Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE15-01348 Final9/21/20169/21/20169/21/2016 2:47:03 PMPFAIL
This is a inspection of level 2 only today. Please keep this permit active for remainder of floors. Contact Brandon Robinson for walk through. Phone #: ###-#### Inspection requested via web by Tom Betty
All lighting for TI portion complete on 2nd floor only. Core and shell lighting not complete in stairways of 2nd floor. Bathrooms and corridors complete.
ELE16-01838 Final9/20/20169/21/20169/21/2016 1:36:55 PMAFAIL
Level 2 Stack 1,2,3,4 Branch Circuit Panels , Branch Circuit Equip conn., Branch Circuit Devices , Office Furniture Phone #: ###-#### Inspection requested via web by Tom Betty
110.3- In complete installation of office furniture all connections shall be complete. Some not connected to wiring supplied, some fed by panel 22C circuits 2, 4, 6 not working. All covers on furniture shall be installed and be securely fastened.
300.15- All boxes installed for cables, card readers, data, misc, all shall have covers installed. All covers for lighting control control panels shall be installed for TCO.
392.60- Cable trays and ladder racks in server rooms shall be completely bonded.
605.5- Complete office furniture connections.
800.110(C)(1)- All data cables shall be supported with in 3' of termination and not more than 10' between supports. Eccess loops elevator lobby, blinds, ect.
ELE15-01348 Final9/20/20169/21/20169/21/2016 1:25:25 PMAFAIL
Level 2 Stack 1,2,3,4 Electrical Rooms Phone #: ###-#### Inspection requested via web by Tom Betty
300.21- Complete fire caulking of penetrations in electrical room walls. Non-electrical found, sprinkler pipe, communication cables and conduits.
ELE16-00089 Conference9/20/20169/21/20169/21/2016 10:49:34 AMADONE
Call Rafael to sign TCO sheets in ESI office. Phone #: ###-#### Inspection requested via web by Rafael Castillo
Signed all TCO sheets for TI portion.
ELE15-00495 Electrical Rough-In9/20/20169/21/20169/21/2016 10:48:40 AMAPASS
TCO, check heat trace, and door on 2nd floor electric room. Phone #: ###-#### Inspection requested via web by Toby Groves
All heat trace terminated in boxes, 2nd floor electrical room door mounted with proper hardware. Signed TCO sheets
ELE16-02557 Electrical Rough-In9/20/20169/21/20169/21/2016 10:06:47 AMAPASS
Randy. Final on 2nd ; 4th floor restrooms. Phone #: ###-#### Inspection requested via web by Sean DeLacy
Baths on 2nd and 4th floor complete. Corridors on these floors not complete
ELE16-01923 Final9/20/20169/21/20169/21/2016 9:14:43 AMAPASS
Phone #: ###-#### Inspection requested via web by Terry Scott
Final ok
ELE16-03060 Rough-In Permanent Service9/20/20169/21/20169/21/2016 8:55:42 AMAPASS
whole house wiring please call if you have any questions Thank you Shaun ###-#### Phone #: ###-#### Inspection requested via web by Shaun Kirkman
Rough in ok cover p/s u/g n ok