Inspections for the day of: Wednesday, September 23, 2009.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE09-01710 Conference9/23/20099/23/20099/23/2009 4:58:56 PMPCANC
needed to look up phone number only
ESC09-00524 General Inspection9/23/20099/23/20099/23/2009 3:58:25 PMPPASS
looked ok
ELE08-02484 DOC - Permit Expired9/23/20099/23/20099/23/2009 3:53:01 PMPPASS
no activity, ok to doc expire
ELE09-01810 Final9/23/20099/23/20099/23/2009 3:50:24 PMPCANC
Phone #: ###-#### Internet Inspection Request from: Bruce Herold see t/s, no esc this project
ELE09-01810 Temporary Service9/23/20099/23/20099/23/2009 3:49:21 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Bruce Herold t/s u/g n ok, no esc this project
ESC09-00398 Random Inspection9/23/20099/23/20099/23/2009 3:30:01 PMPPASS
looked ok
ESC08-00776 General Inspection9/23/20099/23/20099/23/2009 3:29:11 PMPPASS
looked ok street side
ESC09-00379 General Inspection9/23/20099/23/20099/23/2009 3:07:43 PMPPASS
looked ok
ESC09-00360 General Inspection9/23/20099/23/20099/23/2009 2:42:03 PMPPASS
looked ok
ELE08-02826 ELE-Aging Inspection9/23/20099/23/20099/23/2009 1:56:35 PM DONE
no activity, suc, job on hold
ELE09-01809 Temporary Service9/23/20099/23/20099/23/2009 1:48:14 PMPPASS
James Phone #: ###-#### t/s u/g n ok
ELE09-01710 Electrical Rough-In9/23/20099/23/20099/23/2009 1:00:26 PMPFAIL
tim Phone #: ###-#### called, left correction notice, NEC 300.14 there shall be at least 6" free conductor length at each box, 300.4(A) shall provide steel plate if edge of bored hole is less than 1 1/4" from edge of framing member, 250.86 metal enclosures shall be grounded and connected to equipment grounding conductor, BCC shall install mud rings as required before cover
ELE09-01748 Electrical Rough-In9/22/20099/23/20099/23/2009 10:27:03 AMAFAIL
cover inspection Phone #: ###-#### Internet Inspection Request from: Jari Rivers called, left correction notice, NEC 352.26 there shall not be over 360 degrees bend in pvc raceway
ELE09-01795 Electrical Rough-In9/22/20099/23/20099/23/2009 9:55:28 AMAPASS
Classroom addition. Rough inspection Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot called contractor, ric ok
ELE09-01796 Electrical Rough-In9/22/20099/23/20099/23/2009 9:13:18 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Lloyd Looney called contractor, ric ok, no esc this project
ELE08-02248 Final9/22/20099/23/20099/23/2009 8:25:42 AMAPASS
Brian Phone #: ###-#### ok to final, signed card