Inspections for the day of: Friday, September 22, 2017.
Number of inspections: 19
Percentage of inspections complete: 89 %
Percentage of inspections not complete: 11 %
Contact Information
InspectorMike Jordan
TitleBLD-COM/RES INSPECTOR
Phone #794-9473
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD17-01449 BLD-Conference9/22/20179/22/20179/22/2017 4:36:29 PMPDONE
Jim Phone #: ###-####. Reviewed UL listing for 3M putty pads for membrane protection of 3hr. fire barier wall. Per the listing, The puuty pads will only achieve a maxiumum of 2hr rating. Contractor will pursue with 3m on getting an engineer judgement for alternate to achieve the 3hr. rating and submit to building official for approval.
BLD17-02189 BLD-Ceiling Grid Inspection9/22/20179/22/20179/22/2017 2:32:38 PMPPASS
Please call Nic a half hour before inspection. Phone #: ###-#### Inspection requested via web by Nic van Diepen
BLD16-02758 BLD-Foundation9/22/20179/22/20179/22/2017 2:11:08 PMPPASS
Sam-foundation-insulation Phone #: ###-####
BLD16-02759 BLD-Foundation9/22/20179/22/20179/22/2017 2:10:58 PMPPASS
Sam-foundation-insulation Phone #: ###-####
BLD16-04474 BLD-Foundation9/22/20179/22/20179/22/2017 2:10:48 PMPPASS
Sam-foundation-insulation Phone #: ###-####
BLD16-04473 BLD-Foundation9/22/20179/22/20179/22/2017 2:10:12 PMPPASS
Sam-foundation-insulation Phone #: ###-####
BLD17-03408 BLD-Final9/22/20179/22/20179/22/2017 1:26:44 PMPDONE
Phone #: ###-#### Inspection requested via web by Scott Tennant
BLD17-03408 DOC - Permit Finaled9/22/20179/22/20179/22/2017 1:26:25 PMPPASS
All work appeared to be done in accordance with local codes and ordinances
BLD16-02949 BLD-Aging Inspection9/22/20179/22/20179/22/2017 9:16:29 AM PEND
Pending fire.
BLD16-02950 BLD-Aging Inspection9/22/20179/22/20179/22/2017 9:16:13 AM PEND
Pending fire.
BLD17-03105 BLD-Framing/Rough-in9/21/20179/22/20179/22/2017 9:11:46 AMAPASS
Matt Phone #: ###-####. Interior steel stud frmaed wall ok.
ESC17-00708 Site Final9/22/20179/22/20179/22/2017 8:48:31 AMADONE
ESC17-00708 DOC - Permit Finaled9/22/20179/22/20179/22/2017 8:48:23 AMPPASS
BLD17-01801 BLD-Final9/21/20179/22/20179/22/2017 8:48:15 AMAPASS
Phone #: ###-#### Inspection requested via web by Tom Wells. Driveway and landiings have been placed.
BLD17-01801 DOC - Permit Finaled9/22/20179/22/20179/22/2017 8:47:50 AMPPASS
BLD17-02066 BLD-Footing9/21/20179/22/20179/22/2017 8:20:18 AMAPASS
Please schedule for first thing AM. Interior shovel footings before Flatwork pour.

Phone #: ###-#### Inspection requested via web by Joel Hirtle. Interior thickend footings ok.
BLD17-01140 BLD-Footing9/21/20179/22/20179/22/2017 12:00:00 AMACANC
will have special inspection from MTI on site Phone #: ###-#### >> Inspection requested via web by Cassandra Hessing
MIS17-00248 BLD-Conference8/22/20179/22/2017 A 
Check on status...
BLD17-01388 BLD-Foundation9/21/20179/22/2017 P 
Rebar // Ross Phone #: ###-####