Inspections for the day of: Tuesday, September 22, 2015.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE15-02540 Final9/21/20159/22/20159/22/2015 2:35:22 PMPPASS
no access until 2pm please call prior to arrival Phone #: ###-#### Inspection requested via web by Patrick Paz Final ok
ELE15-03026 Permanent Service9/22/20159/22/20159/22/2015 2:11:43 PMPFAIL
Lockbox access code: 2630. Please call Eric Schroeder ###-#### as you are headed that way. He would like to meet you there. Phone #: ###-#### Inspection requested via web by Eric Schroeder
*For service reconnect grounding of service shall be up to present code requirements. 250.53(A)(2)- A single pipe grounding electrode shall be supplemented by an additional rod.
250.68(C)(1)- Underground interior metal water pipe shall be connected within 5' of point of entrance.
408.7- Unused circuit breaker openings shall be closed
ELE15-03028 Final9/22/20159/22/20159/22/2015 1:11:41 PMPPASS
service off over 1 year; Celena Phone #: ###-#### Service reconnect and 50 amp RV receptacle. Final ok
ELE15-03028 Permanent Service9/22/20159/22/20159/22/2015 1:11:07 PMPPASS
service off over 1 year; Celena Phone #: ###-#### p/s u/g rec ok
ELE15-02908 Permanent Service9/21/20159/22/20159/22/2015 11:31:24 AMAPASS
We are requesting a service inspection for tomorrow 9/22/15 in the AM. Our onsite contact is Rod @ ###-####. Thank you Phone #: ###-#### Inspection requested via web by Clint Tate p/s u/g n ok
ELE15-02035 Final9/21/20159/22/20159/22/2015 9:40:06 AMAFAIL
Call for access code - Roger Phone #: ###-#### 210.8(B)(5)- All 120 volt 15 and 20 amp receptacle outlets installed within 6' of a sink shall have GFCI protection.
ELE15-02545 Final9/22/20159/22/20159/22/2015 9:27:44 AMPPART
Need pertial final for fitting rooms. ###-#### Final for fitting rooms ok
ELE15-02926 Temporary Service9/21/20159/22/20159/22/2015 8:54:34 AMAPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn t/s u/g n ok
ELE15-02680 Electrical Rough-In9/21/20159/22/20159/22/2015 8:09:31 AMACANC
We are requesting a final inspection for the fitting rooms only for tomorrow 9/22/15 in the AM - if possible between 7am ; 8:30am. Our onsite contact is Luke @ ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Clint Tate Wrong permit requested