Inspections for the day of: Wednesday, September 21, 2011.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE11-01653 Electrical Rough-In9/21/20119/21/20119/21/2011 4:03:29 PMPPASS
Kevin Phone #: ###-#### walls and u/g note need to address show window recepts
ELE11-01841 Electrical Rough-In9/21/20119/21/20119/21/2011 4:02:44 PMPPASS
bonding for pool//Jeff Phone #: ###-####
bonding for cover rail ok
ELE11-02160 Final9/21/20119/21/20119/21/2011 4:02:12 PMPPASS
ELE11-01864 Permanent Service9/21/20119/21/20119/21/2011 4:01:59 PMPFAIL
Phone #: ###-#### >> Inspection requested via web by Therrin Robertson still needs too replace buses called
ELE11-02175 Electrical Rough-In9/21/20119/21/20119/21/2011 3:22:02 PMPDONE
PAUL UNDERGROUND Phone #: ###-#### >> Inspection requested via web by Sean DeLacy note no r/i conference on wiring to sign NEC 410.30
ELE11-01770 Permanent Service9/20/20119/21/20119/21/2011 2:37:09 PMPPASS
Jr Phone #: ###-#### p/s o/h rec. ok
ELE11-02148 Conference9/20/20119/21/20119/21/2011 12:46:40 PMADONE
Please call Tracy ###-####, in the am, with approximate time to meet. Thank you Phone #: ###-#### >> Inspection requested via web by Tracy Robertson ok addressed # of services allowed , and changing services from plans, and where romex can and cannot be used, all common areas will be wired to meet BCC4-05-31 (D) no romex
ELE11-02012 Electrical Rough-In9/20/20119/21/20119/21/2011 11:43:29 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Thomas Jenkins ok
ELE11-02160 Permanent Service9/20/20119/21/20119/21/2011 11:43:14 AMAPASS
200amp service upgrade,any questions call Jake @ ###-#### Phone #: ###-#### >> Inspection requested via web by Andy Rose
p/s u/g rec. ok
ELE11-02170 Rough-In Permanent Service9/21/20119/21/20119/21/2011 11:42:45 AMAPASS
Rowdy Monroe Phone #: ###-#### p/s u/g new ok
ELE10-02450 Electrical Rough-In9/20/20119/21/20119/21/2011 10:53:51 AMAPASS
sue - underground Phone #: ###-#### ok uf for well
ELE11-02065 Electrical Rough-In9/20/20119/21/20119/21/2011 10:53:14 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Bryan McLaughlin
ELE11-02170 Final9/20/20119/21/20119/21/2011 10:52:36 AMANR
Phone #: ###-#### >> Inspection requested via web by Rowdy Monroe
ELE11-01392 Final9/20/20119/21/20119/21/2011 10:51:30 AMAFAIL
FRANK Phone #: ###-#### called use only manufactures breakers, complete all trimout, use adadapt rings where required, provide panel schedule, test all recepts for gfci protection where required , adjust deadfront of panel so there is no gap between it and breakers