MIS05-00124
| FIR-Final | 9/16/2005 | 9/21/2005 | 9/21/2005 3:59:26 PM | P | PASS |
|
|
Life safety passed inspection.
|
BLD05-01993
| FIRE-Final Inspection | 9/21/2005 | 9/21/2005 | 9/21/2005 3:58:17 PM | A | FAIL |
|
|
Repair emergency light at north stairway, provide lever hardware at restroom, provide directional arrow at main exit sign, need to final sprinkler permit prior to life safety.
|
MIS05-00093
| FIR-Final | 9/20/2005 | 9/21/2005 | 9/21/2005 3:04:30 PM | A | FAIL |
|
|
East exit door must swing outward-also provide ADA approved door hardware at this location, provide current annual inspection on the fire ext. and lower handle to 48" AFF, remove manual flush bolts at main entry/exit and provide sign above door, provide illuminated exit signs, remove latch at cooler door.
|
BLD05-02356
| FIRE-Final Inspection | 9/20/2005 | 9/21/2005 | 9/21/2005 2:03:44 PM | A | FAIL |
|
|
Provide building address, the removal of office 106 has caused sprinkler overspacing in this location, remove manual thumbturn at door from hall 110 to 108, verify current annual inspection on fire sprinkler system, three exit signs fail to operate under backup power.
|
FIR05-00521
| INSP-Sprinkler Rough-in/Hydro | 9/20/2005 | 9/21/2005 | 9/21/2005 11:33:58 AM | A | FAIL |
|
|
Provide approved plans reflecting the actual installation, some areas in the southeast corner lack sufficient coverage.
|
FIR05-00424
| INSP-Supply line flush | 9/20/2005 | 9/21/2005 | 9/21/2005 10:30:06 AM | A | PART |
|
|
UG fire supply line flush is satisfactory.
|
BLD05-02005
| FIRE-Final Inspection | 9/20/2005 | 9/21/2005 | 9/21/2005 9:36:06 AM | A | FAIL |
|
|
Provide street address numbers, install fire extinguisher as discussed, provide approved hardware at the restroom and back exit doors, verify correct hardware at two doors which are not installed at this time.
|