Inspections for the day of: Friday, September 20, 2013.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD13-00479 FIRE-Final Inspection9/19/20139/20/20139/20/2013 4:46:05 PMPPASS
Fire life safety inspection completed acceptable.
FIR13-00274 INSP-Final Inspection9/20/20139/20/20139/20/2013 4:41:39 PMPPASS
Fire alarm work passed after corrections made on site. Permit finaled.
FIR13-00387 INSP-Sprinkler Rough-in9/19/20139/20/20139/20/2013 3:32:43 PMAPART
Okay to cover overhead work at the new grid ceiling areas. Noted one painted upright head at the expanded storage room will need replaced prior to final approval.
FIR13-00308 INSP-Sprinkler Rough-in9/19/20139/20/20139/20/2013 2:59:43 PMPCANC
Overbooked
FIR13-00399 INSP-Sprinkler Rough-in9/19/20139/20/20139/20/2013 2:56:13 PMAPART
Overhead work at the first floor area 1 and second floor areas 1,2,and 3 okay for drop ceiling cover.
FIR13-00507 INSP-Sprinkler Rough-in9/19/20139/20/20139/20/2013 2:21:46 PMPPART
Okay to cover fire sprinkler work above the sheetrock lids as marked on approved plans. Need to revise coverage at the office, provide intermediate temp heads within the fireplace zone of influence, coolers/DP are not yet installed.
FIR13-00492 INSP-Alarm Testing9/20/20139/20/20139/20/2013 1:21:34 PMPPASS
Fire alarm work passed acceptance testing.
FIR13-00482 INSP-Final Inspection9/19/20139/20/20139/20/2013 1:18:36 PMAPASS
Final inspection completed satisfactory. Fire sprinkler permit finaled.
FIR13-00266 INSP-Final Inspection9/19/20139/20/20139/20/2013 11:08:06 AMAPASS
C/N items finished. Reinspection passed. Fire sprinkler permit finaled.
FIR13-00501 INSP-Final Inspection9/18/20139/20/20139/20/2013 11:05:05 AMAPASS
Scope of fire alarm work passed inspection. Permit finaled.
BLD13-01690 FIRE-Final Inspection9/19/20139/20/20139/20/2013 11:03:56 AMAPASS
Noted correction items verified for completion. Life safety finaled.