Inspections for the day of: Monday, September 20, 2004.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00372 FIR-Aging Inspection9/20/20049/20/20049/22/2004 12:00:00 AM PASS
Talked to Don and he will schedule for next week 9/22/2004 1:13:44 PM
FIR03-00690 INSP-Final Inspection8/31/20049/20/20049/20/2004 12:00:00 AMAFAIL
###-#### - cliff Need temporal tone on all sounder bases; sounder bases generate general alarm not supervisory as shown on matrix and drop mags for doors; elevator shunt not working; lockout for 120 volt breaker for shunt as it isn't supervised; all troubles okay on panel; need voltage drops on NAC's and test alarm notification; review the computer program for this system 9/20/2004 4:24:04 PM
FIR04-00208 INSP-Sprinkler Rough-in9/17/20049/20/20049/20/2004 12:00:00 AMAPART
don; Phone #: ###-#### Internet Inspection Request from: Barbara Moore Okay to cover at FDC only 9/20/2004 10:31:38 AM
MIS04-00254 FIR-Final9/20/20049/20/20049/20/2004 12:00:00 AMPPASS
wendy -call 1st before insp -pending structural fn ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
MIS04-00255 FIR-Final9/20/20049/20/20049/20/2004 12:00:00 AMPPASS
wendy -call 1st before insp -pending structural fn ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
FIR04-00524 INSP-Sprinkler Rough-in/Hydro9/20/20049/20/20049/20/2004 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 9/20/2004 at 9:44:25 AM. Contact: ###-####. Work room showed 4 heads and was reduced to 2 - light hazard spacing maintained; okay to cover 9/20/2004 1:43:11 PM
FIR04-00525 INSP-Sprinkler Rough-in/Hydro9/20/20049/20/20049/20/2004 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 9/20/2004 at 9:46:30 AM. Contact: ###-####. Okay to cover 9/20/2004 1:43:19 PM
MIS04-00259 FIR-Final9/20/20049/20/20049/20/2004 12:00:00 AMPPASS
tom ###-#### pending structural fn
BLD04-02126 FIRE-Hydro test above ground9/20/20049/20/20049/20/2004 12:00:00 AMPCANC
Scheduled by a contractor via Hello! on 9/20/2004 at 11:09:30 AM. Contact: ###-####. Fire not required for inspections 9/20/2004 11:41:24 AM