Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD09-00832 FIRE-Conference9/6/20119/20/20119/22/2011 12:26:53 PMADONE
I spoke to Jesse about the permit status
FIR11-00095 INSP-Sprinkler Rough-in/Hydro9/20/20119/20/20119/20/2011 3:35:55 PMPPASS
The hydro test on the remaining riser pass. Also another portion of the warehouse was inspected with minor corrections noted.
FIR11-00498 INSP-Supply line flush9/19/20119/20/20119/20/2011 3:33:39 PMPFAIL
The manual pull station is mounted too high, Also after a discussion it was fount that the exhaust fan does not stay on and the makeup air shut off when the the system activates. The lights under the hood also need to be verified that they shut off when the suppression system activates. No inspection was actually done.
BLD11-01701 FIRE-Final Inspection9/20/20119/20/20119/20/2011 3:30:27 PMPPASS
life safety passed.
FIR11-00378 INSP-Final Inspection9/20/20119/20/20119/20/2011 3:29:22 PMPCANC
Jason Phone #: ###-####
BLD11-00380 FIRE-Final Inspection9/20/20119/20/20119/20/2011 2:22:05 PMAPASS
life safety passed
FIR11-00330 INSP-Final Inspection9/16/20119/20/20119/20/2011 2:00:54 PMAFAIL
The 24 hour air test passed. The project can not be finaled until the inter connections with the fire alarm panel have been tested.
FIR11-00378 INSP-Final Inspection9/19/20119/20/20119/20/2011 12:08:02 PMAFAIL
There is no audible or visual annunciation of an alarm condition at the fire alarm panel as required by IFC 906. Burl is going to install a remote annunciator at the panel and re-inspect for this afternoon.
MIS11-00182 FIR-Conference9/19/20119/20/20119/20/2011 12:03:50 PMADONE
Met with Dixie, the owner and the mechanical contractor and went over installation and permitting requirements It appears that a permit fo the new suppression has been pulled.
FIR11-00422 INSP-Final Inspection9/20/20119/20/20119/20/2011 11:55:21 AMPPASS
Permit finaled
BLD11-01985 FIRE-Final Inspection9/19/20119/20/20119/20/2011 11:30:08 AMAPASS
life safety passed.
FIR11-00475 INSP-Final Inspection9/19/20119/20/20119/20/2011 11:29:25 AMAPASS
permit finaled.
FIR11-00238 INSP-Final Inspection9/19/20119/20/20119/19/2011 3:25:03 PMAPASS
permit finaled. owner is removing the palm fronds that are blocking the sidewall protection in the seating area.