ELE18-03608
| Electrical Rough-In | 9/20/2018 | 9/20/2018 | 9/20/2018 3:18:14 PM | P | PASS |
|
|
This Is All Ready For Inspection And Any Questions Or Concerns Please Feel Free To Call Me Dave ###-#### Phone #: ###-#### Inspection requested via web by jason shifflett Lobby area under stairs and receptacle for wall if needed, Walls and hardlid understair rough in ok cover
|
ELE18-03496
| Electrical Rough-In | 9/18/2018 | 9/20/2018 | 9/20/2018 2:22:12 PM | P | PASS |
|
|
Electrical reenergize inspection. Contact Kurtis with any questions Phone #: ###-#### Inspection requested via web by Christy Cheney Master bed, bath, and closet addition rough in ok cover
|
ELE18-03496
| Permanent Service | 9/20/2018 | 9/20/2018 | 9/20/2018 2:04:48 PM | P | PASS |
|
|
Electrical reenergize inspection. Contact Kurtis with any questions Phone #: ###-#### Inspection requested via web by Christy Cheney p/s o/h rec ok
|
ELE18-03224
| Electrical Rough-In | 9/20/2018 | 9/20/2018 | 9/20/2018 1:52:11 PM | P | PASS |
|
|
Contact: Wes Powell Underground inspection please Phone #: ###-#### Inspection requested via web by Deb Gooden Underground along west side of gym foundation to north 2 4" conduits stopped at north side. Rough in ok cover
|
ELE18-03171
| Final | 9/19/2018 | 9/20/2018 | 9/20/2018 1:19:00 PM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by BRS Permitting Final ok
|
ELE18-03464
| Final | 9/19/2018 | 9/20/2018 | 9/20/2018 12:52:12 PM | A | PASS |
|
|
Pls contact Bryce (Foreman) @ ###-#### or George (Electrician) @ ###-#### one hr prior or if you have any questions. Thank you. Inspection requested via web by Rob Maes Final ok
|
ELE05-04504
| Final | 9/20/2018 | 9/20/2018 | 9/20/2018 12:40:22 PM | P | PASS |
|
|
Contact called and met at 12:30 and completed service inspection. Final ok
|
ELE05-04504
| Final | 9/19/2018 | 9/20/2018 | 9/20/2018 11:58:13 AM | A | NH |
|
|
call atleast 1/2 before to meet for access// Brent Phone #: ###-#### Called contact, no answer, left message to recall when someone is available.
|
ELE18-03600
| Final | 9/19/2018 | 9/20/2018 | 9/20/2018 11:53:58 AM | A | FAIL |
|
|
Please call Marvin a half hour before inspection Phone #: ###-#### Inspection requested via web by Charles Davis New electrical contractor to complete work of permit ELE12-01429. 300.15- All wiring shall terminate in a box. Loose wiring in mechanical room off coverted garage room. 406.3(D)- Where grounding type receptacles have been installed on ungrounded circuits they shall either be changed to 2 prong ungrounding type receptacles or have GFCI protection.
|
ELE12-01429
| Final | 9/20/2018 | 9/20/2018 | 9/20/2018 11:53:35 AM | P | PASS |
|
|
Job completed under ELE18-03600. Final ok
|
ELE18-03444
| Rough-In Permanent Service | 9/19/2018 | 9/20/2018 | 9/20/2018 10:42:22 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn Rough in ok cover p/s u/g n ok
|
ELE18-03442
| Rough-In Permanent Service | 9/19/2018 | 9/20/2018 | 9/20/2018 10:25:04 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn Attic upstairs boxes trimmed at rough in, christmas switches located in entry closet, 327 has pics of 12-2 stubs in family room off kitchen. 250.24- Grounding electrode conductor connection shall connect to grounded conductor in 1 location only. Jumper installed from main breaker panel to meter base creating parallel path between grounded conductor and grounding conductor. 250.68(A)- Connection to concrete encased electrode shall remain accessible. Need mudring. 300.4- Where NM cable is run through bored holes that do not maintain 1 1/4" from framing surface they shall be protected by nail plates. By garage man door, above mudroom switches, pantry wire to under stair light. 348.26- Maximum number of bends in FMC to single garage attic shall not exceed 360 degrees.
|