Inspections for the day of: Friday, September 2, 2016.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJames Ady
TitleELE-INSPECTOR
Phone #914-4683
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE16-02875 Rough-In Permanent Service9/2/20169/2/20169/2/2016 2:58:24 PMPPASS
Phone #: ###-#### Inspection requested via web by daniel bibikov Garage laundry, kitchen, dining and living room only. Beds and Baths untoughed except for smoke detectors. Rough in OK p/s o/h rec ok
ELE16-02397 Final9/2/20169/2/20169/2/2016 2:35:18 PMPFAIL
call ahead for access;Jim Phone #: ###-#### 440.22 C Protective device shall not be high than manufacturers rating (A/C) 210.8 A 6 All receps in kitchen shall be GFCI protected. 406.12 A All receptacles in dwelling units shall be tamper resistant
ELE16-02879 Final9/2/20169/2/20169/2/2016 1:45:17 PMPCANC
service off longer than 1 year; Deven Phone #: ###-#### Needed perm service
ELE16-02879 Permanent Service9/2/20169/2/20169/2/2016 1:45:01 PMPFAIL
service off longer than 1 year; Deven Phone #: ###-#### Could not get in main panel due to lock.
ESC16-00071 Site Final9/2/20169/2/20169/2/2016 1:28:22 PMPPASS
Site final ok
ESC16-00581 Site Final9/2/20169/2/20169/2/2016 1:27:40 PMPPASS
Site final ok
ELE16-02857 Electrical Rough-In9/2/20169/2/20169/2/2016 1:15:57 PMPPASS
Under ground inspection Phone #: ###-#### Inspection requested via web by Ryan Wake Underground to front counter ok to cover
ELE16-02122 Conference9/1/20169/2/20169/2/2016 12:59:24 PMPDONE
Chick Phone #: ###-#### Talked about disc. on detached garage, 4 wire over head to garage, clean up wire supports in laundry room
ELE16-01579 Electrical Rough-In9/2/20169/2/20169/2/2016 12:01:18 PMPPASS
If you have any questions, please call Clay. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan Undergroung to garage ok to cover
ELE16-00770 Electrical Rough-In9/2/20169/2/20169/2/2016 11:22:34 AMPPASS
inspection of ground wire on exterior wall of Fitness bldg poo; room wall.
photos texted Phone #: ###-#### Inspection requested via web by Tracy Robertson Ok to cover Pool room wall only
ELE16-02866 Electrical Rough-In9/1/20169/2/20169/2/2016 11:20:12 AMPPASS
pool - spa bonding cover motor 3ea.water falls Phone #: ###-#### Inspection requested via web by Kevin Koomler Corner Pool bond ok
ELE16-02751 Rough-In Permanent Service9/2/20169/2/20169/2/2016 11:19:18 AMPPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn Rough in ok p/s u/g n ok
ELE16-02103 Final9/2/20169/2/20169/2/2016 11:17:37 AMPPASS
Garage code 1001E Phone #: ###-#### Inspection requested via web by Alan Lusk Final ok
ELE16-02840 Rough-In Permanent Service8/30/20169/2/20169/2/2016 11:15:54 AMAPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk Check UFER mud ring on final Rough in ok to cover p/s u/g n ok
ELE16-02232 Final9/1/20169/2/20169/2/2016 9:27:04 AMAPASS
Call Monica 30 minutes in advance for access
###-#### Phone #: ###-#### Inspection requested via web by danny perrine Kitchen final ok
ELE16-00753 Final9/1/20169/2/20169/2/2016 9:13:18 AMAPART
unit 201 in Cottage A3 Phone #: ###-#### Inspection requested via web by Tracy Robertson Unit 201 0nly Final ok
ELE16-02874 Permanent Service9/2/20169/2/20169/2/2016 8:35:05 AMAPASS
We will be connecting the current Square D meter/panel to a new 2" conduit. The OH mast will be removed once IPCO has killed the power. Thank you Phone #: ###-#### Inspection requested via web by Eric Brown p/s u/g rec ok