Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE16-00089 Electrical Rough-In9/20/20169/20/20169/20/2016 3:46:37 PMPPASS
Call Rafael for TCO inspection of the 2nd floor area "C". Phone #: ###-#### Inspection requested via web by Rafael Castillo
TCO level 2 district building ok
ELE15-00495 Electrical Rough-In9/20/20169/20/20169/20/2016 3:33:51 PMAPASS
Walk 2nd floor 5 story for TCO. Contact is Toby Groves. ###-#### Phone #: ###-#### Inspection requested via web by Toby Groves
Levels 1, 2, 3, core and shell temp occupy ok
ELE13-01291 Conference9/19/20169/20/20169/20/2016 9:59:02 AMADONE
Tony ###-####. Flag pole bases.
Contractor investigated base construction and rebar of flag pole base connected to building rebar system. Additional electrode not required as complete area installed above water membrane so true earth not available by installation of ground rods. Installation as is is sufficient.
ELE16-02164 Final9/20/20169/20/20169/20/2016 9:37:08 AMAFAIL
3535E Phone #: ###-#### Inspection requested via web by Alan Lusk
410.16- Luminaire shall have 12" clearance from storage shelf in closet under stairway.
422.20- Furnace shall have a disconnecting means with in sight of unit.