Todd-garage in alley Phone #: ###-#### r/i ok garage addition. Will look for existing 60 amp disconnect feeding new garage and adjoining bldg. to be relocated to meet code later. Additional work to be added to permit.
ELE15-01509 Final8/28/20159/2/20159/2/2015 9:56:18 AMAPASS
Contact is Justin Metcalf please call him before arriving ###-#### so he can meet you there. Thank you and have a super day! Phone #: ###-#### Inspection requested via web by Laura Longshaw final ok on lighting retrofit Asked contractor to call for r/i insp. "first" next time to see product listings being installed
ELE15-02163 Final9/1/20159/2/20159/2/2015 9:32:14 AMAPASS
code 83706 Phone #: ###-#### Inspection requested via web by Dan Rohl corrections made final ok
ELE15-02599 Permanent Service9/1/20159/2/20159/2/2015 9:13:26 AMACANC
Mirch-pleae call for access Phone #: ###-#### already inspected 9/1 ??
GCE15-00138 GCE-Permanent Service9/1/20159/2/20159/2/2015 8:47:49 AMAPASS
David ###-#### p/s u/g n ok
GCE15-00131 GCE-Final9/1/20159/2/20159/2/2015 8:39:02 AMAPART
Asher ###-#### perm. occupancy ok still need available fault current label and arc flash labels on disconnect and loadcenter