ELE04-02739
| Electrical Rough-In | 9/22/2004 | 9/23/2004 | 9/23/2004 12:00:00 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 9/22/2004 at 11:08:45 AM. Contact: ###-####. ceilings ok 9/23/2004 10:07:27 AM
|
ELE04-02882
| Conference | 9/22/2004 | 9/23/2004 | 9/23/2004 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 9/22/2004 at 1:01:47 PM. Contact: ###-####. ok 9/23/2004 8:40:23 AM
|
ELE04-02882
| Final | 9/22/2004 | 9/23/2004 | 9/23/2004 12:00:00 AM | A | PASS |
|
|
dwayne ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok 9/23/2004 8:40:36 AM
|
ELE04-02349
| Final | 9/22/2004 | 9/23/2004 | 9/23/2004 12:00:00 AM | A | NR |
|
|
george temp occ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie called 9/23/2004 10:30:39 AM
|
ELE04-02842
| Permanent Service | 9/22/2004 | 9/23/2004 | 9/23/2004 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 9/22/2004 at 4:58:51 PM. Contact: ###-####. p/s o/h rec. ok 9/23/2004 9:03:12 AM
|
ELE04-02732
| Rough-In Permanent Service | 9/22/2004 | 9/23/2004 | 9/23/2004 12:00:00 AM | A | PASS |
|
|
We extended the 30 amp 220 volt welder circuit out to a disconnect for the air conditioner and connected the AC into this disconnect.Then discovered that the welder circuit was NOT wired into the panel,customer did not want to spend any more money so we stopped.Thanks!!!Dan.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell ok 9/23/2004 9:32:40 AM
|
ELE04-02608
| Permanent Service | 9/23/2004 | 9/23/2004 | 9/23/2004 12:00:00 AM | P | FAIL |
|
|
THEY ARE POURING CONCRETE ON THE #4 WIRE THIS MORNING. Internet Inspection Request from: Bob Glenn electrode ok for cover only , they have not poured the concrete yet called 9/23/2004 12:21:40 PM
|
ELE04-02922
| Temporary Service | 9/23/2004 | 9/23/2004 | 9/23/2004 12:00:00 AM | P | PASS |
|
|
Internet Inspection Request from: Bob Glenn t/s u/g new ok 9/23/2004 11:09:29 AM
|
ELE04-02914
| Temporary Service | 9/23/2004 | 9/23/2004 | 9/23/2004 12:00:00 AM | P | PASS |
|
|
Internet Inspection Request from: Bob Glenn t/s u/g new ok 9/23/2004 11:09:44 AM
|
ELE04-02910
| Temporary Service | 9/23/2004 | 9/23/2004 | 9/23/2004 12:00:00 AM | P | PASS |
|
|
Internet Inspection Request from: Bob Glenn t/s u/g new ok 9/23/2004 11:09:57 AM
|
ELE04-02909
| Temporary Service | 9/23/2004 | 9/23/2004 | 9/23/2004 12:00:00 AM | P | PASS |
|
|
Internet Inspection Request from: Bob Glenn t/s u/g new ok 9/23/2004 11:10:11 AM
|
ELE04-02923
| Temporary Service | 9/23/2004 | 9/23/2004 | 9/23/2004 12:00:00 AM | P | PASS |
|
|
Internet Inspection Request from: Bob Glenn t/s u/g new ok 9/23/2004 11:10:25 AM
|
ELE04-02458
| Electrical Rough-In | 9/23/2004 | 9/23/2004 | 9/23/2004 12:00:00 AM | P | PART |
|
|
Scheduled by a contractor via Hello! on 9/23/2004 at 8:03:49 AM. Contact: ###-####. u/g ok 9/23/2004 4:06:10 PM
|
ELE04-02924
| Permanent Service | 9/23/2004 | 9/23/2004 | 9/23/2004 12:00:00 AM | P | FAIL |
|
|
Please call 20 mins prior to inspection so he can meet ya there///###-#### bob ###-#### rock called trench cover before inspection , does not look like u/g has proper depth for under driveway 9/23/2004 1:17:52 PM
|
ELE04-02916
| Final | 9/23/2004 | 9/23/2004 | 9/23/2004 12:00:00 AM | P | PART |
|
|
Thank you ; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH walls rest rm areas ok talked to electricians, bond bushing RE washers, grd for x-former to 1st 5 ft of water system bond to sprinkler system bond hot and cold at all W Heaters, remove shelves for clearence in front of gear 9/23/2004 3:35:28 PM
|
ELE04-02064
| Final | 9/23/2004 | 9/23/2004 | 9/23/2004 12:00:00 AM | P | PASS |
|
|
dan; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok card signed 9/23/2004 1:14:38 PM
|
ELE04-02763
| Final | 9/23/2004 | 9/23/2004 | 9/23/2004 12:00:00 AM | P | PASS |
|
|
Thank You ; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH ok card signed needs #12 cord, or hard wire refer case survey 9/23/2004 1:57:04 PM
|
ELE04-02791
| Final | 9/23/2004 | 9/23/2004 | 9/23/2004 12:00:00 AM | P | PASS |
|
|
renee; Phone #: ###-#### Internet Inspection Request from: Barbara Moore see added p/s 9/23/2004 4:25:52 PM
|
ELE04-02582
| Final | 9/23/2004 | 9/23/2004 | 9/23/2004 12:00:00 AM | P | PASS |
|
|
sign ok
|
ELE04-02791
| Permanent Service | 9/23/2004 | 9/23/2004 | 9/23/2004 12:00:00 AM | P | PASS |
|
|
p/s u/g new ok
|
ELE04-02900
| Rough-In Permanent Service | 9/22/2004 | 9/23/2004 | 9/23/2004 12:00:00 AM | P | FAIL |
|
|
We:1)bonded the hot tub and created a bonding grid.2)GFCI protected the hot tub and pool.3)GFCI protected the lights around the hot tub.4)GFCI protected the kitchen receptacles.5)GFCI protected the bath room receptacles.6)GFCI protected the outdoor receptacles.7)installed his new range hood.Thanks!!!Dan.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchellcor. posted called 680.43(C) switches too close to tub, 250.8 NO SMS , 210.8 recepts left and right of kit. sink no gfci, 680.26(C) SSsteel , brass, copper,or copper alloy for bonding lugs 9/23/2004 2:46:22 PM
|