FIR04-00375
| FIR-Aging Inspection | 9/23/2004 | 9/23/2004 | 9/23/2004 12:00:00 AM | | NR |
|
|
wip 9/23/2004 7:46:49 AM
|
BLD04-01657
| FIRE-Final Inspection | 9/22/2004 | 9/23/2004 | 9/23/2004 12:00:00 AM | A | FAIL |
|
|
Remove clips from the pendant heads. Provide canopy for pendant over washer/dryer. Provide remote LED's for duct smoke detectors and provide approved door hardware on second store front door or remove hardware 9/23/2004 8:54:55 AM
|
MIS04-00201
| FIR-Final | 9/22/2004 | 9/23/2004 | 9/23/2004 12:00:00 AM | A | PASS |
|
|
Fire life safety finaled 9/23/2004 8:04:04 AM
|
MIS04-00258
| FIR-Final | 9/22/2004 | 9/23/2004 | 9/23/2004 12:00:00 AM | A | PASS |
|
|
OK for a temporary occupancy. They need two fire extinguishers. They need to be tagged and mounted. One at each level . 9/23/2004 12:20:58 PM
|
FIR03-00462
| INSP-Final Inspection | 9/22/2004 | 9/23/2004 | 9/23/2004 12:00:00 AM | P | PASS |
|
|
Fire sprinklers finaled 9/23/2004 12:35:14 PM
|
FIR04-00238
| INSP-Final Inspection | 9/23/2004 | 9/23/2004 | 9/23/2004 12:00:00 AM | P | FAIL |
|
|
Signals that the monitoring company are different that have been sent out, provide map at facp and drill holes for the duct detector housings 9/23/2004 12:15:56 PM
|
FIR04-00368
| INSP-Sprinkler Rough-in | 9/23/2004 | 9/23/2004 | 9/23/2004 12:00:00 AM | P | PART |
|
|
1st floor rooms are ok to cover except for the room next to the elevators where the 4" dry piping transitions to 6". Piping does not match plans here. Also the entries at the north and the west need holes patched and insulation installed before cover 9/23/2004 2:47:42 PM
|
BLD04-00539
| FIRE-Final Inspection | 9/23/2004 | 9/23/2004 | 9/23/2004 12:00:00 AM | P | FAIL |
|
|
Remove the deadbolts on all three doors and provide fire extinguishers tagged and mounted in the maintenance room 9/23/2004 1:00:42 PM
|
BLD04-01657
| FIRE-Final Inspection | 9/23/2004 | 9/23/2004 | 9/23/2004 12:00:00 AM | P | FAIL |
|
|
Duct detector remote led are wired wrong 9/23/2004 3:58:56 PM
|
BLD04-01657
| FIRE-Final Inspection | 9/23/2004 | 9/23/2004 | 9/23/2004 12:00:00 AM | P | FAIL |
|
|
Remote LED's are lit up all the time. Wiring is wrong. Rewire and test. 9/23/2004 3:25:25 PM
|
FIR04-00429
| INSP-Sprinkler Rough-in/Hydro | 9/23/2004 | 9/23/2004 | 9/23/2004 12:00:00 AM | P | PART |
|
|
sprinkler piping is ok to cover but in areas where two pendant heads are supplied from the same 1" outlet the piping needs to be modified for one outlet, one pendant 9/23/2004 4:00:04 PM
|
FIR04-00300
| INSP-Final Inspection | 9/23/2004 | 9/23/2004 | 9/23/2004 12:00:00 AM | P | PASS |
|
|
fire sprinkler finaled
|