FIR04-00560 INSP-Final Inspection9/17/20049/20/20049/20/2004 9:33:05 AMACANC
Troy, I spoke to the General Contractor, and the Electrician, and they are already planning on being on-site on Monday at 9:00 am. Would that time work for you for an inspection? If so, please let me know so that we can be sure to be there as well, if not, please let me know when you may be available for a final test on this project. It is quite small (3) smokes, and (4) a/v devices. My cell is ###-####, if you cant reach me at the office. Thanks, Jason; Phone #: ###-#### Internet Inspection Request from: Jason Minnick Inspection cancelled from web by: Jason Minnick
BLD04-01819 FIRE-Conference9/17/20049/20/20049/20/2004 12:00:00 AMADONE
I spoke to Dutch with DSCI about sprinkler heads. I found several locations where sprinklers are overspaced. I told him he needs a sprinkler contractor to verify spacing throughout the tenant space. Also there is a control valve on a anti-freeze loop that does not have a tamper switch. 9/20/2004 2:47:09 PM
BLD04-01650 FIRE-Final Inspection9/17/20049/20/20049/20/2004 12:00:00 AMAFAIL
Provide "Door to remain unlocked while building is occupied" sticker at the main exit. Hang and tag fire extinguisher. Provide ada approved door hardware on the office doors. 9/20/2004 11:17:17 AM
FIR04-00238 INSP-Final Inspection9/20/20049/20/20049/20/2004 12:00:00 AMPFAIL
Provide a/v's in rooms 115 and in the facp room as per plan. A/v's overspaced in 116, 103, 106, 107 and outside of toilet 124. Provide correct sample tube lenghts for the duct smoke detectors. Provide map for facp and stickers on the annunciators telling where the map is at. Test remaining duct smoke detectors in the sanctuary and daycare. Test a/v's on second floor. Provide lock outs on breakers. 9/20/2004 3:11:00 PM
BLD04-00577 FIRE-Final Inspection9/20/20049/20/20049/20/2004 12:00:00 AMPPASS
Fire life safety finaled 9/20/2004 3:54:57 PM