FIR09-00165
| INSP-Final Inspection | 9/22/2009 | 9/22/2009 | 9/25/2009 5:04:12 PM | P | FAIL |
|
|
Inspection items for final per notes 9/22 include new batteries at the main FACP, post a current map with accurate floorplan and zone descriptors, install and test a missing smoke detector at the first floor vestibule, provide list of signals recieved at offsite monitoring from this day's testing, new/existing horn strobes are not in sync- second floor elevator lobby and corridors.
|
FIR09-00502
| INSP-Final Inspection | 9/22/2009 | 9/22/2009 | 9/24/2009 10:18:58 AM | P | PART |
|
|
Mark Phone #: ###-####
|
FIR09-00213
| INSP-Final Inspection | 9/22/2009 | 9/22/2009 | 9/23/2009 6:37:01 AM | P | CANC |
|
|
CONTACT: RAFE Phone #: ###-#### Internet Inspection Request from: Deb Gooden Inspection cancelled from web by: Deb Gooden
|
FIR09-00224
| INSP-Final Inspection | 9/22/2009 | 9/22/2009 | 9/23/2009 6:36:59 AM | P | CANC |
|
|
CONTACT: RAFE Phone #: ###-#### Internet Inspection Request from: Deb Gooden Inspection cancelled from web by: Deb Gooden
|
FIR09-00222
| INSP-Final Inspection | 9/22/2009 | 9/22/2009 | 9/23/2009 6:36:57 AM | P | CANC |
|
|
CONTACT: RAFE Phone #: ###-#### Internet Inspection Request from: Deb Gooden Inspection cancelled from web by: Deb Gooden
|
BLD09-01567
| FIRE-Final Inspection | 9/21/2009 | 9/22/2009 | 9/22/2009 2:43:42 PM | A | FAIL |
|
|
Missing building address numbers, door hardware at several locations is not compliant including the main entry/exit office door, noted bare electrical wiring and open junction boxes at some locations, extension cords are not to be used for permanent power sources to equipment, missing floorplan to accurately indicate building layout including service, storage and mezzanine areas, paper faced insulation at the deck is not compliant, suggest further plan review to help determine min. requirements for occupancy.
|
FIR09-00550
| INSP-Final Inspection | 9/22/2009 | 9/22/2009 | 9/22/2009 1:42:24 PM | P | FAIL |
|
|
Relocated heads at one room NE corner must match response type.
|
BLD09-00468
| FIRE-Final Inspection | 9/21/2009 | 9/22/2009 | 9/22/2009 1:05:11 PM | A | FAIL |
|
|
Project related fire alarm permit needs requested for inspection and approval prior to building life safety, repair two exit signs at the main entry/exit doors north and south, provide missing fire extinguisher and post as discussed, repair door closure at the north set of fire doors, sprinkler coverage at the reception area is obstructed.
|
FIR09-00394
| INSP-Final Inspection | 9/21/2009 | 9/22/2009 | 9/22/2009 1:01:32 PM | A | FAIL |
|
|
Millwork at the reception "area 102" obstructs sprinkler coverage, remainder of install passed, previous C/N items are finished.
|
BLD09-00708
| FIRE-Final Inspection | 9/21/2009 | 9/22/2009 | 9/22/2009 11:21:52 AM | A | FAIL |
|
|
Need to remove the manual thumbturn at the main entry/exit door, remiander of fire life safety items okayed.
|
BLD09-00695
| FIRE-Final Inspection | 9/21/2009 | 9/22/2009 | 9/22/2009 11:19:45 AM | A | PASS |
|
|
Vanilla permit fire life safety passed final inspection.
|