Inspections for the day of: Wednesday, September 21, 2016.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorEric Story
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE16-00877 Final9/21/20169/21/20169/21/2016 2:27:13 PMPCANC
Call for access // Dennis Phone #: ###-####
no access called and left message will need it called back in
ELE16-01483 Electrical Rough-In9/20/20169/21/20169/21/2016 1:53:46 PMPPASS
We need a partial ceiling inspection for the North Half, 1st, 2nd, ; 3rd floor. Site contact is Kenny, ###-#### Phone #: ###-#### Inspection requested via web by Stacie Tasker
1st 2nd 3rd floor north side corridor hard lids only ok cover
ELE16-03059 Permanent Service9/20/20169/21/20169/21/2016 1:02:26 PMAPASS
Inspection for service only. We finished service for homeowner. Please call if you have any questions Thank you Shaun ###-#### Phone #: ###-#### Inspection requested via web by Shaun Kirkman
p/s u/g n ok
ELE16-02047 Electrical Rough-In9/21/20169/21/20169/21/2016 1:02:02 PMPPASS
Ren Phone #: ###-####
rough-in only ok cover/will need to final permit #ele16-03059 as well on final for service only
ELE16-02730 Electrical Rough-In9/20/20169/21/20169/21/2016 12:15:50 PMPPASS
Early pm if possible please. Phone #: ###-#### Inspection requested via web by Kerri Hamilton
primary feeds underground only ok cover
ELE16-03058 Final9/20/20169/21/20169/21/2016 11:15:02 AMAFAIL
Call the owner before you go, he said he would be asleep. His name is Chris and the number is above. Phone #: ###-#### Inspection requested via web by George Pascua
352.12(c) sch 40 pvc is not rated for physical damage
ELE16-02480 Electrical Rough-In9/20/20169/21/20169/21/2016 10:44:08 AMAPASS
Phone #: ###-#### Inspection requested via web by jason williams
Column bonding and conduits existing columns on east 3 columns
ELE16-03048 Permanent Service9/20/20169/21/20169/21/2016 10:20:56 AMACANC
With concerns or questions please call ###-#### Phone #: ###-#### Inspection requested via web by Eric Schroeder
Was not ready at this time
ELE16-02161 Final9/20/20169/21/20169/21/2016 9:59:36 AMAFAIL
Lockbox 4750 Phone #: ###-#### Inspection requested via web by Clay Morgan
110.26 working space clearences required for electrical equipment
110.25 Lockout required for hard wired appliances
210.8 GFCI protection required for exterior outlets and will be WR type and in-use type
ELE16-02159 Final9/20/20169/21/20169/21/2016 9:57:01 AMAPASS
Lockbox 4750 Phone #: ###-#### Inspection requested via web by Clay Morgan
final ok
ELE16-01823 Final9/20/20169/21/20169/21/2016 9:56:33 AMAFAIL
Lockbox 4750 Phone #: ###-#### Inspection requested via web by Clay Morgan
210.8 GFCI shall be readily accessible
110.25 lockout for hood
ELE16-02160 Final9/20/20169/21/20169/21/2016 9:55:41 AMAFAIL
Lockbox 4750 Phone #: ###-#### Inspection requested via web by Clay Morgan
Back GFCI in-op
110.25 lock out required for hard wired appliances
110.7 Remove abandoned SER cable in back closet
ELE16-02979 Electrical Rough-In9/20/20169/21/20169/21/2016 8:50:14 AMAPASS
Lewis-underground for spa Phone #: ###-####
underground for spa ok cover
ELE16-02899 Rough-In Permanent Service9/20/20169/21/20169/21/2016 8:23:49 AMAPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn
rough-in ok cover p/s u/g n ok