Inspections for the day of: Monday, September 21, 2009.
Number of inspections: 20
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR09-00550 INSP-Final Inspection9/21/20099/21/20099/22/2009 8:09:45 AMPNH
Scheduled by a contractor via Hello! on 9/21/2009 at 7:54:54 AM. Contact: ###-####.
FIR09-00226 INSP-Final Inspection9/15/20099/21/20099/22/2009 8:09:24 AMAFAIL
Smoke alarms must be interconnected per IFC requirements- see fire code review note #29. Notification tested okay.
FIR09-00224 INSP-Final Inspection9/15/20099/21/20099/22/2009 8:02:29 AMAFAIL
Smoke alarms need to be located away from supply or return air diffusers to avoid a delay in operation a min. of 3' per NFPA 72 -see fire code review notes item #3. Notification tested okay.
FIR09-00223 INSP-Final Inspection9/15/20099/21/20099/22/2009 8:02:04 AMAFAIL
Smoke alarms need to be located away from supply or return air diffusers to avoid a delay in operation a min. of 3' per NFPA 72 -see fire code review notes item #3. Notification tested okay.
FIR09-00222 INSP-Final Inspection9/15/20099/21/20099/22/2009 8:01:41 AMAFAIL
Smoke alarms need to be located away from supply or return air diffusers to avoid a delay in operation a min. of 3' per NFPA 72 -see fire code review notes item #3. Notification tested okay.
FIR09-00213 INSP-Final Inspection9/15/20099/21/20099/22/2009 8:00:49 AMAFAIL
Smoke alarms need to be located away from supply or return air diffusers to avoid a delay in operation a min. of 3' per NFPA 72 -see fire code review notes item #3. Notification tested okay.
FIR09-00216 INSP-Final Inspection9/15/20099/21/20099/22/2009 8:00:04 AMAFAIL
Smoke alarms need to be located away from supply or return air diffusers to avoid a delay in operation a min. of 3' per NFPA 72 -see fire code review notes item #3. Notification tested okay.
BLD09-01289 FIRE-Final Inspection9/21/20099/21/20099/22/2009 7:43:45 AMPPART
Fire life safety for the second floor remodel is acceptable, final pending completion of the scope of work for the project attatched fire sprinkler permit which includes heads at a new freezer in the warehouse area not yet installed.
FIR09-00413 INSP-Sprinkler Rough-in9/21/20099/21/20099/22/2009 7:41:32 AMPPART
Overhead rough-in at the board room, file room and reception area as marked on the stamped plan set are good for cover at the sheetrock ceilings. Breakroom partial cover okayed as one branchline is incomplete.
FIR09-00205 INSP-Final Inspection9/15/20099/21/20099/22/2009 7:37:56 AMAPASS
Fire alarm work passed field testing, permit finaled.
FIR09-00221 INSP-Final Inspection9/15/20099/21/20099/22/2009 7:37:23 AMAPASS
Fire alarm work passed field testing, permit finaled.
FIR09-00220 INSP-Final Inspection9/15/20099/21/20099/22/2009 7:37:00 AMAPASS
Fire alarm work passed field testing, permit finaled.
FIR09-00219 INSP-Final Inspection9/15/20099/21/20099/22/2009 7:36:38 AMAPASS
Fire alarm work passed field testing, permit finaled.
FIR09-00218 INSP-Final Inspection9/15/20099/21/20099/22/2009 7:36:12 AMAPASS
Fire alarm work passed field testing, permit finaled.
FIR09-00217 INSP-Final Inspection9/15/20099/21/20099/22/2009 7:35:43 AMAPASS
Fire alarm work passed field testing, permit finaled.
FIR09-00215 INSP-Final Inspection9/15/20099/21/20099/22/2009 7:35:04 AMAPASS
Fire alarm work passed field testing, permit finaled.
FIR09-00214 INSP-Final Inspection9/15/20099/21/20099/22/2009 7:34:36 AMAPASS
Fire alarm work passed field testing, permit finaled.
BLD09-01490 FIRE-Final Inspection9/21/20099/21/20099/21/2009 2:54:29 PMPPASS
Items on correction notice verified for compliance, life safety passed.
BLD09-01405 FIRE-Final Inspection9/18/20099/21/20099/21/2009 11:01:59 AMAFAIL
Correction items noted at the previous inspection are not done, project is not in condition for final at this time.
BLD09-00905 FIRE-Final Inspection9/18/20099/21/20099/21/2009 11:00:26 AMAPASS
Fire life safety inspection passed for both remodeled units.