Inspections for the day of: Thursday, September 23, 2010.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD10-01305 FIRE-Final Inspection9/21/20109/23/20109/24/2010 10:08:06 AMPFAIL
Replace closure at one door, switch backward hardware at one storage room door 5th floor, project related fire alarm work is not yet approved.
FIR10-00387 INSP-Final Inspection9/22/20109/23/20109/24/2010 10:05:32 AMPPASS
Scope of fire sprinkler work passed final walkthrough, permit final okay.
FIR10-00423 INSP-Final Inspection9/23/20109/23/20109/24/2010 10:04:07 AMPFAIL
Correction items include relocate three SD too close to HVAC diffusers, adjust cd setting per plan at one room 5th floor, voice evacuation message does not meet intelligibility or audibility requirements.
FIR10-00416 INSP-Final Inspection9/23/20109/23/20109/23/2010 3:58:36 PMPPASS
Overhead work passed field inspection, fire sprinkler permit final approved.
FIR09-00074 FIR-Aging Inspection9/23/20109/23/20109/23/2010 3:35:24 PM FAIL
FIR09-00075 FIR-Aging Inspection9/23/20109/23/20109/23/2010 3:34:59 PM FAIL
FIR09-00094 FIR-Aging Inspection9/23/20109/23/20109/23/2010 3:34:41 PM FAIL
FIR09-00079 FIR-Aging Inspection9/23/20109/23/20109/23/2010 3:34:21 PM FAIL
BLD10-00229 FIRE-Final Inspection9/17/20109/23/20109/23/2010 3:31:51 PMAFAIL
Provide approved door hardware at several locations, missing some permit documents on site including list of general requirements and stamped floorplan.
FIR10-00475 INSP-Final Inspection9/22/20109/23/20109/23/2010 3:29:40 PMANR
Project work is not ready for inspection at this time per conversation with contractor.
FIR10-00165 INSP-Final Inspection9/22/20109/23/20109/23/2010 3:28:26 PMAPASS
Final walkthrough passed after corrections made while on site. Permit finaled.
FIR10-00474 INSP-Final Inspection9/23/20109/23/20109/23/2010 12:44:53 PMPCANC
Jim Phone #: ###-#### Inspection cancelled from web by: Connie Danes
BLD10-02147 FIRE-Final Inspection9/21/20109/23/20109/23/2010 12:25:49 PMAPASS
Corrections field verified, fire life safety passed.