Inspections for the day of: Friday, September 22, 2006.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-02990 Final9/22/20069/22/20069/22/2006 4:27:04 PMPPASS
Final inspection call Bob Johnston ###-####; Phone #: ###-#### Internet Inspection Request from: Kristopher wilson ok to final, asked contr to advise when done with strobes and fa in ceiling
ELE06-03486 Permanent Service9/22/20069/22/20069/22/2006 4:07:41 PMPCANC
bo; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley wrong type inspection request, see final
ELE06-03486 Final9/22/20069/22/20069/22/2006 4:06:57 PMPPASS
bo; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok to final, elect shall move and provide fusible disconnect instead of non-fusible disconnect.
ELE06-02613 Final9/21/20069/22/20069/22/2006 4:03:56 PMPPART
any questions please call James Lingelbaugh; Phone #: ###-#### Internet Inspection Request from: Jeff Radford part final ok, signed t/o card, left corr notice, nec 210.62 at least 1 recptacle shall be installed directly above a show window for each 12 linear feet or fraction thereof , 408.4 circuit directory shall be provided and specific as to its purpose, NOTE: corrections shall be made within 2 weeks or further action will be taken, such as removing power., wrote correction to builder/owner: nec 725.2 installed cl2,3,pltc cables not terminated at equipment and not identified for future use with a tag shall be removed per 725.3(B), Note,, correction shall be made within 2 weeks or further action will be taken, such as removing power
ELE06-02254 Rough-In Permanent Service9/21/20069/22/20069/22/2006 3:54:35 PMAPASS
Scheduled by a contractor via Hello! on 9/21/2006 at 2:49:53 PM. Contact: ###-####. ok to pour concrete encased electrode
ELE06-02821 Final9/22/20069/22/20069/22/2006 3:11:24 PMPPASS
tim; Phone #: ###-#### Internet Inspection Request from: Barbara Stitt ok to final, left survey, nec 210.52(C)(1) kitchen counter outlets shall be spaced such that no point is more than 2' from an outlet, 406.4(D) recpts faces shall be flush with faceplate, called contr
ELE06-03531 Electrical Rough-In9/22/20069/22/20069/22/2006 3:04:46 PMPPASS
lloyd; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called contr about nail plates, walls only ok to cover
ELE06-02503 Final9/21/20069/22/20069/22/2006 2:58:57 PMPPASS
trent; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok to final
ELE06-01297 Final9/21/20069/22/20069/22/2006 10:32:04 AMAPASS
These are the Johnstone Supply letters on the wall and the Monument sign in the grass. However both signs are non-illuminated so i don't know why we pulled an electrical permit. oh well, happy friday.; Phone #: ###-#### Internet Inspection Request from: Eric Shaner ok to final
ELE06-03554 Electrical Rough-In9/21/20069/22/20069/22/2006 9:55:03 AMAPART
stu - early morning if possible; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley east wall only ok to cover
ELE06-02968 Final9/21/20069/22/20069/22/2006 9:44:18 AMAPASS
brad; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok to final
ELE06-03531 Electrical Rough-In9/21/20069/22/20069/22/2006 9:24:56 AMANH
lloyd; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley called, left card
ELE06-01538 Final9/21/20069/22/20069/22/2006 9:13:57 AMAPASS
gene - call for access; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok to final
ELE06-02990 Final9/21/20069/22/20069/22/2006 9:11:13 AMAPART
Final inspection call Bob Johnston ###-####; Phone #: ###-#### Internet Inspection Request from: Kristopher wilson met elect, told to be sure lv finished , strap some whips, west side offices ok only, front entry to see again
ELE06-03532 Electrical Rough-In9/21/20069/22/20069/22/2006 8:23:37 AMAFAIL
oga; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called left corr notice, nec 314.20 boxes shall be flush with finished surface of combustible material, 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing members, 250.86 metal boxes shall be grounded, 314.16 boxes shall be sufficient size to provide free space for all enclosed conductors, BCC all make-up shall be done
ELE06-03532 Permanent Service9/22/20069/22/20069/22/2006 8:14:53 AMAPASS
oga; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles p/s u/g n ok
ELE06-03554 Electrical Rough-In9/21/20069/22/20069/22/2006 12:00:00 AMPCANC
nr per stu - late afternoon if possible; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley