FIR14-00714
| INSP-Final Inspection | 9/15/2015 | 9/21/2015 | 9/21/2015 3:47:57 PM | P | PART |
|
|
Fire alarm test of all fire sprinkler and hood and duct FP systems interface, SDs, MPs, HVAC DDs, SFDs, notification devices, etc. All tested OK. NOTE: FA interface to egress door hardware (mag. locks) not tested - not ready.
|
FIR14-00683
| INSP-Final Inspection | 9/17/2015 | 9/21/2015 | 9/21/2015 3:45:30 PM | P | PART |
|
|
Final inspection of wet pipe and dry pipe susyems - Not Ready - DP valve currently under 24 hour air test, and a couple of heads need to be replaced (painted) and a few escutcheon rings need to be installed. All FA interface tested OK
|
FIR14-00683
| INSP-Sprinkler Rough-in | 9/17/2015 | 9/21/2015 | 9/21/2015 3:42:58 PM | P | PART |
|
|
Duplicate request - Fire sprinkler system test with fire alarm interface, including water flows, tampers, trip test of dry pipe valve, exterior bell, etc. All tested OK - trip test of DP valve exceeded 60 seconds for water to IT - Contractor stated that system met <500 gpm to not have to provide water to IT within 60 seconds. Contractor agreed to provide supporting documentation that system meets this criteria. DP system put on 24 hour air test at 2:00pm - will retest tomorrow at same time.
|
FIR14-00683
| INSP-Sprinkler Rough-in/Hydro | 9/17/2015 | 9/21/2015 | 9/21/2015 3:41:42 PM | P | PART |
|
|
Fire sprinkler system test with fire alarm interface, including water flows, tampers, trip test of dry pipe valve, exterior bell, etc. All tested OK - trip test of DP valve exceeded 60 seconds for water to IT - Contractor stated that system met <500 gpm to not have to provide water to IT within 60 seconds. Contractor agreed to provide supporting documentation that system meets this criteria. DP system put on 24 hour air test at 2:00pm - will retest tomorrow at same time.
|
FIR14-00069
| INSP-Final Inspection | 9/17/2015 | 9/21/2015 | 9/21/2015 3:37:15 PM | P | PASS |
|
|
Duplicate request - Final inspection of FS U/G supply - PASSED Tamper valve interface with fire alarm system OK
|
FIR14-00069
| INSP-Sprinkler Rough-in | 9/17/2015 | 9/21/2015 | 9/21/2015 3:36:20 PM | P | PASS |
|
|
Duplicate request - Final inspection of FS U/G supply - PASSED Tamper valve interface with fire alarm system OK
|
FIR14-00069
| INSP-Sprinkler Rough-in/Hydro | 9/17/2015 | 9/21/2015 | 9/21/2015 3:35:15 PM | P | PASS |
|
|
Final inspection of FS U/G supply - PASSED Tamper valve interface with fire alarm system OK
|
FIR15-00043
| INSP-Final Inspection | 9/18/2015 | 9/21/2015 | 9/21/2015 3:32:48 PM | P | PART |
|
|
Test of hood and duct FP system, including detection, manual pull, nozzles placement, type, etc. All tested OK - fire alarm interface OK. K-type extinguisher available. Need sign to better identify MP as for hood FP system.
|