Inspections for the day of: Thursday, September 20, 2007.
Number of inspections: 18
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00958 INSP-Final Inspection9/20/20079/20/20079/20/2007 4:11:41 PMPCANC
Overbooked with Micron plan review.
FIR06-00956 INSP-Final Inspection9/20/20079/20/20079/20/2007 4:11:18 PMPCANC
Overbooked with Micron plan review.
FIR06-00957 INSP-Final Inspection9/20/20079/20/20079/20/2007 4:11:01 PMPCANC
Overbooked with Micron plan review.
FIR06-00811 INSP-Alarm Testing9/18/20079/20/20079/20/2007 3:57:45 PMACANC
Overbooked with Micron plan review.
BLD07-01008 FIRE-Conference9/19/20079/20/20079/20/2007 3:56:54 PMACANC
Wrong inspection type called in.
FIR07-00130 INSP-Final Inspection9/19/20079/20/20079/20/2007 3:20:16 PMAFAIL
It appears that the only item remaining is the approval of the relocation of the fire dept connection from the west end of the building to around to the north side of the building. The forward flow test has passed.
FIR07-00586 INSP-Sprinkler Rough-in9/19/20079/20/20079/20/2007 3:18:00 PMACANC
See yesterdays inspection comments.
FIR07-00582 INSP-Sprinkler Rough-in9/19/20079/20/20079/20/2007 3:17:33 PMACANC
See yesterdays inspection comments.
FIR07-00585 INSP-Sprinkler Rough-in9/19/20079/20/20079/20/2007 3:17:16 PMACANC
See yesterdays inspection comments.
FIR07-00534 INSP-Final Inspection9/19/20079/20/20079/20/2007 3:15:57 PMPCANC
Please call 1/2 hour prior to inspection. Brian is the contact, thank you. Phone #: ###-#### Internet Inspection Request from: Stan Beus Inspection cancelled from web by: Stan Beus
BLD06-01695 FIRE-Final Inspection9/20/20079/20/20079/20/2007 3:15:40 PMPFAIL
Provide building address, provide fire dept access signage, repair the exit discharge light at the first floor north center exit, repair the third floor center exit light, provide emergency lighting in both of the stairwells as per plan, provide annual inspection tags for the fire extinguishers, final fire alarm permit and fire sprinkler permits.
FIR07-00336 INSP-Sprinkler Rough-in/Hydro9/19/20079/20/20079/20/2007 2:43:07 PMAPART
The first floor system passed but the upper level piping hydro test failed. Also the fire dept connection needs hydro tested.
FIR07-00163 INSP-Sprinkler Rough-in9/19/20079/20/20079/20/2007 1:46:08 PMPCANC
OH Cover Inspection
Phone #: ###-#### x1234 Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley
BLD05-00633 FIRE-Final Inspection9/19/20079/20/20079/20/2007 1:01:42 PMACANC
Need the project related fire alarm and fire sprinkler finaled.
FIR06-00988 INSP-Supply line flush9/19/20079/20/20079/20/2007 12:31:18 PMAFAIL
Arrived at the job site but the contractor was not there. Needs to be rescheduled.
BLD07-01646 FIRE-Final Inspection9/20/20079/20/20079/20/2007 10:09:53 AMAPASS
life safety passed.
BLD07-01819 FIRE-Final Inspection9/20/20079/20/20079/20/2007 9:36:28 AMPFAIL
Enclosed combustible patios have been constructed in the warehouse/showroom. These require sprinkler protection. I went over this with the owner. The fire extinguishers need their annual inspection and the exit sign/emergency lights need tested.
BLD07-01008 FIRE-Final Inspection9/20/20079/20/20079/20/2007 8:41:30 AMPPASS
life safety passed