MIS06-00249
| FIR-Final | 9/22/2006 | 9/22/2006 | 9/25/2006 2:28:27 PM | P | PASS |
|
|
c/n items have been completed, inspection passed.
|
BLD06-01589
| FIRE-Final Inspection | 9/21/2006 | 9/22/2006 | 9/22/2006 8:28:07 PM | P | NR |
|
|
Project related alarm permit must be finaled prior to BLD life safety final.
|
FIR06-00598
| INSP-Final Inspection | 9/21/2006 | 9/22/2006 | 9/22/2006 12:23:46 PM | A | PART |
|
|
OH rough-in at the drop ceilings is approved for cover.
|
FIR06-00461
| INSP-Sprinkler Rough-in/Hydro | 9/22/2006 | 9/22/2006 | 9/22/2006 12:13:07 PM | A | FAIL |
|
|
Two heads at the back exit near the riser exceed min. spacing, missing orfice at the inspectors test connection, the electrical/telephone closet will require walls extended to the deck for upright protection or provide a drop ceiling and pendent head. The remainder of drop ceiling areas are good for cover.
|
MIS06-00249
| FIR-Final | 9/21/2006 | 9/22/2006 | 9/22/2006 12:06:31 PM | A | FAIL |
|
|
Need to provide signage above the main entry/exit door, provide emergency lighting for the path of egress, install panic hardware at the second exit as indicated on review notes.
|