Inspections for the day of: Thursday, September 22, 2016.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR16-00427 INSP-Conference9/22/20169/22/20169/23/2016 11:21:40 AMPPASS
Underground flush witnessed and passed by Tim Frost. See attached email on discussion of adequate coverage of underground supply piping.
BLD16-03369 FIRE-Final Inspection9/21/20169/22/20169/22/2016 2:27:37 PMPPASS
Life safety passed. Per discussion owner is going to have the two non-functional exit signs removed prior to the building inspection.
BLD16-02267 FIRE-Final Inspection9/21/20169/22/20169/22/2016 2:10:16 PMPPASS
Life safety passed
BLD16-02323 FIRE-Final Inspection9/21/20169/22/20169/22/2016 12:50:18 PMAFAIL
Provide building address numbers, knox box and annual inspection tag for the fire extinguishers.
FIR16-00577 INSP-Final Inspection9/21/20169/22/20169/22/2016 11:26:28 AMAPART
A temporary for the fire alarm is ok per the fire dept until the knox key box has been installed.
FIR16-00406 INSP-Sprinkler Rough-in9/21/20169/22/20169/22/2016 10:09:22 AMAPASS
Remaining underground piping is ok to cover.
FIR16-00305 INSP-Sprinkler Rough-in9/22/20169/22/20169/22/2016 9:35:30 AMPCANC
Per discussion with Adam this is rescheduled for tomorrow morning
FIR16-00565 INSP-Sprinkler Rough-in9/21/20169/22/20169/22/2016 9:34:01 AMAFAIL
See the city approved plans for corrections marked in red which include incorrect tenting, lack of coverage in the toilet area, missing nailer plates, cpvc pipe to far from wall at pump/riser, lack of heat in Sun Room for the two pendants. Also piping has been covered in the Sun Room (needs tenting or dry heads) and in the Garage. Also Tim provided note about staying minimum 3' from fixtures which has not been adhered to. Piping can not be covered.
NAF16-00055 INSP-Sprinkler Rough-in/Hydro9/21/20169/22/20169/22/2016 9:30:40 AMAFAIL
Piping is not buried deep enough. It varies from 4'-2" to 4'-0". Minimum bury depth is 4'-6"
FIR16-00395 INSP-Final Inspection9/21/20169/22/20169/22/2016 7:49:07 AMAPASS
Permit finaled