FIR05-00429
| INSP-Final Inspection | 9/23/2005 | 9/23/2005 | 9/23/2005 12:45:37 PM | P | CANC |
|
|
Hydrostatic test rescheduled for monday the 26th per agreement with Brian of TV sprinkler.
|
FIR05-00462
| INSP-Final Inspection | 9/22/2005 | 9/23/2005 | 9/23/2005 12:37:16 PM | P | FAIL |
|
|
The pull station installed does not match submittals and is mounted too high, provide lock at breaker to FACP, two smoke alarms are installed on a different zone than approved plans show, restroom smoke alarms report as office smoke zone 1, provide resubmittals reflecting correct zoning, phone lines, battery, smoke at panel, restroom smoke tested okay, no other items tested at this time.
|
FIR05-00473
| INSP-Sprinkler Rough-in | 9/22/2005 | 9/23/2005 | 9/23/2005 10:10:49 AM | A | PART |
|
|
Overhead sprinkler rough-in is good for cover, will final when ceiling tile and escutcheons are installed and verification is made at closet that shelving has been installed to the ceiling and a sprinkler is indeed not required.
|
BLD05-02207
| FIRE-Final Inspection | 9/22/2005 | 9/23/2005 | 9/23/2005 8:40:57 AM | A | PASS |
|
|
Fire life safety passed inspection.
|