Inspections for the day of: Thursday, September 21, 2006.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorPat Lass
TitleELE-INSPECTOR
Phone #794-9478
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-02335 ELE-Aging Inspection9/21/20069/21/20069/25/2006 10:12:51 AM PASS
ELE06-03520 Electrical Rough-In9/21/20069/21/20069/21/2006 4:08:32 PMPPART
scott ###-####
east central U/G Ok
ELE06-03535 Temporary Service9/21/20069/21/20069/21/2006 3:39:34 PMPPASS
jason; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
t/S O/H Ok
ELE06-03123 Permanent Service9/21/20069/21/20069/21/2006 2:31:16 PMPFAIL
roger ; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley
concrete encased electrode required because the re-bar is only 3/8"
ELE06-03545 Electrical Rough-In9/21/20069/21/20069/21/2006 2:19:19 PMPPART
clyde - partial; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley
under floor ok
ELE06-03143 Electrical Rough-In9/20/20069/21/20069/21/2006 1:36:11 PMPPART
don; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
ceiling ANOP
ELE06-03212 Permanent Service9/21/20069/21/20069/21/2006 1:00:36 PMPPASS
pat; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley
P/S O/H R Ok to transfer power
ELE06-03524 Final9/20/20069/21/20069/21/2006 11:45:26 AMAFAIL
NEED FINAL ON SERVICE RISER REPLACEMENT, CAUSED BY FIRE DAMAGE. THANK YOU.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH
no dead front for panel and it is fed with undersized wire also no grounding. not much can be salvaged of this old service.
ELE06-03512 Electrical Rough-In9/20/20069/21/20069/21/2006 11:23:40 AMAPASS
mike - reinsp; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley
ELE06-03377 Electrical Rough-In9/21/20069/21/20069/21/2006 11:20:55 AMPCANC
Cover inspection. Questions please call Mike @ ###-####. Scheduled by Heather w/ Doherty; Phone #: ###-#### Internet Inspection Request from: Heather Packer Inspection cancelled from web by: Heather Packer
ELE06-01917 Final9/20/20069/21/20069/21/2006 10:36:00 AMAPASS
Scheduled by a contractor via Hello! on 9/20/2006 at 7:57:08 PM. Contact: ###-####.
final ok with survey for unused openings at service and installation of stiff leg if Idaho power doesn't change direction of drop.
ELE06-01917 Permanent Service9/21/20069/21/20069/21/2006 10:33:54 AMPPASS
Scheduled by a contractor via Hello! on 9/20/2006 at 7:57:08 PM. Contact: ###-####.
P/S O/H R Ok
ELE06-03493 Electrical Rough-In9/20/20069/21/20069/21/2006 10:21:14 AMAPART
Scheduled by a contractor via Hello! on 9/20/2006 at 3:02:27 PM. Contact: ###-####.lobby R/I Ok
ELE06-03519 Conference9/20/20069/21/20069/21/2006 9:03:24 AMAPART
conference on code upgrade; Phone #: ###-#### Internet Inspection Request from: joe wheeler
talked about burned up disconnect rewire.