BLD07-00328
| FIRE-Final Inspection | 9/21/2007 | 9/21/2007 | 9/21/2007 4:11:59 PM | P | PASS |
|
|
Corrections are complete, verified resubmitted plans, fire life safety passed.
|
FIR07-00667
| INSP-Final Inspection | 9/21/2007 | 9/21/2007 | 9/21/2007 4:10:53 PM | P | PASS |
|
|
Fire sprinkler permit finaled.
|
BLD07-01718
| FIRE-Final Inspection | 9/21/2007 | 9/21/2007 | 9/21/2007 3:49:59 PM | P | NR |
|
|
Need to final project related fire sprinkler permit, missing door hardware at the storage room, provide approved hardware at one door as discussed, missing ceiling tile needs to be installed.
|
FIR07-00683
| INSP-Final Inspection | 9/20/2007 | 9/21/2007 | 9/21/2007 3:47:07 PM | P | PART |
|
|
Annual inspection is complete, still missing ceiling tile at several locations-need to install prior to final.
|
FIR07-00664
| INSP-Final Inspection | 9/20/2007 | 9/21/2007 | 9/21/2007 3:44:49 PM | P | NR |
|
|
Need NFPA 72 record of completion forms.
|
FIR07-00285
| INSP-Sprinkler Rough-in | 9/20/2007 | 9/21/2007 | 9/21/2007 3:38:08 PM | A | PART |
|
|
Noted correction items from the previous inspection are complete, OH rough-in is acceptable.
|
BLD06-01887
| FIRE-Final Inspection | 9/20/2007 | 9/21/2007 | 9/21/2007 2:36:49 PM | P | CANC |
|
|
Overbooked.
|
FIR07-00106
| INSP-Final Inspection | 9/19/2007 | 9/21/2007 | 9/21/2007 2:36:03 PM | A | PART |
|
|
OH hydrostatic testing passed inspection.
|
FIR07-00134
| INSP-Final Inspection | 9/19/2007 | 9/21/2007 | 9/21/2007 2:35:08 PM | A | PART |
|
|
OH hydrostatic testing completed satisfactory.
|
FIR07-00344
| INSP-Sprinkler Rough-in/Hydro | 9/20/2007 | 9/21/2007 | 9/21/2007 2:33:19 PM | P | PASS |
|
|
24 hour pneumatic testing for both dry systems passed, final pending alarm and tamper supervision, trip test, flex couplings at risers.
|
BLD06-03540
| FIRE-Final Inspection | 9/21/2007 | 9/21/2007 | 9/21/2007 1:47:06 PM | P | PASS |
|
|
Fire life safety final inspection passed.
|
FIR07-00204
| INSP-Sprinkler Rough-in/Hydro | 9/21/2007 | 9/21/2007 | 9/21/2007 1:42:16 PM | P | PART |
|
|
Retest of the overhead hydrostatic for the 3rd floor wet system passed.
|
FIR07-00063
| INSP-Final Inspection | 9/20/2007 | 9/21/2007 | 9/21/2007 1:09:01 PM | P | CANC |
|
|
Overbooked.
|
FIR07-00416
| INSP-Final Inspection | 9/20/2007 | 9/21/2007 | 9/21/2007 1:08:27 PM | P | CANC |
|
|
Overbooked.
|
BLD07-01734
| FIRE-Final Inspection | 9/20/2007 | 9/21/2007 | 9/21/2007 1:07:34 PM | A | PASS |
|
|
Fire life safety inspection passed, the surface bolt lock at the mens restroom removed while on site, noted separate permits have been issued for the adjacent express care project and fire sprinkler system modifications.
|
FIR07-00235
| INSP-Sprinkler Rough-in/Hydro | 9/20/2007 | 9/21/2007 | 9/21/2007 1:04:44 PM | A | FAIL |
|
|
Some items remian to be completed on the rough-in correction notice, overhead hydro is not ready for inspection.
|
FIR07-00236
| INSP-Sprinkler Rough-in/Hydro | 9/20/2007 | 9/21/2007 | 9/21/2007 12:53:41 PM | A | NR |
|
|
System is not pressured for hydrostatic testing.
|
FIR07-00674
| INSP-Final Inspection | 9/18/2007 | 9/21/2007 | 9/20/2007 2:33:06 PM | P | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: Greg Kirkes Inspection cancelled from web by: Greg Kirkes
|