ELE06-02990
| Final | 9/22/2006 | 9/22/2006 | 9/22/2006 4:27:04 PM | P | PASS |
|
|
Final inspection call Bob Johnston ###-####; Phone #: ###-#### Internet Inspection Request from: Kristopher wilson ok to final, asked contr to advise when done with strobes and fa in ceiling
|
ELE06-03486
| Permanent Service | 9/22/2006 | 9/22/2006 | 9/22/2006 4:07:41 PM | P | CANC |
|
|
bo; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley wrong type inspection request, see final
|
ELE06-03486
| Final | 9/22/2006 | 9/22/2006 | 9/22/2006 4:06:57 PM | P | PASS |
|
|
bo; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok to final, elect shall move and provide fusible disconnect instead of non-fusible disconnect.
|
ELE06-02613
| Final | 9/21/2006 | 9/22/2006 | 9/22/2006 4:03:56 PM | P | PART |
|
|
any questions please call James Lingelbaugh; Phone #: ###-#### Internet Inspection Request from: Jeff Radford part final ok, signed t/o card, left corr notice, nec 210.62 at least 1 recptacle shall be installed directly above a show window for each 12 linear feet or fraction thereof , 408.4 circuit directory shall be provided and specific as to its purpose, NOTE: corrections shall be made within 2 weeks or further action will be taken, such as removing power., wrote correction to builder/owner: nec 725.2 installed cl2,3,pltc cables not terminated at equipment and not identified for future use with a tag shall be removed per 725.3(B), Note,, correction shall be made within 2 weeks or further action will be taken, such as removing power
|
ELE06-02254
| Rough-In Permanent Service | 9/21/2006 | 9/22/2006 | 9/22/2006 3:54:35 PM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 9/21/2006 at 2:49:53 PM. Contact: ###-####. ok to pour concrete encased electrode
|
ELE06-02821
| Final | 9/22/2006 | 9/22/2006 | 9/22/2006 3:11:24 PM | P | PASS |
|
|
tim; Phone #: ###-#### Internet Inspection Request from: Barbara Stitt ok to final, left survey, nec 210.52(C)(1) kitchen counter outlets shall be spaced such that no point is more than 2' from an outlet, 406.4(D) recpts faces shall be flush with faceplate, called contr
|
ELE06-03531
| Electrical Rough-In | 9/22/2006 | 9/22/2006 | 9/22/2006 3:04:46 PM | P | PASS |
|
|
lloyd; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called contr about nail plates, walls only ok to cover
|
ELE06-02503
| Final | 9/21/2006 | 9/22/2006 | 9/22/2006 2:58:57 PM | P | PASS |
|
|
trent; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok to final
|
ELE06-01297
| Final | 9/21/2006 | 9/22/2006 | 9/22/2006 10:32:04 AM | A | PASS |
|
|
These are the Johnstone Supply letters on the wall and the Monument sign in the grass. However both signs are non-illuminated so i don't know why we pulled an electrical permit. oh well, happy friday.; Phone #: ###-#### Internet Inspection Request from: Eric Shaner ok to final
|
ELE06-03554
| Electrical Rough-In | 9/21/2006 | 9/22/2006 | 9/22/2006 9:55:03 AM | A | PART |
|
|
stu - early morning if possible; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley east wall only ok to cover
|
ELE06-02968
| Final | 9/21/2006 | 9/22/2006 | 9/22/2006 9:44:18 AM | A | PASS |
|
|
brad; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok to final
|
ELE06-03531
| Electrical Rough-In | 9/21/2006 | 9/22/2006 | 9/22/2006 9:24:56 AM | A | NH |
|
|
lloyd; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley called, left card
|
ELE06-01538
| Final | 9/21/2006 | 9/22/2006 | 9/22/2006 9:13:57 AM | A | PASS |
|
|
gene - call for access; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok to final
|
ELE06-02990
| Final | 9/21/2006 | 9/22/2006 | 9/22/2006 9:11:13 AM | A | PART |
|
|
Final inspection call Bob Johnston ###-####; Phone #: ###-#### Internet Inspection Request from: Kristopher wilson met elect, told to be sure lv finished , strap some whips, west side offices ok only, front entry to see again
|
ELE06-03532
| Electrical Rough-In | 9/21/2006 | 9/22/2006 | 9/22/2006 8:23:37 AM | A | FAIL |
|
|
oga; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called left corr notice, nec 314.20 boxes shall be flush with finished surface of combustible material, 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing members, 250.86 metal boxes shall be grounded, 314.16 boxes shall be sufficient size to provide free space for all enclosed conductors, BCC all make-up shall be done
|
ELE06-03532
| Permanent Service | 9/22/2006 | 9/22/2006 | 9/22/2006 8:14:53 AM | A | PASS |
|
|
oga; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles p/s u/g n ok
|
ELE06-03554
| Electrical Rough-In | 9/21/2006 | 9/22/2006 | 9/22/2006 12:00:00 AM | P | CANC |
|
|
nr per stu - late afternoon if possible; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley
|