FIR16-00427
| INSP-Conference | 9/22/2016 | 9/22/2016 | 9/23/2016 11:21:40 AM | P | PASS |
|
|
Underground flush witnessed and passed by Tim Frost. See attached email on discussion of adequate coverage of underground supply piping.
|
BLD16-03369
| FIRE-Final Inspection | 9/21/2016 | 9/22/2016 | 9/22/2016 2:27:37 PM | P | PASS |
|
|
Life safety passed. Per discussion owner is going to have the two non-functional exit signs removed prior to the building inspection.
|
BLD16-02267
| FIRE-Final Inspection | 9/21/2016 | 9/22/2016 | 9/22/2016 2:10:16 PM | P | PASS |
|
|
Life safety passed
|
BLD16-02323
| FIRE-Final Inspection | 9/21/2016 | 9/22/2016 | 9/22/2016 12:50:18 PM | A | FAIL |
|
|
Provide building address numbers, knox box and annual inspection tag for the fire extinguishers.
|
FIR16-00577
| INSP-Final Inspection | 9/21/2016 | 9/22/2016 | 9/22/2016 11:26:28 AM | A | PART |
|
|
A temporary for the fire alarm is ok per the fire dept until the knox key box has been installed.
|
FIR16-00406
| INSP-Sprinkler Rough-in | 9/21/2016 | 9/22/2016 | 9/22/2016 10:09:22 AM | A | PASS |
|
|
Remaining underground piping is ok to cover.
|
FIR16-00305
| INSP-Sprinkler Rough-in | 9/22/2016 | 9/22/2016 | 9/22/2016 9:35:30 AM | P | CANC |
|
|
Per discussion with Adam this is rescheduled for tomorrow morning
|
FIR16-00565
| INSP-Sprinkler Rough-in | 9/21/2016 | 9/22/2016 | 9/22/2016 9:34:01 AM | A | FAIL |
|
|
See the city approved plans for corrections marked in red which include incorrect tenting, lack of coverage in the toilet area, missing nailer plates, cpvc pipe to far from wall at pump/riser, lack of heat in Sun Room for the two pendants. Also piping has been covered in the Sun Room (needs tenting or dry heads) and in the Garage. Also Tim provided note about staying minimum 3' from fixtures which has not been adhered to. Piping can not be covered.
|
NAF16-00055
| INSP-Sprinkler Rough-in/Hydro | 9/21/2016 | 9/22/2016 | 9/22/2016 9:30:40 AM | A | FAIL |
|
|
Piping is not buried deep enough. It varies from 4'-2" to 4'-0". Minimum bury depth is 4'-6"
|
FIR16-00395
| INSP-Final Inspection | 9/21/2016 | 9/22/2016 | 9/22/2016 7:49:07 AM | A | PASS |
|
|
Permit finaled
|