Inspections for the day of: Wednesday, September 21, 2005.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorWilliam E Thomas
TitleELE-INSPECTOR
Phone #794-9492
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-03135 Electrical Rough-In9/21/20059/21/20059/22/2005 1:46:17 PMPFAIL
Scheduled by a contractor via Hello! on 9/21/2005 at 9:26:35 AM. Contact: ###-####.
rebar needs to be blocked off the ground so as to be in the concrete when poured
ELE05-03448 Electrical Rough-In9/21/20059/21/20059/21/2005 10:33:39 PMPPASS
john ###-####
ri ok
ELE05-03423 Electrical Rough-In9/21/20059/21/20059/21/2005 10:33:13 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Dana Moyer
ri ok
ELE05-00855 Electrical Rough-In9/21/20059/21/20059/21/2005 3:30:18 PMPPASS
Contact: Lyle Dean - 1st floor re -inspection; Phone #: ###-#### Internet Inspection Request from: Deb McCoy
as noted on prints for slab ok to cover
ELE05-03444 Temporary Service9/21/20059/21/20059/21/2005 3:18:09 PMPFAIL
rob ###-####
1. 314.17 attach grounding electrode conductor to the box
2. replace all broken receps.
3. provide manufacturer specs for grounding/bonding of the service
ELE05-03443 Temporary Service9/21/20059/21/20059/21/2005 2:43:27 PMPPASS
rob ###-####
t/s u/g n ok
ELE05-01470 Final9/21/20059/21/20059/21/2005 12:51:45 PMPFAIL
ron; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
300.5 burial depth to be 18in or gfci protected for post light conduit
ELE05-03251 Rough-In Permanent Service9/20/20059/21/20059/21/2005 12:15:50 PMAPASS
Scheduled by a contractor via Hello! on 9/20/2005 at 11:10:34 AM. Contact: ###-####.
ri ok
p/s u/g n ok
ELE05-03431 Temporary Service9/20/20059/21/20059/21/2005 10:47:10 AMAFAIL
Scheduled by a contractor via Hello! on 9/20/2005 at 3:45:15 PM. Contact: ###-####.
314.17 grounding electrode conductor not fastened to box where it enters the box
weatherhead not serviceable
ELE05-01436 Final9/21/20059/21/20059/21/2005 10:13:34 AMAPASS
Scheduled by a contractor via Hello! on 9/21/2005 at 5:57:04 AM. Contact: ###-####.
ELE05-03403 Permanent Service9/20/20059/21/20059/21/2005 10:05:53 AMAPASS
Re inspection for corrections as per Pat Lass.; Phone #: ###-#### Internet Inspection Request from: Rich Rice
p/s o/h r ok
ELE05-03367 Electrical Rough-In9/20/20059/21/20059/21/2005 9:41:09 AMAPASS
Contact: Neil Ramsey; Phone #: ###-#### Internet Inspection Request from: Deb McCoy
walls ok to cover
ELE05-02931 Electrical Rough-In9/20/20059/21/20059/21/2005 9:40:43 AMAPASS
contact: Neil Ramsey; Phone #: ###-#### Internet Inspection Request from: Deb McCoy
walls ok to cover
ELE05-03245 Final9/19/20059/21/20059/21/2005 9:40:16 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Dana Moyer
survey note- label the panel
ELE05-03403 Final9/21/20059/21/20059/21/2005 12:00:00 AMAPASS