FIR03-00329
| INSP-Final Inspection | 9/19/2005 | 9/20/2005 | 9/20/2005 4:24:51 PM | P | PASS |
|
|
Hood suppression system operated correctly under test conditions, permit finaled.
|
BLD05-01707
| FIRE-Final Inspection | 9/19/2005 | 9/20/2005 | 9/20/2005 3:56:10 PM | P | PASS |
|
|
Items on correction notice have been completed, fire life safety finaled.
|
FIR03-00398
| INSP-Final Inspection | 9/19/2005 | 9/20/2005 | 9/20/2005 3:25:04 PM | P | PASS |
|
|
Hood suppression system operated correctly under test conditions, permit finaled.
|
BLD05-02307
| FIRE-Final Inspection | 9/20/2005 | 9/20/2005 | 9/20/2005 3:23:19 PM | P | FAIL |
|
|
One sprinkler head in the NW room is overspaced from the new wall, a fire sprinkler permit will be required for correction, provide an additional emergency light at south hall in front of restrooms, lower height of the provided fire ext. to no higher than 48" AFF, verify sprinkler system is current with an annual inspection.
|
BLD05-01632
| FIRE-Final Inspection | 9/19/2005 | 9/20/2005 | 9/20/2005 1:48:12 PM | P | FAIL |
|
|
The new wall configuration has caused fire sprinklers in two locations to be overspaced. A fire sprinkler permit will be required for this work to be completed, inspected and approved prior to life safety sign-off, need to install fire ext. as discussed.
|
BLD05-01975
| FIRE-Final Inspection | 9/19/2005 | 9/20/2005 | 9/20/2005 1:43:58 PM | P | PASS |
|
|
Fire life safety passed inspection.
|
FIR05-00328
| INSP-Final Inspection | 9/19/2005 | 9/20/2005 | 9/20/2005 11:00:51 AM | A | PASS |
|
|
Fire sprinkler work is satisfactory, permit finaled.
|
BLD05-02029
| FIRE-Final Inspection | 9/19/2005 | 9/20/2005 | 9/20/2005 10:41:57 AM | A | FAIL |
|
|
HVAC duct smoke detectors failed to shut down unit upon activation, manual surface bolts at restroom doors are not ADA approved see note #5 on attatched fire code review.
|
FIR05-00474
| INSP-Final Inspection | 9/13/2005 | 9/20/2005 | 9/20/2005 9:27:18 AM | A | NR |
|
|
Appliances have not been installed, electrical is not ready. Contractor to reschedule when complete for inspection.
|
FIR04-00724
| INSP-Final Inspection | 9/16/2005 | 9/20/2005 | 9/20/2005 9:23:34 AM | A | PASS |
|
|
Fire sprinkler passed inspection, permit finaled.
|
FIR05-00498
| INSP-Final Inspection | 9/20/2005 | 9/20/2005 | 9/20/2005 12:00:00 AM | P | PASS |
|
|
Fire sprinkler finaled.
|