Inspections for the day of: Tuesday, September 21, 2010.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorDoug A Poedy
TitleELE-INSPECTOR
Phone #447-7209
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE09-01936 Electrical Rough-In9/21/20109/21/20109/21/2010 12:19:35 PMPPASS
Bret Phone #: ###-####. Soffet ok to cover.
ELE10-01746 Final9/20/20109/21/20109/21/2010 11:17:44 AMAPASS
Final for service change Phone #: ###-#### >> Inspection requested via web by Emmet Bushman
ELE10-01746 DOC - Permit Finaled9/21/20109/21/20109/21/2010 11:17:24 AMPPASS
ELE10-02006 Permanent Service9/20/20109/21/20109/21/2010 11:06:49 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Kevin Burke. P/S O/H Connect ok.
ELE10-02082 Final9/20/20109/21/20109/21/2010 10:46:06 AMAPASS
call prior to inspection to gain access. ###-#### Phone #: ###-#### >> Inspection requested via web by BARRY KENDALL
ELE10-02082 DOC - Permit Finaled9/21/20109/21/20109/21/2010 10:45:58 AMPPASS
ELE10-02081 Final9/20/20109/21/20109/21/2010 10:45:50 AMAPASS
call prior to inspection to meet and get access. ###-#### Phone #: ###-#### >> Inspection requested via web by BARRY KENDALL
ELE10-02081 DOC - Permit Finaled9/21/20109/21/20109/21/2010 10:45:35 AMPPASS
ELE10-02051 Rough-In Permanent Service9/20/20109/21/20109/21/2010 10:25:19 AMAFAIL
Should be open, if not, lock box code 1290, any questions, please call Clay. Thank You. Phone #: ###-#### >> Inspection requested via web by Clay Morgan. Left correction notice on-site. NEC 800.133 a2, NEC 300.4 need more nailplates, NEC 200.7 Re-identify nuetral, NEC 250.94 Intersystem bonding bar, Boise city code requires 2 ground rods even with water pipe ground.
ELE10-01838 Electrical Rough-In9/20/20109/21/20109/21/2010 9:12:49 AMAPASS
mike - floor heat inspection Phone #: ###-####
ELE10-01687 Electrical Rough-In9/20/20109/21/20109/21/2010 8:58:10 AMAPART
Ric Phone #: ###-#### >> Inspection requested via web by Dave Friend. Ceiling bld. 5