FIR04-00372
| FIR-Aging Inspection | 9/20/2004 | 9/20/2004 | 9/22/2004 12:00:00 AM | | PASS |
|
|
Talked to Don and he will schedule for next week 9/22/2004 1:13:44 PM
|
FIR03-00690
| INSP-Final Inspection | 8/31/2004 | 9/20/2004 | 9/20/2004 12:00:00 AM | A | FAIL |
|
|
###-#### - cliff Need temporal tone on all sounder bases; sounder bases generate general alarm not supervisory as shown on matrix and drop mags for doors; elevator shunt not working; lockout for 120 volt breaker for shunt as it isn't supervised; all troubles okay on panel; need voltage drops on NAC's and test alarm notification; review the computer program for this system 9/20/2004 4:24:04 PM
|
FIR04-00208
| INSP-Sprinkler Rough-in | 9/17/2004 | 9/20/2004 | 9/20/2004 12:00:00 AM | A | PART |
|
|
don; Phone #: ###-#### Internet Inspection Request from: Barbara Moore Okay to cover at FDC only 9/20/2004 10:31:38 AM
|
MIS04-00254
| FIR-Final | 9/20/2004 | 9/20/2004 | 9/20/2004 12:00:00 AM | P | PASS |
|
|
wendy -call 1st before insp -pending structural fn ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
|
MIS04-00255
| FIR-Final | 9/20/2004 | 9/20/2004 | 9/20/2004 12:00:00 AM | P | PASS |
|
|
wendy -call 1st before insp -pending structural fn ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
|
FIR04-00524
| INSP-Sprinkler Rough-in/Hydro | 9/20/2004 | 9/20/2004 | 9/20/2004 12:00:00 AM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 9/20/2004 at 9:44:25 AM. Contact: ###-####. Work room showed 4 heads and was reduced to 2 - light hazard spacing maintained; okay to cover 9/20/2004 1:43:11 PM
|
FIR04-00525
| INSP-Sprinkler Rough-in/Hydro | 9/20/2004 | 9/20/2004 | 9/20/2004 12:00:00 AM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 9/20/2004 at 9:46:30 AM. Contact: ###-####. Okay to cover 9/20/2004 1:43:19 PM
|
MIS04-00259
| FIR-Final | 9/20/2004 | 9/20/2004 | 9/20/2004 12:00:00 AM | P | PASS |
|
|
tom ###-#### pending structural fn
|
BLD04-02126
| FIRE-Hydro test above ground | 9/20/2004 | 9/20/2004 | 9/20/2004 12:00:00 AM | P | CANC |
|
|
Scheduled by a contractor via Hello! on 9/20/2004 at 11:09:30 AM. Contact: ###-####. Fire not required for inspections 9/20/2004 11:41:24 AM
|