Inspections for the day of: Tuesday, September 20, 2005.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00329 INSP-Final Inspection9/19/20059/20/20059/20/2005 4:24:51 PMPPASS
Hood suppression system operated correctly under test conditions, permit finaled.
BLD05-01707 FIRE-Final Inspection9/19/20059/20/20059/20/2005 3:56:10 PMPPASS
Items on correction notice have been completed, fire life safety finaled.
FIR03-00398 INSP-Final Inspection9/19/20059/20/20059/20/2005 3:25:04 PMPPASS
Hood suppression system operated correctly under test conditions, permit finaled.
BLD05-02307 FIRE-Final Inspection9/20/20059/20/20059/20/2005 3:23:19 PMPFAIL
One sprinkler head in the NW room is overspaced from the new wall, a fire sprinkler permit will be required for correction, provide an additional emergency light at south hall in front of restrooms, lower height of the provided fire ext. to no higher than 48" AFF, verify sprinkler system is current with an annual inspection.
BLD05-01632 FIRE-Final Inspection9/19/20059/20/20059/20/2005 1:48:12 PMPFAIL
The new wall configuration has caused fire sprinklers in two locations to be overspaced. A fire sprinkler permit will be required for this work to be completed, inspected and approved prior to life safety sign-off, need to install fire ext. as discussed.
BLD05-01975 FIRE-Final Inspection9/19/20059/20/20059/20/2005 1:43:58 PMPPASS
Fire life safety passed inspection.
FIR05-00328 INSP-Final Inspection9/19/20059/20/20059/20/2005 11:00:51 AMAPASS
Fire sprinkler work is satisfactory, permit finaled.
BLD05-02029 FIRE-Final Inspection9/19/20059/20/20059/20/2005 10:41:57 AMAFAIL
HVAC duct smoke detectors failed to shut down unit upon activation, manual surface bolts at restroom doors are not ADA approved see note #5 on attatched fire code review.
FIR05-00474 INSP-Final Inspection9/13/20059/20/20059/20/2005 9:27:18 AMANR
Appliances have not been installed, electrical is not ready. Contractor to reschedule when complete for inspection.
FIR04-00724 INSP-Final Inspection9/16/20059/20/20059/20/2005 9:23:34 AMAPASS
Fire sprinkler passed inspection, permit finaled.
FIR05-00498 INSP-Final Inspection9/20/20059/20/20059/20/2005 12:00:00 AMPPASS
Fire sprinkler finaled.