FIR17-00542
| INSP-Sprinkler Rough-in | 9/22/2017 | 9/22/2017 | 9/22/2017 1:41:33 PM | P | CANC |
|
|
Underground supply not ready to inspect, inspection request will be reschedule for a later date, this request is cancelled.
|
FIR16-00606
| INSP-Sprinkler Rough-in/Hydro | 9/22/2017 | 9/22/2017 | 9/22/2017 1:40:07 PM | P | PASS |
|
|
24 hour air test complete
|
FIR16-00586
| INSP-Sprinkler Rough-in/Hydro | 9/22/2017 | 9/22/2017 | 9/22/2017 1:39:47 PM | P | PASS |
|
|
24 hour air test complete
|
FIR17-00542
| INSP-Supply line flush | 9/22/2017 | 9/22/2017 | 9/22/2017 1:39:26 PM | P | CANC |
|
|
Underground Rough-In Phone #: ###-#### Inspection requested via web by Connie Danes
|
FIR17-00531
| INSP-Sprinkler Rough-in | 9/22/2017 | 9/22/2017 | 9/22/2017 12:40:59 PM | P | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping for area of work complete, area of work approved for cover. Cooler to be installed at a later date.
|
BLD17-01815
| FIRE-Final Inspection | 9/22/2017 | 9/22/2017 | 9/22/2017 12:25:25 PM | A | CANC |
|
|
Called point of contact provided two times, Mike McHargue Phone #: ###-####, message was left on voicemail. Proceeded to tenant space for inspection, tenant space was locked with no access, life fire safety inspection will need to be rescheduled, this request is cancelled.
|
BLD17-02754
| FIRE-Conference | 9/21/2017 | 9/22/2017 | 9/22/2017 12:04:36 PM | A | DONE |
|
|
Fire conference complete
|
FIR17-00515
| INSP-Sprinkler Rough-in | 9/21/2017 | 9/22/2017 | 9/22/2017 11:54:50 AM | A | CANC |
|
|
Contact Brad Westbrook ###-#### 30 min prior to RCT Insp start please. Please change the Insp code if this can be finaled...
Thank YOU Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank
|
BLD14-03139
| FIRE-Conference | 9/21/2017 | 9/22/2017 | 9/22/2017 11:30:34 AM | A | DONE |
|
|
Fire conference complete
|
BLD16-02414
| FIRE-Final Inspection | 9/22/2017 | 9/22/2017 | 9/22/2017 10:29:57 AM | P | PART |
|
|
Partial final life fire safety inspection complete, fire alarms have been tested/inspected (FIR permit for fire alarms is in the received status, fire alarm inspection authorized by Scott Arellano), fire sprinkler inspection complete. TCO authorized for life fire safety contingent on fire alarm permit being issued and finaled for inspection.
|
FIR16-00786
| INSP-Final Inspection | 9/22/2017 | 9/22/2017 | 9/22/2017 10:22:34 AM | P | PASS |
|
|
Final fire sprinkler inspection passed/complete.
|
FIR16-00789
| INSP-Sprinkler Rough-in | 9/21/2017 | 9/22/2017 | 9/22/2017 10:22:00 AM | A | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping/tenting complete, approved for cover.
|
FIR17-00444
| INSP-Final Inspection | 9/20/2017 | 9/22/2017 | 9/22/2017 9:08:19 AM | A | PASS |
|
|
As-builts are complete, final fire alarm inspection passed/complete.
|
FIR16-00508
| INSP-Sprinkler Rough-in | 9/22/2017 | 9/22/2017 | 9/22/2017 8:33:00 AM | A | FAIL |
|
|
Multiple hangers are overspaced in garage area's, garage area's are not approved for cover, any cover material installed that blocks the veiw of fire sprinkler piping/hangers will be removed for follow up inspection.
|
FIR16-00508
| INSP-Sprinkler Rough-in | 9/21/2017 | 9/22/2017 | 9/22/2017 8:30:15 AM | A | PART |
|
|
Rough to cover inspection for overhead fire sprinkler piping/tenting on level 2 complete, level 2 approved for cover. Level 1 apartment on east side approved for cover.
|