Inspections for the day of: Friday, September 21, 2018.
Number of inspections: 21
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBen Livingston
TitleMEC-COM/RES INSPECTOR
Phone #576-1208
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC18-04603 Final9/21/20189/21/20189/21/2018 3:40:24 PMPPASS
After 2 please. Call 8709150 Inspection requested via web by william kerwin
MEC18-04390 Final9/20/20189/21/20189/21/2018 3:07:40 PMPPASS
Inspection requested via web by Andrea Grigsby
MEC18-03982 Final9/21/20189/21/20189/21/2018 2:39:42 PMPPASS
Please call Bryan, Thank YOU! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
MEC18-04221 Final9/19/20189/21/20189/21/2018 2:13:02 PMPPASS
field super; Chad Robertson Phone #: ###-#### Inspection requested via web by Lisa Whitney
MEC18-03909 Final9/19/20189/21/20189/21/2018 1:51:08 PMPFAIL
if possible can you please call when you are on the way Phone #: ###-#### Inspection requested via web by Marisa Hone
need to witness flue pressure test on 2nd furnace, also need to access AC on roof
MEC18-04570 Pressure Test9/21/20189/21/20189/21/2018 1:10:02 PMPPASS
Phone #: ###-#### Inspection requested via web by PATTY KIRK
20lb
MEC18-04570 Final9/21/20189/21/20189/21/2018 1:09:46 PMPPASS
Phone #: ###-#### Inspection requested via web by PATTY KIRK
MEC18-04575 Final9/21/20189/21/20189/21/2018 12:58:22 PMPFAIL
Phone #: ###-#### Inspection requested via web by Mary LaFayette
max fuse for condencer is 25amp, 50amp is installed
MEC18-01596 Final9/19/20189/21/20189/21/2018 11:38:44 AMAPASS
please call Shawn for access Phone #: ###-#### Inspection requested via web by Nicholas Paige
MEC18-01658 Pressure Test9/20/20189/21/20189/21/2018 11:37:52 AMAPASS
Pressure test gas main through 4th floor, if questions call Donny @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
60lb gas main to 4th floor
MEC18-01658 Pressure Test9/21/20189/21/20189/21/2018 11:37:10 AMPPASS
Pressure test ll1 fintubes 100lb test
MEC18-04543 Final9/19/20189/21/20189/21/2018 11:12:14 AMAPASS
Please call customer, Nancy, prior to arrival ###-#### Phone #: ###-#### Inspection requested via web by Andrea Grigsby
5lb flue
MEC18-03505 Final9/20/20189/21/20189/21/2018 10:32:21 AMAFAIL
open jobsite but our job portion is 100% completed for our scope of work. You dont need to call anyone and you can access anytime, setting for AM request. If you have any questions, please call me at Diamond Office number listed above, my name is Steve Dale Phone #: ###-#### Inspection requested via web by Rick Montgomery
3/8" flex tubing not approved material, condensate needs to be run down to the ground to an approved location,
condensate cannot be run to a walkway,
armaflex needs UV protection, line sets need more supports
MEC18-04316 Final9/14/20189/21/20189/21/2018 10:14:23 AMAFAIL
Please call the Owner, Courtney at ###-#### with a 30 minute heads up arrival time. Phone #: ###-#### Inspection requested via web by David or K Cole
need to finish armaflex condensate piping to close to flue
MEC18-04561 Rough-in9/20/20189/21/20189/21/2018 9:50:40 AMAPASS
Phone #: ###-#### Inspection requested via web by Gary Duncan
MEC18-04561 Final9/21/20189/21/20189/21/2018 9:50:28 AMPPASS
Phone #: ###-#### Inspection requested via web by Gary Duncan
MEC18-04558 Rough-in9/20/20189/21/20189/21/2018 9:33:24 AMAPASS
Phone #: ###-#### Inspection requested via web by Ashley Stegemann
MEC18-04570 Pressure Test9/20/20189/21/20189/21/2018 9:17:14 AMAFAIL
gas pressure test Phone #: ###-#### Inspection requested via web by PATTY KIRK
gauge is stuck at 18lbs, didnt zero out
MEC18-03271 Final9/20/20189/21/20189/21/2018 8:26:59 AMAPASS
JOB SUPER: JOEY AT ###-#### Phone #: ###-#### Inspection requested via web by Mike Almanza
MEC17-05666 Mec-Aging Inspection9/21/20189/21/20189/21/2018 8:00:20 AM CANC
MEC17-05666 DOC - Permit Expired9/21/20189/21/20189/21/2018 8:00:11 AMPPASS