FIR06-00958
| INSP-Final Inspection | 9/20/2007 | 9/20/2007 | 9/20/2007 4:11:41 PM | P | CANC |
|
|
Overbooked with Micron plan review.
|
FIR06-00956
| INSP-Final Inspection | 9/20/2007 | 9/20/2007 | 9/20/2007 4:11:18 PM | P | CANC |
|
|
Overbooked with Micron plan review.
|
FIR06-00957
| INSP-Final Inspection | 9/20/2007 | 9/20/2007 | 9/20/2007 4:11:01 PM | P | CANC |
|
|
Overbooked with Micron plan review.
|
FIR06-00811
| INSP-Alarm Testing | 9/18/2007 | 9/20/2007 | 9/20/2007 3:57:45 PM | A | CANC |
|
|
Overbooked with Micron plan review.
|
BLD07-01008
| FIRE-Conference | 9/19/2007 | 9/20/2007 | 9/20/2007 3:56:54 PM | A | CANC |
|
|
Wrong inspection type called in.
|
FIR07-00130
| INSP-Final Inspection | 9/19/2007 | 9/20/2007 | 9/20/2007 3:20:16 PM | A | FAIL |
|
|
It appears that the only item remaining is the approval of the relocation of the fire dept connection from the west end of the building to around to the north side of the building. The forward flow test has passed.
|
FIR07-00586
| INSP-Sprinkler Rough-in | 9/19/2007 | 9/20/2007 | 9/20/2007 3:18:00 PM | A | CANC |
|
|
See yesterdays inspection comments.
|
FIR07-00582
| INSP-Sprinkler Rough-in | 9/19/2007 | 9/20/2007 | 9/20/2007 3:17:33 PM | A | CANC |
|
|
See yesterdays inspection comments.
|
FIR07-00585
| INSP-Sprinkler Rough-in | 9/19/2007 | 9/20/2007 | 9/20/2007 3:17:16 PM | A | CANC |
|
|
See yesterdays inspection comments.
|
FIR07-00534
| INSP-Final Inspection | 9/19/2007 | 9/20/2007 | 9/20/2007 3:15:57 PM | P | CANC |
|
|
Please call 1/2 hour prior to inspection. Brian is the contact, thank you. Phone #: ###-#### Internet Inspection Request from: Stan Beus Inspection cancelled from web by: Stan Beus
|
BLD06-01695
| FIRE-Final Inspection | 9/20/2007 | 9/20/2007 | 9/20/2007 3:15:40 PM | P | FAIL |
|
|
Provide building address, provide fire dept access signage, repair the exit discharge light at the first floor north center exit, repair the third floor center exit light, provide emergency lighting in both of the stairwells as per plan, provide annual inspection tags for the fire extinguishers, final fire alarm permit and fire sprinkler permits.
|
FIR07-00336
| INSP-Sprinkler Rough-in/Hydro | 9/19/2007 | 9/20/2007 | 9/20/2007 2:43:07 PM | A | PART |
|
|
The first floor system passed but the upper level piping hydro test failed. Also the fire dept connection needs hydro tested.
|
FIR07-00163
| INSP-Sprinkler Rough-in | 9/19/2007 | 9/20/2007 | 9/20/2007 1:46:08 PM | P | CANC |
|
|
OH Cover Inspection
Phone #: ###-#### x1234 Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley
|
BLD05-00633
| FIRE-Final Inspection | 9/19/2007 | 9/20/2007 | 9/20/2007 1:01:42 PM | A | CANC |
|
|
Need the project related fire alarm and fire sprinkler finaled.
|
FIR06-00988
| INSP-Supply line flush | 9/19/2007 | 9/20/2007 | 9/20/2007 12:31:18 PM | A | FAIL |
|
|
Arrived at the job site but the contractor was not there. Needs to be rescheduled.
|
BLD07-01646
| FIRE-Final Inspection | 9/20/2007 | 9/20/2007 | 9/20/2007 10:09:53 AM | A | PASS |
|
|
life safety passed.
|
BLD07-01819
| FIRE-Final Inspection | 9/20/2007 | 9/20/2007 | 9/20/2007 9:36:28 AM | P | FAIL |
|
|
Enclosed combustible patios have been constructed in the warehouse/showroom. These require sprinkler protection. I went over this with the owner. The fire extinguishers need their annual inspection and the exit sign/emergency lights need tested.
|
BLD07-01008
| FIRE-Final Inspection | 9/20/2007 | 9/20/2007 | 9/20/2007 8:41:30 AM | P | PASS |
|
|
life safety passed
|