Inspections for the day of: Wednesday, September 20, 2017.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR17-00323 INSP-Sprinkler Rough-in9/20/20179/20/20179/20/2017 2:01:39 PMPFAIL
Underground supply piping does not meet the min. 4'6" bury depth.
FIR17-00322 INSP-Sprinkler Rough-in9/20/20179/20/20179/20/2017 2:01:09 PMPFAIL
Underground supply piping does not meet the min. 4'6" bury depth.
BLD17-00665 FIRE-Conference9/20/20179/20/20179/20/2017 1:18:54 PMPDONE
Mark and I discussed the security features on the new door in the exit corridor. I also discussed this with Carl Madsen in plan review. This door will need to meet all of the requirements in the IFC and IBC for Access Controled Egress Doors which includes the sensor. The Training Room needs two exits and this door causes issues with the secondary exiting from the Training Room per Carl. So plans will need to be re-submitted to plan review for possible approval of a different exiting system
FIR17-00503 INSP-Final Inspection9/19/20179/20/20179/20/2017 1:04:26 PMPPASS
Permit finaled
BLD17-01746 FIRE-Conference9/20/20179/20/20179/20/2017 9:34:02 AMPDONE
Rick and I discussed the new double exit doors. Per Rick doors will not be installed until November and when installed will not impede exiting. Right now no doors will be installed. I'm ok with this but will need to inspect operation when installed. Fire sprinkler permit is finaled, fire alarm permit has not been inspected nor has life safety yet.
BLD17-01746 FIRE-Supply Line Hydro9/19/20179/20/20179/20/2017 9:31:31 AMACANC
Wrong inspection type called in.
Rick Phone #: ###-####
BLD17-03203 FIRE-Final Inspection9/19/20179/20/20179/20/2017 8:10:34 AMAFAIL
Provide plan mod for the kitchen sink/fixtures/counter that has been built. Repair the exit sign/emergency light at the back door. Repair the emergency light at the kitchen sink. Remove the deadbolt from the rear exit door.

Lex Phone #: ###-####
FIR17-00514 INSP-Final Inspection9/19/20179/20/20179/19/2017 10:57:27 AMACANC
As early as possible Phone #: 2089411846 >> Inspection requested via mobile web by SVC Brian A Inspection cancelled via mobile web on Tuesday, September 19, 2017.