ELE15-01348
| Conference | 9/2/2015 | 9/2/2015 | 9/2/2015 2:48:04 PM | P | DONE |
|
|
Article 376 Wireways - Fill and Derating Conductors Phone #: ###-#### Inspection requested via web by Tom Betty discuss with Tom 2-custom pull boxes with 2 covers being made for electrical room. After reviewing drawings and NEC requirements, we agreed on this application that will satisfy NEC 376.22(A)&(B), will also satisfy 310.10 (H), will also satisfy 314.28(A)(2), will also satisfy 314.40(C)and(D), will also satisfy 314.71(A) and (B). Cables will be supported so as to not lay on cover.
|
GCE14-00207
| GCE-Rough-In | 9/2/2015 | 9/2/2015 | 9/2/2015 1:15:32 PM | P | PASS |
|
|
Kevin ###-#### - 2nd & 3rd floor and rooftop r/i ok 2nd and 3rd floor corridors east wing. Final ok rooftop mechanical electrical ok 500 mcm cu ok to 1600amp meter section
|
GCE15-00138
| GCE-Final | 9/1/2015 | 9/2/2015 | 9/2/2015 10:22:25 AM | A | CANC |
|
|
David ###-#### not needed or ready for final
|
ELE15-02730
| Electrical Rough-In | 9/1/2015 | 9/2/2015 | 9/2/2015 10:21:43 AM | A | PASS |
|
|
Todd-garage in alley Phone #: ###-#### r/i ok garage addition. Will look for existing 60 amp disconnect feeding new garage and adjoining bldg. to be relocated to meet code later. Additional work to be added to permit.
|
ELE15-01509
| Final | 8/28/2015 | 9/2/2015 | 9/2/2015 9:56:18 AM | A | PASS |
|
|
Contact is Justin Metcalf please call him before arriving ###-#### so he can meet you there. Thank you and have a super day! Phone #: ###-#### Inspection requested via web by Laura Longshaw final ok on lighting retrofit Asked contractor to call for r/i insp. "first" next time to see product listings being installed
|
ELE15-02163
| Final | 9/1/2015 | 9/2/2015 | 9/2/2015 9:32:14 AM | A | PASS |
|
|
code 83706 Phone #: ###-#### Inspection requested via web by Dan Rohl corrections made final ok
|
ELE15-02599
| Permanent Service | 9/1/2015 | 9/2/2015 | 9/2/2015 9:13:26 AM | A | CANC |
|
|
Mirch-pleae call for access Phone #: ###-#### already inspected 9/1 ??
|
GCE15-00138
| GCE-Permanent Service | 9/1/2015 | 9/2/2015 | 9/2/2015 8:47:49 AM | A | PASS |
|
|
David ###-#### p/s u/g n ok
|
GCE15-00131
| GCE-Final | 9/1/2015 | 9/2/2015 | 9/2/2015 8:39:02 AM | A | PART |
|
|
Asher ###-#### perm. occupancy ok still need available fault current label and arc flash labels on disconnect and loadcenter
|