Inspections for the day of: Friday, September 22, 2017.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR17-00542 INSP-Sprinkler Rough-in9/22/20179/22/20179/22/2017 1:41:33 PMPCANC
Underground supply not ready to inspect, inspection request will be reschedule for a later date, this request is cancelled.
FIR16-00606 INSP-Sprinkler Rough-in/Hydro9/22/20179/22/20179/22/2017 1:40:07 PMPPASS
24 hour air test complete
FIR16-00586 INSP-Sprinkler Rough-in/Hydro9/22/20179/22/20179/22/2017 1:39:47 PMPPASS
24 hour air test complete
FIR17-00542 INSP-Supply line flush9/22/20179/22/20179/22/2017 1:39:26 PMPCANC
Underground Rough-In Phone #: ###-#### Inspection requested via web by Connie Danes
FIR17-00531 INSP-Sprinkler Rough-in9/22/20179/22/20179/22/2017 12:40:59 PMPPASS
Rough to cover inspection for overhead fire sprinkler piping for area of work complete, area of work approved for cover. Cooler to be installed at a later date.
BLD17-01815 FIRE-Final Inspection9/22/20179/22/20179/22/2017 12:25:25 PMACANC
Called point of contact provided two times, Mike McHargue Phone #: ###-####, message was left on voicemail. Proceeded to tenant space for inspection, tenant space was locked with no access, life fire safety inspection will need to be rescheduled, this request is cancelled.
BLD17-02754 FIRE-Conference9/21/20179/22/20179/22/2017 12:04:36 PMADONE
Fire conference complete
FIR17-00515 INSP-Sprinkler Rough-in9/21/20179/22/20179/22/2017 11:54:50 AMACANC
Contact Brad Westbrook ###-#### 30 min prior to RCT Insp start please.
Please change the Insp code if this can be finaled...

Thank YOU Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank
BLD14-03139 FIRE-Conference9/21/20179/22/20179/22/2017 11:30:34 AMADONE
Fire conference complete
BLD16-02414 FIRE-Final Inspection9/22/20179/22/20179/22/2017 10:29:57 AMPPART
Partial final life fire safety inspection complete, fire alarms have been tested/inspected (FIR permit for fire alarms is in the received status, fire alarm inspection authorized by Scott Arellano), fire sprinkler inspection complete. TCO authorized for life fire safety contingent on fire alarm permit being issued and finaled for inspection.
FIR16-00786 INSP-Final Inspection9/22/20179/22/20179/22/2017 10:22:34 AMPPASS
Final fire sprinkler inspection passed/complete.
FIR16-00789 INSP-Sprinkler Rough-in9/21/20179/22/20179/22/2017 10:22:00 AMAPASS
Rough to cover inspection for overhead fire sprinkler piping/tenting complete, approved for cover.
FIR17-00444 INSP-Final Inspection9/20/20179/22/20179/22/2017 9:08:19 AMAPASS
As-builts are complete, final fire alarm inspection passed/complete.
FIR16-00508 INSP-Sprinkler Rough-in9/22/20179/22/20179/22/2017 8:33:00 AMAFAIL
Multiple hangers are overspaced in garage area's, garage area's are not approved for cover, any cover material installed that blocks the veiw of fire sprinkler piping/hangers will be removed for follow up inspection.
FIR16-00508 INSP-Sprinkler Rough-in9/21/20179/22/20179/22/2017 8:30:15 AMAPART
Rough to cover inspection for overhead fire sprinkler piping/tenting on level 2 complete, level 2 approved for cover. Level 1 apartment on east side approved for cover.