FIR18-00414
| INSP-Sprinkler Rough-in | 9/19/2018 | 9/20/2018 | 9/21/2018 12:00:00 AM | A | PART |
|
|
Phone #: ###-#### >> Inspection requested via web by Stan Beus
______________
Barely got started before I ran out of time. There is problems with conduits in the storage area. ESFR can not have obstruction. Went over the problem with the fitter and GC. Sway branch line restraints were missing in the office area I checked.
|
FIR18-00727
| INSP-Final Inspection | 9/19/2018 | 9/20/2018 | 9/20/2018 12:00:00 AM | A | PASS |
|
|
ADAM CHITWOOD Phone #: ###-#### >> Inspection requested via web by Brodie Stenquist
|
FIR18-00511
| INSP-Supply line flush | 9/20/2018 | 9/20/2018 | 9/20/2018 12:00:00 AM | A | PASS |
|
|
Flush and forward flush. Call Anthony to coordinate Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello
_________
Flush was ok.
Forward flow test failed. Could not achieve 12 Psi:
|
FIR16-00563
| INSP-Supply line flush | 9/17/2018 | 9/20/2018 | 9/20/2018 12:00:00 AM | A | PASS |
|
|
Coordinate Fire Service flush with Lonnie Greenfield Phone #: ###-#### >> Inspection requested via web by Christophe Wilson
___________________
Flush was ok
|