Inspections for the day of: Thursday, September 23, 2004.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00375 FIR-Aging Inspection9/23/20049/23/20049/23/2004 12:00:00 AM NR
wip 9/23/2004 7:46:49 AM
BLD04-01657 FIRE-Final Inspection9/22/20049/23/20049/23/2004 12:00:00 AMAFAIL
Remove clips from the pendant heads. Provide canopy for pendant over washer/dryer. Provide remote LED's for duct smoke detectors and provide approved door hardware on second store front door or remove hardware 9/23/2004 8:54:55 AM
MIS04-00201 FIR-Final9/22/20049/23/20049/23/2004 12:00:00 AMAPASS
Fire life safety finaled 9/23/2004 8:04:04 AM
MIS04-00258 FIR-Final9/22/20049/23/20049/23/2004 12:00:00 AMAPASS
OK for a temporary occupancy. They need two fire extinguishers. They need to be tagged and mounted. One at each level . 9/23/2004 12:20:58 PM
FIR03-00462 INSP-Final Inspection9/22/20049/23/20049/23/2004 12:00:00 AMPPASS
Fire sprinklers finaled 9/23/2004 12:35:14 PM
FIR04-00238 INSP-Final Inspection9/23/20049/23/20049/23/2004 12:00:00 AMPFAIL
Signals that the monitoring company are different that have been sent out, provide map at facp and drill holes for the duct detector housings 9/23/2004 12:15:56 PM
FIR04-00368 INSP-Sprinkler Rough-in9/23/20049/23/20049/23/2004 12:00:00 AMPPART
1st floor rooms are ok to cover except for the room next to the elevators where the 4" dry piping transitions to 6". Piping does not match plans here. Also the entries at the north and the west need holes patched and insulation installed before cover 9/23/2004 2:47:42 PM
BLD04-00539 FIRE-Final Inspection9/23/20049/23/20049/23/2004 12:00:00 AMPFAIL
Remove the deadbolts on all three doors and provide fire extinguishers tagged and mounted in the maintenance room 9/23/2004 1:00:42 PM
BLD04-01657 FIRE-Final Inspection9/23/20049/23/20049/23/2004 12:00:00 AMPFAIL
Duct detector remote led are wired wrong 9/23/2004 3:58:56 PM
BLD04-01657 FIRE-Final Inspection9/23/20049/23/20049/23/2004 12:00:00 AMPFAIL
Remote LED's are lit up all the time. Wiring is wrong. Rewire and test. 9/23/2004 3:25:25 PM
FIR04-00429 INSP-Sprinkler Rough-in/Hydro9/23/20049/23/20049/23/2004 12:00:00 AMPPART
sprinkler piping is ok to cover but in areas where two pendant heads are supplied from the same 1" outlet the piping needs to be modified for one outlet, one pendant 9/23/2004 4:00:04 PM
FIR04-00300 INSP-Final Inspection9/23/20049/23/20049/23/2004 12:00:00 AMPPASS
fire sprinkler finaled