Inspections for the day of: Friday, September 22, 2006.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MIS06-00249 FIR-Final9/22/20069/22/20069/25/2006 2:28:27 PMPPASS
c/n items have been completed, inspection passed.
BLD06-01589 FIRE-Final Inspection9/21/20069/22/20069/22/2006 8:28:07 PMPNR
Project related alarm permit must be finaled prior to BLD life safety final.
FIR06-00598 INSP-Final Inspection9/21/20069/22/20069/22/2006 12:23:46 PMAPART
OH rough-in at the drop ceilings is approved for cover.
FIR06-00461 INSP-Sprinkler Rough-in/Hydro9/22/20069/22/20069/22/2006 12:13:07 PMAFAIL
Two heads at the back exit near the riser exceed min. spacing, missing orfice at the inspectors test connection, the electrical/telephone closet will require walls extended to the deck for upright protection or provide a drop ceiling and pendent head. The remainder of drop ceiling areas are good for cover.
MIS06-00249 FIR-Final9/21/20069/22/20069/22/2006 12:06:31 PMAFAIL
Need to provide signage above the main entry/exit door, provide emergency lighting for the path of egress, install panic hardware at the second exit as indicated on review notes.