FIR05-00089
| INSP-Sprinkler Rough-in/Hydro | 9/22/2005 | 9/22/2005 | 9/22/2005 3:30:04 PM | P | CANC |
|
|
Wrong permit called in, this inspection was for tenant P.F. Chang's FIR05-00378, not the core and shell.
|
FIR05-00301
| INSP-Final Inspection | 9/22/2005 | 9/22/2005 | 9/22/2005 3:27:03 PM | P | FAIL |
|
|
Power to one electrical box below hood failed to shut down upon system activation, per contractor, the wiring to this box is to be removed. Need verification of removal for final.
|
FIR05-00442
| INSP-Final Inspection | 9/22/2005 | 9/22/2005 | 9/22/2005 2:37:45 PM | P | PART |
|
|
Overhead fire sprinkler rough-in is good for cover, some areas in the two south apartments already covered, heads in the washer/dryer closets need correct temperature rating.
|
BLD05-01993
| FIRE-Final Inspection | 9/21/2005 | 9/22/2005 | 9/22/2005 11:06:20 AM | A | PART |
|
|
Fire life safety passed inspection, final pending approval of sprinkler modifications on resubmittals. A temporary occupancy was approved with Sam Rogers permission pending sprinkler sign off.
|
BLD05-02207
| FIRE-Final Inspection | 9/21/2005 | 9/22/2005 | 9/22/2005 10:08:15 AM | A | FAIL |
|
|
Provide address and suite numbers, remove manual thumbturns on main entry/exit doors and provide ADA hardware, provide inspection certification tag for fire extinguisher.
|
FIR05-00510
| INSP-Final Inspection | 9/21/2005 | 9/22/2005 | 9/22/2005 9:40:51 AM | A | PASS |
|
|
Fire alarm passed inspection, permit finaled.
|
BLD05-01314
| FIRE-Final Inspection | 9/22/2005 | 9/22/2005 | 9/22/2005 12:00:00 AM | A | FAIL |
|
|
Remove keyed locking hardware at the intermediate door in pharmacy, fire sprinkler is overspaced due to the new wall - a fire sprinkler permit will be required for any modifications.
|
FIR05-00521
| INSP-Final Inspection | 9/22/2005 | 9/22/2005 | 9/22/2005 12:00:00 AM | A | PART |
|
|
Modifications have been completed, approval pending resubmittals.
|
FIR05-00287
| INSP-Final Inspection | 9/22/2005 | 9/22/2005 | 9/22/2005 12:00:00 AM | P | PASS |
|
|
Fire sprinkler permit finaled.
|
FIR05-00378
| INSP-Sprinkler Rough-in | 9/22/2005 | 9/22/2005 | 9/22/2005 12:00:00 AM | P | PART |
|
|
Overhead rough-in is okay for cover in the grid ceiling areas, will verify proper spacing and head temp. ratings at heat sources in the kitchen after all drops have been cut in. One branch line is directly over an electrical panel, this will need to be relocated per electrical code.
|