ELE17-03079
| Electrical Rough-In | 9/21/2017 | 9/21/2017 | 9/21/2017 2:37:42 PM | P | PASS |
|
|
Call when on the way // Jose Phone #: ###-#### Conference room required receptacle outlets will be placed in floor due to movable partitians. Grid rough in ok cover
|
ELE17-03153
| Electrical Rough-In | 9/21/2017 | 9/21/2017 | 9/21/2017 1:59:34 PM | P | PASS |
|
|
Please give me half an hour notice to insure access. Than you Shaun ###-#### Phone #: ###-#### Inspection requested via web by Shaun Kirkman Repair due to water damage bathroom rough in ok cover
|
ELE17-02187
| Final | 9/21/2017 | 9/21/2017 | 9/21/2017 1:13:35 PM | P | PASS |
|
|
Kurt Phone #: ###-#### Final ok
|
ELE17-03142
| Electrical Rough-In | 9/20/2017 | 9/21/2017 | 9/21/2017 11:11:23 AM | A | PASS |
|
|
Keys are under front doormat for access Phone #: ###-#### Inspection requested via web by Zane Robertson Plumbing not started at time of inspection. Master bed and bath and kitchen rough in ok cover
|
ELE17-03055
| Rough-In Permanent Service | 9/20/2017 | 9/21/2017 | 9/21/2017 10:41:39 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn Rough in ok cover p/s u/g n ok
|
ELE17-03148
| Electrical Rough-In | 9/20/2017 | 9/21/2017 | 9/21/2017 10:07:52 AM | A | PASS |
|
|
Job is complete. Final please Phone #: ###-#### Inspection requested via web by Stuart Welton Rough in ok
|
ELE17-03148
| Final | 9/21/2017 | 9/21/2017 | 9/21/2017 10:07:41 AM | P | PASS |
|
|
Job is complete. Final please Phone #: ###-#### Inspection requested via web by Stuart Welton Final ok
|
ELE17-03140
| Electrical Rough-In | 9/20/2017 | 9/21/2017 | 9/21/2017 9:46:23 AM | A | PASS |
|
|
Terry Cushing is the contact on site ###-#### Phone #: ###-#### Inspection requested via web by Debby Pierce Future work to be permited when building permit is pulled. Floor receptacles only rough in ok cover
|
ELE17-03150
| Conference | 9/21/2017 | 9/21/2017 | 9/21/2017 9:25:36 AM | P | DONE |
|
|
Please contact Tate Borstelman @ ###-####
Have a lovely day and THANK YOU!!! Phone #: ###-#### Inspection requested via web by JENNY EMEL Discussed equipment grounding of new watt meter being installed for new solar array system. Single bonding point for grounded conductor shall remain in place, at watt meter location grounded conductor shall splice thru meter with grounding conductor to terminate at lugs and bond meter can. Grounded conductor shall not be connected to noncurrent carryiing metal parts on load side of service. If connection to grounded conductor needed for watt meter a tap shall be supplied off isolated connection of grounded conductor.
|