ELE05-03422
| Rough-In Permanent Service | 9/20/2005 | 9/20/2005 | 9/20/2005 4:41:59 PM | P | NR |
|
|
APROX. 3 PM FOR INSPECTION PLEASE; Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack met with contractor
|
ELE05-03376
| Electrical Rough-In | 9/20/2005 | 9/20/2005 | 9/20/2005 4:22:49 PM | P | FAIL |
|
|
tom; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called , cor. posted still needs 300.4 and add required outlet for kit counter space added after inspection
|
ELE05-03430
| Temporary Service | 9/20/2005 | 9/20/2005 | 9/20/2005 3:22:49 PM | P | FAIL |
|
|
###-#### - john cor. posted called needs conn for GEC, replace or protect #8 GEC
|
ELE05-03426
| Temporary Service | 9/20/2005 | 9/20/2005 | 9/20/2005 2:42:39 PM | P | FAIL |
|
|
###-#### tim 250.25 terminate GEC so neutral is grounded, 250.53(G) drive grd rod flush cor. posted called left message
|
ELE05-03424
| Final | 9/20/2005 | 9/20/2005 | 9/20/2005 2:19:52 PM | P | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Dana Moyer could not located called left message, what do you want finaled?
|
ELE05-02951
| Final | 9/19/2005 | 9/20/2005 | 9/20/2005 12:48:40 PM | A | PASS |
|
|
charlene; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa note house was not wired to meet code, owner complained about correction, persons above me allowed wiring less than 2005 NEC, final by them
|
ELE05-01897
| Final | 9/19/2005 | 9/20/2005 | 9/20/2005 10:54:16 AM | A | NH |
|
|
darren; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa notice posted called
|
ELE05-03417
| Electrical Rough-In | 9/19/2005 | 9/20/2005 | 9/20/2005 10:41:09 AM | A | PART |
|
|
unground post light insp --jim ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok no romex allowed in conduit
|
ELE05-02555
| Electrical Rough-In | 9/19/2005 | 9/20/2005 | 9/20/2005 10:40:27 AM | A | FAIL |
|
|
unground post light insp --jim ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie not ready u/g installed by general, not electrical, and over 360 degrees of bends, do not cover posted called
|
ELE05-03025
| Electrical Rough-In | 9/19/2005 | 9/20/2005 | 9/20/2005 10:02:48 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 9/19/2005 at 1:00:28 PM. Contact: ###-####. kit and basement ok
|
ELE05-02730
| Electrical Rough-In | 9/20/2005 | 9/20/2005 | 9/20/2005 8:39:22 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 9/20/2005 at 7:01:39 AM. Contact: ###-####. u/g auditorium 1st floor, u/g for main service
|
ELE05-03432
| Final | 9/20/2005 | 9/20/2005 | 9/20/2005 12:00:00 AM | P | PASS |
|
|
###-#### glenn
|
ELE05-03433
| Permanent Service | 9/20/2005 | 9/20/2005 | 9/20/2005 12:00:00 AM | P | FAIL |
|
|
glenn ###-#### fail met contractor, 250.52 or104 grd or bond service, p/s set too high breakers over 6ft7", 250.148 terminate all equip grds together and tag box
|
ELE05-03433
| Final | 9/20/2005 | 9/20/2005 | 9/20/2005 12:00:00 AM | P | PASS |
|
|
glenn ###-####
|