Inspections for the day of: Wednesday, September 21, 2016.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorChad Schwendiman
TitleMEC-INSPECTOR
Phone #780-9549
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC15-02759 Final9/21/20169/21/20169/21/2016 4:28:45 PMPPART
Partial Final inspection for 1st Floor and 2nd Floor Prefunction/Lobby Areas, please contact Jim Brown. Phone #: ###-#### Inspection requested via web by Melissa Kaae - temporary occupancy okay for the 1st and 2nd floor lobby
MEC16-03376 Rough-in9/21/20169/21/20169/21/2016 3:32:17 PMPFAIL
The venting for the boilers installed in the VRT space in the basement exceeds the manufactures total lenth allowed, the manufacture also calls out for the vent to slope up at a 1/4" per foot from the boilers to the termination location
MEC16-01020 Mec-Aging Inspection9/21/20169/21/20169/21/2016 3:01:27 PM CANC
MEC16-01023 Mec-Aging Inspection9/21/20169/21/20169/21/2016 3:01:21 PM PASS
MEC16-01023 DOC - Permit Finaled9/21/20169/21/20169/21/2016 3:01:14 PMPPASS
MEC16-02497 Final9/21/20169/21/20169/21/2016 10:11:35 AMPPASS
MEC16-01213 Conference9/21/20169/21/20169/21/2016 10:03:22 AMAPART
2nd Floor Lobby-temp occupancy. Phone #: ###-#### Inspection requested via web by Crystal Grant - Temporary occupancy okay for the 2nd floor lobby
MEC16-01892 Final9/21/20169/21/20169/21/2016 10:02:37 AMPPASS
Final Inspection Phone #: ###-#### Inspection requested via web by Crystal Grant