ELE18-03607
| Electrical Rough-In | 9/21/2018 | 9/21/2018 | 9/21/2018 3:04:22 PM | P | PASS |
|
|
Can you come toward the end of your rounds so I can finish making up some boxes thanks Phone #: ###-#### Inspection requested via web by Ron Zimmerman Covered awning ceiling rough in ok cover
|
ELE17-03734
| Conference | 9/21/2018 | 9/21/2018 | 9/21/2018 2:53:03 PM | P | PASS |
|
|
Spoke with general foreman on site. All work performed after 9-14-18 must be done and permitted by a licenced contractor due to original contractor no longer in business.
|
ELE17-02862
| Permanent Service | 9/21/2018 | 9/21/2018 | 9/21/2018 2:23:16 PM | P | PASS |
|
|
Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty 86,448 AIC value provided on print. p/s u/g n ok
|
ELE18-03320
| Electrical Rough-In | 9/21/2018 | 9/21/2018 | 9/21/2018 1:43:17 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Level 4 interior walls rough in ok cover
|
ELE18-03048
| Final | 9/20/2018 | 9/21/2018 | 9/21/2018 12:24:25 PM | A | FAIL |
|
|
Please use side gate for entry if no one is home Phone #: ###-#### Inspection requested via web by Robert Carter 210.8(A)(2)- All receptacles located in hobby room shall have GFCI protection. Refer/ freezer. 406.9(A)- All receptacles installed outdoors in damp or wet locations shall be weather resistant type. 406.12- All receptacles installed in addition to residential garage shall be tamper resistant type.
|
ELE18-03320
| Electrical Rough-In | 9/20/2018 | 9/21/2018 | 9/21/2018 11:06:38 AM | P | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Kerri Hamilton Inspection cancelled from web by: Kerri Hamilton
|
ELE18-03277
| Final | 9/20/2018 | 9/21/2018 | 9/21/2018 10:53:54 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by BRS Permitting Final ok
|
ELE18-03202
| Electrical Rough-In | 9/20/2018 | 9/21/2018 | 9/21/2018 10:22:52 AM | A | PASS |
|
|
Request for cover Phone #: ###-#### Inspection requested via web by Tyler Ridley Check notes on ELE18-03086. Underground in slab Phone #: ###-#### Inspection requested via web by Kotton Corder Spoke with electrical contractor and owner as per NEC 511.3 to declassify minor repair garage and office areas minimum ventilation 4 or more air exchanges per hour with supply and outlet with in 12" of floor shall be provided by final so no electrical issues remain. Stamped Documentation must be provided. Under slab rough in for garage area rough in ok cover. New contractor taking over job. Office walls only rough in ok cover
|
ELE18-03562
| Final | 9/20/2018 | 9/21/2018 | 9/21/2018 9:48:16 AM | A | NH |
|
|
Please call Brodie at ###-#### with any questions. Phone #: ###-#### Inspection requested via web by William Salts No answer at door, left notice to call and reschedule
|
ELE18-01608
| Electrical Rough-In | 9/20/2018 | 9/21/2018 | 9/21/2018 9:29:33 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Jeremy Cloud Underground E.O. Wilson common area rough in ok cover
|
ELE18-02584
| Final | 9/20/2018 | 9/21/2018 | 9/20/2018 3:40:46 PM | A | PART |
|
|
Contact Jon Novak Thank you, Phone #: ###-#### Inspection requested via web by Tom Betty Phase 1 TCO. No card posted. Temp final ok
|