Inspections for the day of: Thursday, September 20, 2007.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00490 INSP-Final Inspection9/19/20079/20/20079/24/2007 9:43:00 AMAFAIL
The DSW head installed appears to be the wrong temperature-verify exta high temp. is provided, the flow switch at the SW supply pipe is not connected, provide approved access hatch as described per fire code review notes.
FIR07-00614 INSP-Final Inspection9/20/20079/20/20079/21/2007 1:46:15 PMPPASS
Resubmittals verified for compliance, final fire sprinkler inspection passed.
FIR07-00772 INSP-Sprinkler Rough-in9/19/20079/20/20079/21/2007 10:56:27 AMAPART
Two existing standard response heads at the east corner need to be QR type matching the new heads installed in the same fire area, also missing hangers at five arm-overs to new pendent heads, see plans for annotations, rough-in approved for cover pending corrections.
BLD07-00625 FIRE-Conference9/19/20079/20/20079/21/2007 10:27:40 AMADONE
On site conference regarding fire sprinkler coverage at a storage room below the entry stairway, also discussed fire alarm permit work.
FIR07-00344 INSP-Sprinkler Rough-in9/20/20079/20/20079/20/2007 3:50:00 PMPPART
Begin 24 hr. air testing of the two new dry systems at 42psi each @3:30 pm.
BLD07-01848 FIRE-Final Inspection9/20/20079/20/20079/20/2007 3:45:53 PMPFAIL
Need to final project related fire sprinkler permit prior to life safety final, missing ceiling tile, floor coverings, electrical junction boxes are open, project is not ready for final at this time.
BLD06-00740 FIRE-Final Inspection9/19/20079/20/20079/20/2007 2:57:54 PMPPASS
Fire life safety finaled, c/n items are complete.
BLD07-00851 FIRE-Final Inspection9/19/20079/20/20079/20/2007 2:56:53 PMPPASS
Required corrections are finished, fire life safety final inspection passed.
BLD06-00500 FIRE-Final Inspection9/19/20079/20/20079/20/2007 2:55:43 PMPPASS
All noted items for correction have been completed, fire life safety inspection passed.
FIR06-00753 INSP-Final Inspection9/20/20079/20/20079/20/2007 2:54:16 PMPPASS
UG fire supply line permit finaled.
FIR07-00501 INSP-Final Inspection9/19/20079/20/20079/20/2007 2:53:04 PMAPASS
Noted items at the previous inspection have been verified for completion, fire sprinkler permit finaled.
FIR06-00995 INSP-Final Inspection9/19/20079/20/20079/20/2007 2:02:39 PMAPASS
Final inspection passed, supply line flushed, double check backflow to be certified today, one missing escutcheon installed and travel cap at the ssu at the riser removed while on site, also need to install a test orifice at the inspectors test connection.
FIR07-00619 INSP-Sprinkler Rough-in/Hydro9/19/20079/20/20079/20/2007 1:51:32 PMANR
Permit work is not yet completed for inspection at this time.
FIR07-00718 INSP-Sprinkler Rough-in/Hydro9/19/20079/20/20079/20/2007 1:49:56 PMAPART
Overhead rough-in is acceptable, no access provided to a janitors room-will verifiy at next visit, noted a hydrostatic test for this portion of the building has been completed,
FIR07-00316 INSP-Sprinkler Rough-in/Hydro9/19/20079/20/20079/20/2007 1:46:45 PMAPASS
UG fire supply line passed hydrostatic testing.
FIR07-00620 INSP-Sprinkler Rough-in9/19/20079/20/20079/20/2007 1:41:27 PMAPART
Remainder of the overhead rough-in is approved for cover as noted on stamped plan set.