ELE05-02806
| Electrical Rough-In | 9/22/2005 | 9/22/2005 | 9/22/2005 4:22:37 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Ryan Christensen ok to cover walls only in repair area
|
ELE05-02353
| Final | 9/22/2005 | 9/22/2005 | 9/22/2005 3:03:17 PM | P | PART |
|
|
ron; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa check backsplashes for recpts,labels in panels, trim, rest ok, need to sign occ card
|
ELE05-03468
| Temporary Service | 9/22/2005 | 9/22/2005 | 9/22/2005 1:47:34 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Clyde Logan called contr to drive in gnd rod and add abrasion prot for gec. told to use job id sticker. t/s u/g n ok
|
ELE05-01293
| Electrical Rough-In | 9/22/2005 | 9/22/2005 | 9/22/2005 12:33:12 PM | P | PART |
|
|
ANY QUESTIONS PLEASE CALL ED SCHALLOCK; Phone #: ###-#### Internet Inspection Request from: Jeff Radford ok to cover 4 balcony areas in each corner of 2nd floor
|
ELE05-02893
| Rough-In Permanent Service | 9/22/2005 | 9/22/2005 | 9/22/2005 12:14:00 PM | P | CANC |
|
|
Scheduled by a contractor via Hello! on 9/22/2005 at 10:54:20 AM. Contact: ###-####. see p/s
|
ELE05-03447
| Final | 9/21/2005 | 9/22/2005 | 9/22/2005 10:34:53 AM | A | PASS |
|
|
john ###-#### told contr to blank off 2 recpts, rest ok. ok to final
|
ELE05-03298
| Rough-In Permanent Service | 9/20/2005 | 9/22/2005 | 9/22/2005 10:31:55 AM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 9/20/2005 at 4:20:06 PM. Contact: ###-####. called contr, left corr notice, left message,312.5 conductors entering enclosures shall have abrasion protection, 408.38 panel shall be dead front, 300.4(D) 1 1/4" shall be maintained from edge of framing members
|
ELE05-03411
| Electrical Rough-In | 9/21/2005 | 9/22/2005 | 9/22/2005 9:49:21 AM | A | PASS |
|
|
###-#### jay ok to cover walls only
|
ELE05-03446
| Electrical Rough-In | 9/21/2005 | 9/22/2005 | 9/22/2005 9:04:12 AM | A | FAIL |
|
|
###-#### - doug called left message, left corr notice,330.30(B) mc cable shall be strapped within 12" of boxes, and at 6' intervals, 110.12(A) unused openings shall be closed
|
ELE05-02728
| Electrical Rough-In | 9/21/2005 | 9/22/2005 | 9/22/2005 8:25:35 AM | A | PART |
|
|
ceiling inspection front half Sam is on site ; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH ceiling cover sales area only ok
|
ELE05-03466
| Final | 9/21/2005 | 9/22/2005 | 9/22/2005 8:24:12 AM | A | PASS |
|
|
Please call Gene Wright with status.; Phone #: ###-#### Internet Inspection Request from: Gary Coonse ok to final
|
ELE05-02893
| Permanent Service | 9/22/2005 | 9/22/2005 | 9/22/2005 12:00:00 AM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 9/22/2005 at 10:54:20 AM. Contact: ###-####. p/s exst meter pak, n ok
|