Inspections for the day of: Monday, September 23, 2002.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR02-00244 INSP-Final Inspection9/20/20029/23/20029/23/2002 12:00:00 AMAPART
temporary occupancy was given for the sprinkler system, with dave millers permission. Several sprinkler heads are spaced too close. When the owner occupies the storage cabinets will be built to the ceiling to separate sprinklers 9/23/2002 10:05:39 AM
BLD02-00097 FIRE-Final Inspection9/22/20029/23/20029/23/2002 12:00:00 AMAFAIL
fire extinguishers on the gas islands need to have the correct inspection tags. all other items on the correction notice have been corrected 9/23/2002 3:50:10 PM
FIR02-00349 INSP-Final Inspection9/23/20029/23/20029/23/2002 12:00:00 AMPPASS
fire sprinkler finaled 9/23/2002 3:00:12 PM
BLD02-01300 FIRE-Final Inspection9/23/20029/23/20029/23/2002 12:00:00 AMPPASS
fire life safety finaled
FIR02-00070 INSP-Final Inspection9/18/20029/23/20029/23/2002 12:00:00 AMPFAIL
relocate the electric alarm bell to the fdc location, provide a dedicated non switched circuit for the air compressor, provide enclosures for the duct detectors. Test the dry pipe system for signals. 9/23/2002 3:31:47 PM 9/23/2002 3:37:39 PM