ELE15-02540
| Final | 9/21/2015 | 9/22/2015 | 9/22/2015 2:35:22 PM | P | PASS |
|
|
no access until 2pm please call prior to arrival Phone #: ###-#### Inspection requested via web by Patrick Paz Final ok
|
ELE15-03026
| Permanent Service | 9/22/2015 | 9/22/2015 | 9/22/2015 2:11:43 PM | P | FAIL |
|
|
Lockbox access code: 2630. Please call Eric Schroeder ###-#### as you are headed that way. He would like to meet you there. Phone #: ###-#### Inspection requested via web by Eric Schroeder *For service reconnect grounding of service shall be up to present code requirements. 250.53(A)(2)- A single pipe grounding electrode shall be supplemented by an additional rod. 250.68(C)(1)- Underground interior metal water pipe shall be connected within 5' of point of entrance. 408.7- Unused circuit breaker openings shall be closed
|
ELE15-03028
| Final | 9/22/2015 | 9/22/2015 | 9/22/2015 1:11:41 PM | P | PASS |
|
|
service off over 1 year; Celena Phone #: ###-#### Service reconnect and 50 amp RV receptacle. Final ok
|
ELE15-03028
| Permanent Service | 9/22/2015 | 9/22/2015 | 9/22/2015 1:11:07 PM | P | PASS |
|
|
service off over 1 year; Celena Phone #: ###-#### p/s u/g rec ok
|
ELE15-02908
| Permanent Service | 9/21/2015 | 9/22/2015 | 9/22/2015 11:31:24 AM | A | PASS |
|
|
We are requesting a service inspection for tomorrow 9/22/15 in the AM. Our onsite contact is Rod @ ###-####. Thank you Phone #: ###-#### Inspection requested via web by Clint Tate p/s u/g n ok
|
ELE15-02035
| Final | 9/21/2015 | 9/22/2015 | 9/22/2015 9:40:06 AM | A | FAIL |
|
|
Call for access code - Roger Phone #: ###-#### 210.8(B)(5)- All 120 volt 15 and 20 amp receptacle outlets installed within 6' of a sink shall have GFCI protection.
|
ELE15-02545
| Final | 9/22/2015 | 9/22/2015 | 9/22/2015 9:27:44 AM | P | PART |
|
|
Need pertial final for fitting rooms. ###-#### Final for fitting rooms ok
|
ELE15-02926
| Temporary Service | 9/21/2015 | 9/22/2015 | 9/22/2015 8:54:34 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn t/s u/g n ok
|
ELE15-02680
| Electrical Rough-In | 9/21/2015 | 9/22/2015 | 9/22/2015 8:09:31 AM | A | CANC |
|
|
We are requesting a final inspection for the fitting rooms only for tomorrow 9/22/15 in the AM - if possible between 7am ; 8:30am. Our onsite contact is Luke @ ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Clint Tate Wrong permit requested
|