ELE16-02827
| Final | 9/21/2016 | 9/22/2016 | 9/22/2016 2:33:02 PM | P | PASS |
|
|
DA Davidson space Phone #: ###-#### Inspection requested via web by steve ragan This space actually marked 1800 other tenant in 1801. No one knows where future 1803 will be. Attached to BLD16-02961. Wall dividing individual offices in 1800 Final ok
|
ELE16-02981
| Electrical Rough-In | 9/21/2016 | 9/22/2016 | 9/22/2016 2:13:40 PM | P | PASS |
|
|
In lobby, left of elevator lobby, concierge area Phone #: ###-#### Inspection requested via web by steve ragan Permit mislabelled. 1st floor unit 110 Correct BLD. Wall rough in ok cover
|
ELE16-01750
| Final | 9/21/2016 | 9/22/2016 | 9/22/2016 1:41:13 PM | P | PART |
|
|
Randy. Phone #: ###-#### Inspection requested via web by Sean DeLacy All equipment shall be present for final. Check GFCI protection on customer side of bar, some were some were not. Temp final for training
|
ELE16-01838
| Final | 9/21/2016 | 9/22/2016 | 9/22/2016 12:27:19 PM | A | FAIL |
|
|
Level 3 Stack 1,2,3,4 Power Branch Circuit Panels, Equip. Conn., Outlets, Office Furniture. LV Systems Phone #: ###-#### Inspection requested via web by Tom Betty 110.3- Furniture connections between each piece shall be complete. Panel 31A 21, 23, 25 not working. 31A 13, 15, 17 not working. 300.15- All boxes installed shall have covers. Low volt card reader, internet interface, misc. 300.15- Funiture covers missing and loose. 300.21- All penetrations in firewalls shall be sealed electrical and non electrical. 392.60- Cable trays and ladder racks bonding shall be complete. 422.30- Hardwired appliances shall have a disconnecting means. 110.25 lock out acceptable. 605.5- Office furniture installation shall be complete. Misc. not connected and level 3 stack 1 no furniture installed
|
ELE16-01838
| Conference | 9/22/2016 | 9/22/2016 | 9/22/2016 12:25:55 PM | P | DONE |
|
|
Level 3 Stack 1,2,3,4 Power Branch Circuit Panels, Equip. Conn., Outlets, Office Furniture. LV Systems Phone #: ###-#### Inspection requested via web by Tom Betty Levels 2 and 3 stack 1, 2, 3, 4 lighting complete.
|
ELE15-01348
| Final | 9/21/2016 | 9/22/2016 | 9/22/2016 12:24:27 PM | A | FAIL |
|
|
Level 3 Stack 1,2,3,4 Power Electrical Rooms, Restrooms, IDF Rooms, Vestibules. Branch Circuit Panels and Circuits to Equip, outlets, Phone #: ###-#### Inspection requested via web by Tom Betty 110.3- Furniture connections between each piece shall be complete. Panel 31A 21, 23, 25 not working. 31A 13, 15, 17 not working. 300.15- All boxes installed shall have covers. Low volt card reader, internet interface, misc. 300.15- Funiture covers missing and loose. 300.21- All penetrations in firewalls shall be sealed electrical and non electrical. 392.60- Cable trays and ladder racks bonding shall be complete. 422.30- Hardwired appliances shall have a disconnecting means. 110.25 lock out acceptable. 605.5- Office furniture installation shall be complete. Misc. not connected and level 3 stack 1 no furniture installed
|
ELE16-02723
| Final | 9/21/2016 | 9/22/2016 | 9/22/2016 9:25:17 AM | A | PASS |
|
|
Sam is Contact Phone #: ###-#### Inspection requested via web by Lori Stout No card posted. Final ok
|
ELE16-02009
| Final | 9/22/2016 | 9/22/2016 | 9/22/2016 8:46:00 AM | A | PASS |
|
|
Lock box code 6363
Phone #: ###-#### Inspection requested via web by Robert Schroder Final ok
|
ELE16-02981
| Final | 9/21/2016 | 9/22/2016 | 9/21/2016 5:05:54 PM | P | CANC |
|
|
DA Davidson space Phone #: ###-#### >> Inspection requested via web by steve ragan Inspection cancelled from web by: steve ragan
|