Inspections for the day of: Thursday, September 23, 2004.
Number of inspections: 21
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE04-02739 Electrical Rough-In9/22/20049/23/20049/23/2004 12:00:00 AMAPART
Scheduled by a contractor via Hello! on 9/22/2004 at 11:08:45 AM. Contact: ###-####. ceilings ok 9/23/2004 10:07:27 AM
ELE04-02882 Conference9/22/20049/23/20049/23/2004 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 9/22/2004 at 1:01:47 PM. Contact: ###-####. ok 9/23/2004 8:40:23 AM
ELE04-02882 Final9/22/20049/23/20049/23/2004 12:00:00 AMAPASS
dwayne ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok 9/23/2004 8:40:36 AM
ELE04-02349 Final9/22/20049/23/20049/23/2004 12:00:00 AMANR
george temp occ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie called 9/23/2004 10:30:39 AM
ELE04-02842 Permanent Service9/22/20049/23/20049/23/2004 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 9/22/2004 at 4:58:51 PM. Contact: ###-####. p/s o/h rec. ok 9/23/2004 9:03:12 AM
ELE04-02732 Rough-In Permanent Service9/22/20049/23/20049/23/2004 12:00:00 AMAPASS
We extended the 30 amp 220 volt welder circuit out to a disconnect for the air conditioner and connected the AC into this disconnect.Then discovered that the welder circuit was NOT wired into the panel,customer did not want to spend any more money so we stopped.Thanks!!!Dan.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell ok 9/23/2004 9:32:40 AM
ELE04-02608 Permanent Service9/23/20049/23/20049/23/2004 12:00:00 AMPFAIL
THEY ARE POURING CONCRETE ON THE #4 WIRE THIS MORNING. Internet Inspection Request from: Bob Glenn electrode ok for cover only , they have not poured the concrete yet called 9/23/2004 12:21:40 PM
ELE04-02922 Temporary Service9/23/20049/23/20049/23/2004 12:00:00 AMPPASS
Internet Inspection Request from: Bob Glenn t/s u/g new ok 9/23/2004 11:09:29 AM
ELE04-02914 Temporary Service9/23/20049/23/20049/23/2004 12:00:00 AMPPASS
Internet Inspection Request from: Bob Glenn t/s u/g new ok 9/23/2004 11:09:44 AM
ELE04-02910 Temporary Service9/23/20049/23/20049/23/2004 12:00:00 AMPPASS
Internet Inspection Request from: Bob Glenn t/s u/g new ok 9/23/2004 11:09:57 AM
ELE04-02909 Temporary Service9/23/20049/23/20049/23/2004 12:00:00 AMPPASS
Internet Inspection Request from: Bob Glenn t/s u/g new ok 9/23/2004 11:10:11 AM
ELE04-02923 Temporary Service9/23/20049/23/20049/23/2004 12:00:00 AMPPASS
Internet Inspection Request from: Bob Glenn t/s u/g new ok 9/23/2004 11:10:25 AM
ELE04-02458 Electrical Rough-In9/23/20049/23/20049/23/2004 12:00:00 AMPPART
Scheduled by a contractor via Hello! on 9/23/2004 at 8:03:49 AM. Contact: ###-####. u/g ok 9/23/2004 4:06:10 PM
ELE04-02924 Permanent Service9/23/20049/23/20049/23/2004 12:00:00 AMPFAIL
Please call 20 mins prior to inspection so he can meet ya there///###-#### bob ###-#### rock called trench cover before inspection , does not look like u/g has proper depth for under driveway 9/23/2004 1:17:52 PM
ELE04-02916 Final9/23/20049/23/20049/23/2004 12:00:00 AMPPART
Thank you ; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH walls rest rm areas ok talked to electricians, bond bushing RE washers, grd for x-former to 1st 5 ft of water system bond to sprinkler system bond hot and cold at all W Heaters, remove shelves for clearence in front of gear 9/23/2004 3:35:28 PM
ELE04-02064 Final9/23/20049/23/20049/23/2004 12:00:00 AMPPASS
dan; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok card signed 9/23/2004 1:14:38 PM
ELE04-02763 Final9/23/20049/23/20049/23/2004 12:00:00 AMPPASS
Thank You ; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH ok card signed needs #12 cord, or hard wire refer case survey 9/23/2004 1:57:04 PM
ELE04-02791 Final9/23/20049/23/20049/23/2004 12:00:00 AMPPASS
renee; Phone #: ###-#### Internet Inspection Request from: Barbara Moore see added p/s 9/23/2004 4:25:52 PM
ELE04-02582 Final9/23/20049/23/20049/23/2004 12:00:00 AMPPASS
sign ok
ELE04-02791 Permanent Service9/23/20049/23/20049/23/2004 12:00:00 AMPPASS
p/s u/g new ok
ELE04-02900 Rough-In Permanent Service9/22/20049/23/20049/23/2004 12:00:00 AMPFAIL
We:1)bonded the hot tub and created a bonding grid.2)GFCI protected the hot tub and pool.3)GFCI protected the lights around the hot tub.4)GFCI protected the kitchen receptacles.5)GFCI protected the bath room receptacles.6)GFCI protected the outdoor receptacles.7)installed his new range hood.Thanks!!!Dan.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchellcor. posted called 680.43(C) switches too close to tub, 250.8 NO SMS , 210.8 recepts left and right of kit. sink no gfci, 680.26(C) SSsteel , brass, copper,or copper alloy for bonding lugs 9/23/2004 2:46:22 PM