Inspections for the day of: Friday, September 21, 2007.
Number of inspections: 18
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD07-00328 FIRE-Final Inspection9/21/20079/21/20079/21/2007 4:11:59 PMPPASS
Corrections are complete, verified resubmitted plans, fire life safety passed.
FIR07-00667 INSP-Final Inspection9/21/20079/21/20079/21/2007 4:10:53 PMPPASS
Fire sprinkler permit finaled.
BLD07-01718 FIRE-Final Inspection9/21/20079/21/20079/21/2007 3:49:59 PMPNR
Need to final project related fire sprinkler permit, missing door hardware at the storage room, provide approved hardware at one door as discussed, missing ceiling tile needs to be installed.
FIR07-00683 INSP-Final Inspection9/20/20079/21/20079/21/2007 3:47:07 PMPPART
Annual inspection is complete, still missing ceiling tile at several locations-need to install prior to final.
FIR07-00664 INSP-Final Inspection9/20/20079/21/20079/21/2007 3:44:49 PMPNR
Need NFPA 72 record of completion forms.
FIR07-00285 INSP-Sprinkler Rough-in9/20/20079/21/20079/21/2007 3:38:08 PMAPART
Noted correction items from the previous inspection are complete, OH rough-in is acceptable.
BLD06-01887 FIRE-Final Inspection9/20/20079/21/20079/21/2007 2:36:49 PMPCANC
Overbooked.
FIR07-00106 INSP-Final Inspection9/19/20079/21/20079/21/2007 2:36:03 PMAPART
OH hydrostatic testing passed inspection.
FIR07-00134 INSP-Final Inspection9/19/20079/21/20079/21/2007 2:35:08 PMAPART
OH hydrostatic testing completed satisfactory.
FIR07-00344 INSP-Sprinkler Rough-in/Hydro9/20/20079/21/20079/21/2007 2:33:19 PMPPASS
24 hour pneumatic testing for both dry systems passed, final pending alarm and tamper supervision, trip test, flex couplings at risers.
BLD06-03540 FIRE-Final Inspection9/21/20079/21/20079/21/2007 1:47:06 PMPPASS
Fire life safety final inspection passed.
FIR07-00204 INSP-Sprinkler Rough-in/Hydro9/21/20079/21/20079/21/2007 1:42:16 PMPPART
Retest of the overhead hydrostatic for the 3rd floor wet system passed.
FIR07-00063 INSP-Final Inspection9/20/20079/21/20079/21/2007 1:09:01 PMPCANC
Overbooked.
FIR07-00416 INSP-Final Inspection9/20/20079/21/20079/21/2007 1:08:27 PMPCANC
Overbooked.
BLD07-01734 FIRE-Final Inspection9/20/20079/21/20079/21/2007 1:07:34 PMAPASS
Fire life safety inspection passed, the surface bolt lock at the mens restroom removed while on site, noted separate permits have been issued for the adjacent express care project and fire sprinkler system modifications.
FIR07-00235 INSP-Sprinkler Rough-in/Hydro9/20/20079/21/20079/21/2007 1:04:44 PMAFAIL
Some items remian to be completed on the rough-in correction notice, overhead hydro is not ready for inspection.
FIR07-00236 INSP-Sprinkler Rough-in/Hydro9/20/20079/21/20079/21/2007 12:53:41 PMANR
System is not pressured for hydrostatic testing.
FIR07-00674 INSP-Final Inspection9/18/20079/21/20079/20/2007 2:33:06 PMPCANC
Phone #: ###-#### Internet Inspection Request from: Greg Kirkes Inspection cancelled from web by: Greg Kirkes