ELE16-02724
| Final | 9/2/2016 | 9/2/2016 | 9/2/2016 3:48:46 PM | P | PASS |
|
|
job complete, final ok
|
ELE16-02724
| Electrical Rough-In | 9/2/2016 | 9/2/2016 | 9/2/2016 3:39:26 PM | P | PASS |
|
|
Replace window pendent luminaires above seating boothes, and LED track lighting above front counter,provide additional LED track lighting and LED pendent lighting in dinning area. rough-in ok
|
ELE15-02740
| Final | 9/1/2016 | 9/2/2016 | 9/2/2016 2:09:40 PM | A | PASS |
|
|
Seth Phone #: ###-#### Guess room furniture light switchs alteration approved final ok
|
ELE15-03901
| Electrical Rough-In | 9/2/2016 | 9/2/2016 | 9/2/2016 12:52:16 PM | P | PASS |
|
|
Call Pierce for inspection of 8th floor furniture. Phone #: ###-#### Inspection requested via web by Rafael Castillo Rough-in ok UL lIsted office furniture, Yellow section drawn on print.
|
ELE16-01652
| Electrical Rough-In | 9/1/2016 | 9/2/2016 | 9/2/2016 12:50:28 PM | A | PASS |
|
|
Grounding of re bar around fountain in trench drain concrete also bonding of trench drain cover. Please call 8604010 when headed over thanks.John Phone #: ###-#### Inspection requested via web by John Rourke Rough-ok cover common bonding grid around fountain. Discussed bonding perimeter surface
|
ELE16-01838
| Electrical Rough-In | 9/1/2016 | 9/2/2016 | 9/2/2016 11:38:05 AM | A | NR |
|
|
Level 3 Annex ceiling ( 4 X 4 ) tiles. Call John Phone #: ###-#### Inspection requested via web by Brandon Robinson Not ready, open j-boxes, uncapped MC for future lighting
|
ELE16-02860
| Electrical Rough-In | 9/2/2016 | 9/2/2016 | 9/2/2016 10:32:30 AM | A | PASS |
|
|
This is for the PVC underground raceways from the building to the new outdoor class room. Please call Jimmy when on site. Phone #: ###-#### Inspection requested via web by Kevin Perez Rough-in ok cover trench, sch 40 stubs to change to EMT
|
ELE16-02869
| Rough-In Permanent Service | 9/1/2016 | 9/2/2016 | 9/2/2016 8:58:40 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by David Nelson Additional ground rod needed, enclosure required over NM cables, complete panel directory, p/s o/h rec ok
|