Inspections for the day of: Tuesday, September 20, 2005.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-03422 Rough-In Permanent Service9/20/20059/20/20059/20/2005 4:41:59 PMPNR
APROX. 3 PM FOR INSPECTION PLEASE; Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack met with contractor
ELE05-03376 Electrical Rough-In9/20/20059/20/20059/20/2005 4:22:49 PMPFAIL
tom; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called , cor. posted still needs 300.4 and add required outlet for kit counter space added after inspection
ELE05-03430 Temporary Service9/20/20059/20/20059/20/2005 3:22:49 PMPFAIL
###-#### - john cor. posted called needs conn for GEC, replace or protect #8 GEC
ELE05-03426 Temporary Service9/20/20059/20/20059/20/2005 2:42:39 PMPFAIL
###-#### tim 250.25 terminate GEC so neutral is grounded, 250.53(G) drive grd rod flush cor. posted called left message
ELE05-03424 Final9/20/20059/20/20059/20/2005 2:19:52 PMPFAIL
Phone #: ###-#### Internet Inspection Request from: Dana Moyer could not located called left message, what do you want finaled?
ELE05-02951 Final9/19/20059/20/20059/20/2005 12:48:40 PMAPASS
charlene; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa note house was not wired to meet code, owner complained about correction, persons above me allowed wiring less than 2005 NEC, final by them
ELE05-01897 Final9/19/20059/20/20059/20/2005 10:54:16 AMANH
darren; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa notice posted called
ELE05-03417 Electrical Rough-In9/19/20059/20/20059/20/2005 10:41:09 AMAPART
unground post light insp --jim ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok no romex allowed in conduit
ELE05-02555 Electrical Rough-In9/19/20059/20/20059/20/2005 10:40:27 AMAFAIL
unground post light insp --jim ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie not ready u/g installed by general, not electrical, and over 360 degrees of bends, do not cover posted called
ELE05-03025 Electrical Rough-In9/19/20059/20/20059/20/2005 10:02:48 AMAPASS
Scheduled by a contractor via Hello! on 9/19/2005 at 1:00:28 PM. Contact: ###-####. kit and basement ok
ELE05-02730 Electrical Rough-In9/20/20059/20/20059/20/2005 8:39:22 AMAPART
Scheduled by a contractor via Hello! on 9/20/2005 at 7:01:39 AM. Contact: ###-####. u/g auditorium 1st floor, u/g for main service
ELE05-03432 Final9/20/20059/20/20059/20/2005 12:00:00 AMPPASS
###-#### glenn
ELE05-03433 Permanent Service9/20/20059/20/20059/20/2005 12:00:00 AMPFAIL
glenn ###-#### fail met contractor, 250.52 or104 grd or bond service, p/s set too high breakers over 6ft7", 250.148 terminate all equip grds together and tag box
ELE05-03433 Final9/20/20059/20/20059/20/2005 12:00:00 AMPPASS
glenn ###-####