FIR08-00551
| INSP-Sprinkler Rough-in/Hydro | 9/22/2008 | 9/22/2008 | 9/22/2008 6:24:52 PM | P | FAIL |
|
|
Dry system rough-in failed, items include two missing upright heads and piping not installed, 5 BB attic heads to be replaced due to field modified deflector orientation, overspaced coverage at one location above the riser room, noted remote inspectors test connection has been moved from where indicated on approved plan, also noted possible coverage issue at hatched areas due to change in roof pitch at zone of coverage for the BB heads. Also discovered two leaks to be repaired and bushings at some fittings.
|
FIR08-00551
| INSP-Sprinkler Rough-in/Hydro | 9/22/2008 | 9/22/2008 | 9/22/2008 6:20:50 PM | A | PART |
|
|
Overhead dry system and wet system hydrostatic testing passed. KR
|
FIR08-00426
| FIR-Aging Inspection | 9/22/2008 | 9/22/2008 | 9/22/2008 5:54:58 PM | | DONE |
|
|
Work in progress, site inspection schedule pending this week per contractor.
|
FIR08-00516
| INSP-Sprinkler Rough-in/Hydro | 9/22/2008 | 9/22/2008 | 9/22/2008 5:47:40 PM | P | FAIL |
|
|
OH rough-in failed due to missing SW head at an overhead door, blocked upright by deck insulation, incorrect head types at the paint storage and mixing room, overspaced pendent at the dry goods storage room, need to install flex couplings at the riser per key note #16 on plans. See annotations on stamped plan set.
|
FIR07-00928
| INSP-Sprinkler Rough-in/Hydro | 9/22/2008 | 9/22/2008 | 9/22/2008 5:43:05 PM | P | FAIL |
|
|
SW heads at balconies must meet obstruction criteria or additonal coverage needs to be provided.
|
FIR08-00239
| INSP-Sprinkler Rough-in/Hydro | 9/19/2008 | 9/22/2008 | 9/22/2008 5:41:51 PM | A | FAIL |
|
|
See areas on approved plan for locations inspected today and items in need of revision at the dry system and 4th floor wet system west side. Noted two missing EQ braces, one blocked upright head, two heads exceeding min. spacing, one overspaced pendent, exterior balconies and patios are not protected, tenting at some locations needs adjusted, field changes at the lobby, stair and elevator hoistway need to be shown on as-built drawings, two noted concealed spaces must be non-combustible or protected.
|
FIR07-00827
| INSP-Sprinkler Rough-in | 9/19/2008 | 9/22/2008 | 9/22/2008 5:30:01 PM | A | NH |
|
|
Contractor not available on site.
|